Honeywell GENT S4-INTERFACE-PROG User Manual Download Page 2

Instructions to convert S4-34450 or S4-34410

LV Interface units

These procedures must be followed to convert a S4-34450 LV
Interface unit to a legacy 34450 4-channel interface unit or a S4-34410
LV interface unit to a legacy 34410 Loop powered zone module.

a.

Set the channel

rotary switches

on the Programmer as per

section headed 'Setting the rotary switches'.

b.

Set the

links

on the S4-34450 interface unit to the required

orientation

j

for input or output application. Note the S4-34410

Interface unit has no configuration links. Remove the terminal
block

k

from the interface unit to be programmed.

c.

Plug the S4-34450/S4-34410 Interface
Unit into the terminal blocks on the
Programmer

l

. Connect the AC-DC

Adaptor lead to the power socket

m

on

the Programmer and the other end to a
mains socket.

Note the programming status indications

n

given on the Programmer and LED

indication

o

on the S4-34450/S4-34410

Interface unit. The programming duration
is approximately 10 seconds.

d.

If programming another
S4-34450/S4-34410 Interface unit then
repeat the process from a).

e.

When all the programming is finished,
switch off the mains supply and unplug the
AC-DC Adaptor lead from the Programmer
and mains socket.

The programmed S4-34450/S4-34410 Interface
unit is now ready and can replace an existing
34450 or 34410 loop interface unit on a loop
circuit of an Analogue Addressable fire
detection and alarm system. Connect the
system cables to the programmed interface unit
and ensure the correct EOL device(s) are fitted.

User guide

S4 Interface Programmer kit

2

S4 Interface programmer

S4-Interface Unit
(S4-34450 or S4-34410)

Flashing green

Communicating

LED Indications

Steady green

Flashing amber

Programming

Programming complete

No power applied

Fault

(for example the S4 Interface

is not plugged in correctly)

Steady amber

LED Indications

Programmer

When programming a
it is important to set channels 2,
3 and 4 on the Programmer to
the ‘UNUSED’ setting.

S4-34410

Removable
terminal blocks

Light pipe

Link Configurations

For a S4-34450 all
should be configured for Input,
Output or unused

4 Channels

For a S4-34410 only
is required to be configured

Channel 1

Removable
terminal blocks

Other
modes

Relay
Output

Summary of Contents for GENT S4-INTERFACE-PROG

Page 1: ... 5 N C Fault Input No delay P P P 6 N O Fault Input No delay P P P 7 N C Supervisory Input No delay P P P 8 N O Supervisory Input No delay P P P 9 N C Fire Input 10s delay P A N O Fire Input 10s delay P B N C Fault Input 10s delay P C N O Fault Input 10s delay P D N C Supervisory Input 10s delay P E N O Supervisory Input 10s delay P F Zone Input S4 34450 and S4 34410 channel 1 only P P P N C Norma...

Page 2: ...er S4 34450 S4 34410 Interface unit then repeat the process from a e When all the programming is finished switch off the mains supply and unplug the AC DC Adaptor lead from the Programmer and mains socket The programmed S4 34450 S4 34410 Interface unit is now ready and can replace an existing 34450 or 34410 loop interface unit on a loop circuit of an Analogue Addressable fire detection and alarm s...

Page 3: ...connect the battery lead from connector P7 on the PCB and remove the batteries and leads from the unit If mains supply was used to power up the S4 34440 02 Mains powered interface unit then power down and disconnect the Mains cable Close the door on the unit g If programming a number of S4 34440 02 Mains powered interface units then follow procedures a to f h When programming is finished switch of...

Page 4: ...S4 34404 Mains switching interface unit can be used in place of a legacy interface 34450 having a 19245 06 Power supply unit A programmed S4 34401 Mains switching interface unit can be used in place of a legacy 34415 Single channel loop powered interface unit Where the interface unit is installed on a loop circuit of an Analogue Addressable fire detection and alarm system Connect the system cables...