
GSMV4G/GSMVCN4G Installation and Setup Guide
3-6
PROMPTS
OPTIONS
DESCRIPTION
24
Old Alarm Time
10 Minutes_
•
10 Minutes
•
4 Hours
•
15 Minutes
•
8 Hours
•
30 Minutes
•
12 Hours
•
1 Hour
•
24 Hours
•
2 Hours
•
4 Hours
•
8 Hours
•
12 Hours
•
24 Hours
The old alarm time sets how long an undeliverable alarm is retried
for delivery to the central station. If the message is not validated, it
is retried until the old alarm time is reached or the message is
validated.
Press the [space] key to scroll through choices.
UL/ULC: Must be set to 10 minutes.
25
GSM Flt Time
(00 mins)_
[00-99]
[00] = not used
In the event the communicator detects a communication path
failure, enter the time delay (in minutes) before the communicator
notifies the control panel with a trouble message (and trips the
Fault Output if used; (terminal 11) see next prompt). The control
panel can then notify the central station.
UL/ULC: Must be one (01) minute.
26
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is normally energized to
ground, and de-energizes (open circuit) in the event of a
communicator fault. For conditions that trip the fault relay refer to
Supervision Features
in Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring the Fault Relay
in Section 2.
UL/ULC: Must be set to "Y."
27
Pwr Loss Rpt Y/N
(Y)_
[Y], [N]
Sends a primary power loss report to the central station within 1-3
hours after its detection. A restore report is sent within 1-3 hours
after power is restored.
UL/ULC: Must be set to "Y."
28
Low Bat Rpt Y/N
(Y)_
[Y], [N]
Sends a low-battery report when a low battery condition exists.
UL/ULC: Must be set to "Y."
29
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report when the communicator detects a tamper
condition. A tamper restore is automatically sent when the tamper
condition clears.
UL/ULC: Must be set to "Y."
Important Information Regarding Zone Input Options
ECP mode supports two optional hardwire zone input triggers by making connections to the communicator’s zone 6
and/or zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
•
(V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
•
(V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
•
(EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
UL: Set V+ to inverted, and V– as non-inverted.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for
the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed
format.
Summary of Contents for GSMV4G
Page 2: ......
Page 40: ...GSMV4G GSMVCN4G Installation and Setup Guide 4 4 ...
Page 46: ...GSMV4G GSMVCN4G Installation and Setup Guide 5 6 ...
Page 47: ...A 1 Appendices Appendix A Summary of LED Operation ...
Page 48: ...GSMV4G GSMVCN4G Installation and Setup Guide A 2 ...
Page 50: ...GSMV4G GSMVCN4G Installation and Setup Guide B 2 ...
Page 52: ...GSMV4G GSMVCN4G Installation and Setup Guide C 2 ...
Page 53: ...NOTES ...
Page 54: ...NOTES ...
Page 55: ...NOTES ...
Page 56: ...NOTES ...
Page 57: ...NOTES ...
Page 58: ...NOTES ...
Page 59: ...NOTES ...
Page 60: ...NOTES ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...