Instructions to convert S4-34404 or S4-34401

Mains switching interface units

These procedures must be followed to convert a:

S4-34404 Mains switching interface in to a legacy 34450
Interface unit that operates with a 19245-06 Power supply
unit for mains switching. For this a VSINTL-PCB on
chassis is available to replace the PCB inside a 34450
legacy interface unit.

S4-34401 Mains switching interface to a legacy 34415
Single channel (output) Interface unit used for mains
switching, this unit also has a switch input.

a.

Set the channel rotary switches on the Programmer as per
section headed 'Setting the rotary switches'.

b.

Remove terminal block

j

from the

cable assembly

supplied.

c.

Connect the L1 & 0V leads

k

of the

cable assembly

to TB6

on a S4-34404/S4-34401 Mains switching interface unit, as
illustrated. Remove the loop terminal block from the
Programmer

l

and connect the terminal block end of the

cable assembly to the loop pins

m

on the Programmer, as

illustrated.

d.

Fit the AC-DC Adaptor lead to the Interface programmer and
connect the mains plug to a mains socket

n

. Note the

programming status LED

o

on the Programmer and LED

p

on the S4-34401/S4-34404 Mains switching interface PCB.
The programming duration is approximately 10 seconds.

e.

Disconnect the

cable assembly

from the loop

pins of the programmed S4-34401/S4-34404
Mains switching interface unit and close the
door on the unit.

f.

If programming a number of
S4-34401/S4-34404 Mains switching interface
units the repeat procedures a) to e).

g.

Reconnect the previously removed terminal
block

j

to the cable assembly.

h.

When programming is finished, switch off the
mains supply and unplug the AC-DC Adaptor
from the Programmer.

A programmed S4-34404 Mains switching interface
unit can be used in place of a legacy interface
34450 having a 19245-06 Power supply unit. A
programmed S4-34401 Mains switching interface
unit can be used in place of a legacy 34415 Single
channel loop powered interface unit. Where the
interface unit is installed on a
loop circuit of an Analogue
Addressable fire detection and
alarm system.
Connect the system cables to
the programmed interface unit
and ensure the correct EOL
device(s) are fitted, where
used.

User guide

S4 Interface Programmer

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK

Website: www.gent.co.uk

Tel44 (0) 116 246 2000

Website: www.gentexpert.co.uk

Fax (UK): +44 (0)116 246 2300

4

4188-982 issue 5-3_10-13_S4 Interface progkit

by Honeywell

Do not dispose of with your normal household waste.
Do not burn.

WEEE Directive:

At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.

At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.

S4-Mains switching interface unit
(S4-34404 or S4-34401)

LED Indications

Steady green

Flashing amber

Programming

Programming complete

No power applied

Fault

(for example the S4 Interface

is not plugged in correctly)

Steady amber

Programmer

0V

L1

Flashing green

Communicating

LED Indications

L1

01

Remove
this block

Loop

terminals

TB3

NO3

NC3

COM3

TB4

NO4

NC4

COM4

TB2

NO2

NC2

COM2

TB1

NO1

NC1

COM1

TB5

I1+ I1- I2+ I2- I3+ I3- I4+ I4-

L1 0V L2+ 0V

TB6

RL1

RL3

RL2

RL4

LD1

LD2

LD3

LD4

LD5

SK1

Not fitted on a S4-34401

Cable assembly

Ix Ix

10K

EOL

W

Switch Input

cable

length

max.

50m

10K

W

Summary of Contents for GENT S4-INTERFACE-PROG

Page 1: ... 5 N C Fault Input No delay P P P 6 N O Fault Input No delay P P P 7 N C Supervisory Input No delay P P P 8 N O Supervisory Input No delay P P P 9 N C Fire Input 10s delay P A N O Fire Input 10s delay P B N C Fault Input 10s delay P C N O Fault Input 10s delay P D N C Supervisory Input 10s delay P E N O Supervisory Input 10s delay P F Zone Input S4 34450 and S4 34410 channel 1 only P P P N C Norma...

Page 2: ...er S4 34450 S4 34410 Interface unit then repeat the process from a e When all the programming is finished switch off the mains supply and unplug the AC DC Adaptor lead from the Programmer and mains socket The programmed S4 34450 S4 34410 Interface unit is now ready and can replace an existing 34450 or 34410 loop interface unit on a loop circuit of an Analogue Addressable fire detection and alarm s...

Page 3: ...connect the battery lead from connector P7 on the PCB and remove the batteries and leads from the unit If mains supply was used to power up the S4 34440 02 Mains powered interface unit then power down and disconnect the Mains cable Close the door on the unit g If programming a number of S4 34440 02 Mains powered interface units then follow procedures a to f h When programming is finished switch of...

Page 4: ...S4 34404 Mains switching interface unit can be used in place of a legacy interface 34450 having a 19245 06 Power supply unit A programmed S4 34401 Mains switching interface unit can be used in place of a legacy 34415 Single channel loop powered interface unit Where the interface unit is installed on a loop circuit of an Analogue Addressable fire detection and alarm system Connect the system cables...

Reviews: