GSMV4G/GSMVCN4G Installation and Setup Guide
3-14
PROMPTS
ZONE
TRIG.
4204/
2-4204
OPTIONS
DESCRIPTION
•
(V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
•
(EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
UL:
Set V+ to inverted, and V– as non-inverted.
Inverted Trigger: Zones can be programmed for inverted trigger, where the alarm and normal states of the zones
are inverted; this can serve a fail-safe supervisory purpose for certain installations.
Restore and Delayed Reports: Zone inputs can be programmed for restore reporting, and for delayed reporting
(allowing time for the user to abort false alarms).
UL/ULC:
Zone restoral must be enabled.
Report Only if Armed option: To help eliminate redundant reports, zone alarms can be restricted to report only if
a conditional zone is triggered (armed). If this feature is desired, the conditional zone is automatically used as the
“arming” zone. Connect the appropriate control panel trigger to the conditional (arming) zone. The trigger must be
programmed as necessary in the control panel.
The conditional (arming) zone on the communicator is a different dedicated zone for each programming mode, as
follows:
Mode
Conditional (Arming) Zone
Zone Trigger
7
4204
4
2-4204
8
IMPORTANT: If any zone (zones 1-6 in zone trigger mode, zones 1-3 in 4204 mode, zones 1-7 in 2-4204 mode) is set
for Report Only if Armed, the conditional (arming) zone becomes unavailable for reporting (as it is reserved for the
“arming” trigger connection).
26
Trip Inputs 1or2
w/Bell Out (N)_
X
[Y], [N]
Use if the zone 1 connection to the control panel's
bell output causes a bell fault on the control panel.
NOTE: If used, EOLR trigger type is not available
for zones 1 and 3.
27
Telco Zone
(0)_
X
X
Zone Trig: [3-7]
4204: [1-4]
2-4204:
[1-8]
[0] = not used
See "Important Information Regarding Zone Input
Options" on previous page.
Enter the zone number to be used for Telco line
fault reports. This zone assignment must be unique
from the open/close zone selected in Prompt 28.
Zone Trigger Mode: If any zone is programmed for
"report only if armed," zone 7 cannot be used.
4204 Mode: If any zone is programmed for "report
only if armed," zone 4 cannot be used as a Telco
zone.
2-4204 Mode: If any zone is programmed for "report
only if armed," or if tamper reporting is enabled,
zone 8 cannot be used.
NOTE: Connect the Telco line fault output (or relay
output programmed for "Telco line fault") to the
Telco zone.
Summary of Contents for GSMV4G
Page 2: ......
Page 40: ...GSMV4G GSMVCN4G Installation and Setup Guide 4 4 ...
Page 46: ...GSMV4G GSMVCN4G Installation and Setup Guide 5 6 ...
Page 47: ...A 1 Appendices Appendix A Summary of LED Operation ...
Page 48: ...GSMV4G GSMVCN4G Installation and Setup Guide A 2 ...
Page 50: ...GSMV4G GSMVCN4G Installation and Setup Guide B 2 ...
Page 52: ...GSMV4G GSMVCN4G Installation and Setup Guide C 2 ...
Page 53: ...NOTES ...
Page 54: ...NOTES ...
Page 55: ...NOTES ...
Page 56: ...NOTES ...
Page 57: ...NOTES ...
Page 58: ...NOTES ...
Page 59: ...NOTES ...
Page 60: ...NOTES ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...