Special functions

Auto Changeover

 (Setup Function 12): When set to Auto, the thermostat automatically selects 

heating or cooling depending on the indoor temperature. The thermostat will automatically 

adjust heat and cool settings to maintain a 3-degree separation (fixed). Note: If you select Auto 

Changeover Only, the System Setting on the thermostat will stay locked in the Auto position, 

preventing the user from changing it to Em Heat, Heat, Cool or Off.

Adaptive Intelligent Recovery

 (Setup Function 13): Allows the thermostat to “learn” how 

long the furnace and air conditioner take to reach programmed temperature settings, so the 

temperature is reached at the scheduled time.

Compressor Protection

 (Setup Function 15): Forces the compressor to wait a few minutes 

before restarting, to prevent damage. During the wait time, the message Cool On or Heat On 

(heat pumps only) will flash on the display.

Accessories & replacement parts

Please contact your distributor to order replacement parts.

Battery holder . . . . . . . . . . . . . . . . . . . . . . . . . . . . Part Number 50007072-001
Cover plate assembly* . . . . . . . . . . . . . . . . . . . . . Part Number 50002883-001
12 pack of medium cover plates* . . . . . . . . . . . . Part Number 50007298-001

*Use to cover marks left by old thermostats.

Specifications

Temperature Ranges

•  Heat: 40� to 90�F (4.5� to 32�C)
•  Cool: 50� to 99�F (10� to 37�C)

Operating Ambient Temperature

•  32� to 120�F (0� to 48.9�C)

Shipping Temperature

•  -20� to 120�F (-28.9� to 48.9�C)

Operating Relative Humidity

•  5% to 90% (non-condensing)

Physical Dimensions

•  3-9/16" H x 5-13/16" W x 1-1/2" D
 

91 mm H x 147 mm W x 38 mm D

Electrical Ratings

Terminal 

Voltage (50/60Hz)  Running Current

W

 Heating 

20-30 Vac 

0.02-1.0 A

(Powerpile) 

750 mV DC 

100 mA DC

W2

 (Aux) Heating 

20-30 Vac 

0.02-0.5 A

Y

 Cooling 

20-30 Vac 

0.02-1.0 A

Y2

 Cooling 

20-30 Vac 

0.02-1.0 A

G

 Fan 

20-30 Vac 

0.02-0.5 A

O/B

 Changeover 

20-30 Vac 

0.02-0.5 A

E

 Emergency heat 

20-30 Vac 

0.02-1.0 A

L

 Output 

20-30 Vac 

0.02-0.5 A

Summary of Contents for FocusPRO Wi-Fi TH6000 Series

Page 1: ... product please visit http yourhome honeywell com or call Honeywell Customer Care toll free at 1 800 468 1502 69 1920ES This manual covers the following models TH6110D For 1 Heat 1 Cool systems TH6220D For up to 2 Heat 2 Cool systems TH6320U For up to 3 Heat 2 Cool systems Remove battery holder to find model number System Types Gas oil or electric heat with air conditioning Warm air hot water high...

Page 2: ...er before beginning installation MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube do not place the old control in the trash Contact your local waste management authority for instructions regarding recycling and proper disposal Pull here to remove wallplate from new thermostat Remove battery holder Insert reference card after wallplate is mounted see inst...

Page 3: ...er Heat Pump Terminals Rc 24VAC power from cooling transformer R 24VAC power from heating transformer O B Changeover valve Y Compressor contactor stage 1 Y2 Compressor contactor stage 2 TH6320U only G Fan relay Aux Auxiliary heat relay E Emergency heat relay L Sends output when set to Em Heat C 24VAC common Wiring Terminal designations Shaded areas below apply only to TH6320U TH6220D or as otherwi...

Page 4: ...ting transformer 1 2 Y Compressor contactor C 24VAC common 3 4 W Heat relay G Fan relay Heat only System with Fan Rc Power 1 R R Rc joined by jumper C 24VAC common 3 W Heat relay G Fan relay Cool only System Rc Power 1 R R Rc joined by jumper Y Compressor contactor C 24VAC common 3 G Fan relay 2H 2C System 1 transformer 6 Rc Power 1 R R Rc joined by jumper Y Compressor contactor stage 1 C 24VAC co...

Page 5: ...mmon 3 O B Changeover valve 7 G Fan relay Aux E Auxiliary Emergency heat relay L Sends output when set to Em Heat 11 2H 2C Heat Pump System TH6320U only 9 Rc Power 1 R R Rc joined by jumper Y Compressor contactor stage 1 C 24 VAC common 3 O B Changeover valve 7 G Fan relay Y2 Compressor contactor stage 2 L Sends output when set to Em Heat 11 3H 2C Heat Pump System TH6320U only 10 Rc Power 1 R R Rc...

Page 6: ...ly 10 3 heat 2 cool heat pump with aux heat TH6320U only 2 Changeover valve O B terminal 0 Changeover valve O B terminal energized in cooling 1 Changeover valve O B terminal energized in heating 3 Fan control heating 0 Gas or oil furnace equipment controls fan in heating 1 Electric furnace thermostat controls fan in heating 5 Stage 1 heat cycle rate CPH cycles hour 5 For gas or oil furnaces of les...

Page 7: ... 0 Fahrenheit 1 Celsius 15 Compressor protection 5 Five minute compressor off time See page 8 Other options 0 1 2 3 or 4 minute off time 16 Schedule format 0 5 2 programmable weekdays and weekends 1 5 1 1 weekdays Saturday Sunday programmable 27 Heat temperature range stops 90 Max heat temperature setting is 90 F 32 C Other options 40 F to 89 F 4 5 C to 31 5 C 28 Cool temperature range stops 50 Mi...

Page 8: ...so the temperature is reached at the scheduled time Compressor Protection Setup Function 15 Forces the compressor to wait a few minutes before restarting to prevent damage During the wait time the message Cool On or Heat On heat pumps only will flash on the display Accessories replacement parts Please contact your distributor to order replacement parts Battery holder Part Number 50007072 001 Cover...

Page 9: ...cliente de Honeywell llamando al 1 800 468 1502 69 1920ES Este manual incluye los siguientes modelos TH6110D para sistemas de 1 calentador y 1 refrigerador TH6220D para sistemas de 2 calentadores y 2 refrigeradores TH6320U para sistemas de 3 calentadores y 2 refrigeradores Quite el soporte de la batería para ver el número de modelo Tipos de sistemas Sistema de calefacción de gas de aceite o eléctr...

Page 10: ...o en tubo sellado evite arrojar el viejo control a la basura Póngase en contacto con la autoridad local para el manejo de desechos a fin de obtener instrucciones sobre el reciclado y la correcta eliminación de este tipo de desechos Hale de aquí para quitar la placa para pared del nuevo termostato Extraiga el soporte de la batería Introduzca la tarjeta de referencia luego de montar la placa para pa...

Page 11: ...formador de la refrigeración Terminales de la bomba de calor Rc 24 V CA desde el transformador de la refrigeración R 24 V CA desde el transformador de la calefacción O B Válvula inversora Y Interruptor automático del compresor etapa 1 Y2 Interruptor automático del compresor etapa 2 únicamente TH6320U G Relé del ventilador Aux Relé auxiliar de calor E Relé de emergencia de calor L Cuando se fija en...

Page 12: ...R Rc unidos por un puente R Electricidad 1 Y Válvula de separación normalmente abierta C 24 V CA 3 Sistema de 1 calentador y 1 refrigerador transformadores Rc Electricidad transformador de refrigeración 1 2 R Electricidad transformador de calefacción 1 2 Y Interruptor automático del compresor C 24 V CA 3 4 W Relé de calor G Relé del ventilador Sistema de calefacción con ventilador Rc Electricidad ...

Page 13: ...erruptor automático del compresor C 24 V CA 3 O B Válvula inversora 7 G Relé del ventilador Aux E Relé de calor auxiliar de emergencia L Cuando se fija en Em Heat envía un flujo de aire caliente 11 Sistema de bomba de calor de 2 calentadores y 2 refrigeradores Únicamente TH63 0U 9 Rc Electricidad 1 R R Rc unidos por un puente Y Interruptor automático del compresor etapa 1 C 24 V CA 3 O B Válvula i...

Page 14: ...icidad durante la refrigeración 1 Válvula de conversión terminal O B con Electricidad durante la calefacción 3 Control del ventilador calefacción 0 Sistemas de calefacción de gas o de aceite el equipo controla el ventilador para calefacción 1 Sistema de calefacción eléctrico el termostato controla el ventilador para calefacción 5 Velocidad del ciclo térmico de la primera etapa CPH ciclos por hora ...

Page 15: ... para el compresor Vea la página 8 otras opciones tiempo de apagado de 0 1 2 3 o 4 minutos 16 Formato del programa 0 5 2 programable los días de semana y los fines de semana 1 5 1 1 programable los días de semana sábados y domingos 27 Limitador del rango de temperatura del sistema de calefacción 90 La configuración máxima de temperatura es de 90 F 32 C otras opciones 40 F a 89 F 4 5 C a 31 5 C 28 ...

Page 16: ...da a la hora programada Protección del compresor configuración 15 Hace que el compresor espere unos minutos antes de reiniciarse para prevenir daños Durante el tiempo de espera el mensaje Cool On o Heat On sólo para las bombas de calor aparecerá parpadeando en la pantalla del visor Accesorios y piezas de repuesto Póngase en contacto con su distribuidor para solicitar piezas de repuesto Soporte de ...

Reviews: