Honeywell GENT S4-INTERFACE-PROG User Manual Download Page 3

Instructions to convert a S4-34440-02 Mains powered

Interface unit

These procedures must be followed to convert a S4-34440-02 Mains
powered interface to a legacy 34440 Mains powered interface unit.

a.

Set the channel rotary switches on the Programmer as per
section headed 'Setting the rotary switches'.

b.

Remove the

Loop

terminal block PB1

j

from the S4-34440-02

Mains powered interface PCB.

c.

Connect the

cable assembly

supplied

,

fitting the 6-way terminal

block end to the

Loop

pins

k

PB1 on the S4-34440-02 Mains

powered interface PCB. Remove the loop terminal block from the
Programmer

l

. Connect the other end of the cable assembly to

the loop pins

m

on the Programmer, as illustrated.

d.

Install and connect the 12V 12Ah batteries

n

inside the

S4-34440-02 Mains powered interface unit enclosure and power
up by pressing the switch SW1

o

. If charged batteries are not

available then power up the S4 mains powered interface using
the Mains supply.

e.

Fit the AC-DC Adaptor lead to the Interface programmer and
connect the mains plug to a mains socket

p

.

Note the programming status LED

q

on the Programmer and

LED

r

on the S4-34440-02 Mains powered interface PCB. The

programming duration is approximately 10 seconds.

f.

Disconnect the

cable assembly

from the

loop pins of the programmed S4-34440-02
Mains powered interface PCB. Disconnect
the battery lead from connector P7 on the
PCB and remove the batteries and leads
from the unit. If mains supply was used to
power up the S4-34440-02 Mains powered
interface unit then power down and
disconnect the Mains cable. Close the door
on the unit.

g.

If programming a number of S4-34440-02
Mains powered interface units then follow
procedures a) to f)

h.

When programming is finished, switch off
the mains supply and unplug the AC-DC
Adaptor from the Programmer.

The S4 Mains powered interface unit is now
programmed and can be used in place of a
legacy 34440 Mains powered interface unit on a
loop circuit of an Analogue Addressable fire
detection and alarm system.
Connect the system cables to the programmed
interface unit and ensure the correct EOL
device(s) are fitted.

S4 Interface programmer

3

S4 Interface Programmer kit

User guide

PB2

S+

Z+ Z-

S-

SECTOR / ZONE1

PB3

S+

Z+ Z-

S-

SECTOR / ZONE2

PB4

S+

Z+ Z-

S-

SECTOR / ZONE3

PB5

S+

Z+ Z-

S-

SECTOR / ZONE4

PB1

0C LC 01 L1 02 L2

LOOP

L

N

PB6

+

+

-

-

AUX O/P

P3

FS6
T3.16A
CERAMIC
ANTI-SURGE

SW1 - POWER UP

Mains Powered
Interface Unit Mk 3

P1

DANGER
DO NOT
REMOVE

FS8 F3.16A

QUICK

BLOW

S4-Mains powered
interface unit
(S4-34440-02)

LED Indications

Steady green

Flashing amber

Programming

Programming complete

No power applied

Fault

(for example the S4 Interface

is not plugged in correctly)

Steady amber

Programmer

01

L1

P7

2 x 12V 2.1Ah
Batteries

Battery
lead

SW1 -
Battery
power up

Flashing green

Communicating

LED Indications

L1

01

Remove
this block

Loop

terminals

Mains
terminal
block

Red

Black

Summary of Contents for GENT S4-INTERFACE-PROG

Page 1: ... 5 N C Fault Input No delay P P P 6 N O Fault Input No delay P P P 7 N C Supervisory Input No delay P P P 8 N O Supervisory Input No delay P P P 9 N C Fire Input 10s delay P A N O Fire Input 10s delay P B N C Fault Input 10s delay P C N O Fault Input 10s delay P D N C Supervisory Input 10s delay P E N O Supervisory Input 10s delay P F Zone Input S4 34450 and S4 34410 channel 1 only P P P N C Norma...

Page 2: ...er S4 34450 S4 34410 Interface unit then repeat the process from a e When all the programming is finished switch off the mains supply and unplug the AC DC Adaptor lead from the Programmer and mains socket The programmed S4 34450 S4 34410 Interface unit is now ready and can replace an existing 34450 or 34410 loop interface unit on a loop circuit of an Analogue Addressable fire detection and alarm s...

Page 3: ...connect the battery lead from connector P7 on the PCB and remove the batteries and leads from the unit If mains supply was used to power up the S4 34440 02 Mains powered interface unit then power down and disconnect the Mains cable Close the door on the unit g If programming a number of S4 34440 02 Mains powered interface units then follow procedures a to f h When programming is finished switch of...

Page 4: ...S4 34404 Mains switching interface unit can be used in place of a legacy interface 34450 having a 19245 06 Power supply unit A programmed S4 34401 Mains switching interface unit can be used in place of a legacy 34415 Single channel loop powered interface unit Where the interface unit is installed on a loop circuit of an Analogue Addressable fire detection and alarm system Connect the system cables...

Reviews: