86
MS-5UD & MS-10UD Series Manual —
P/N 52626:C2 1/24/2012
Programming
Master Programming Level
ANN-80 Options Screen
Pressing
2
while viewing ANN-BUS screen #2 will display the following screen:
The
Piezo Enable
option allows the programmer to select whether the piezo sounder on any
installed ANN-80 module will ever sound. Pressing
1
while viewing the ANN-80 Options Screen
#1 causes the display to toggle between
Piezo Enable Yes
and
Piezo Enable No
.
The
Lock Enable
option allows the programmer to select whether or not the ANN-80 annunciator
must be unlocked by its key before any annunciator key presses will function. Pressing
2
while
viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Yes
(annunciator must be unlocked for keys to function) and
Lock Enable No
(lock position is ignored).
The Acknowledge Button Enable (
ACK BTN ENABLE
) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 annunciator will function normally or
always be ignored. Pressing
3
while viewing the ANN-80 Options Screen #1 causes the display to
toggle between
Ack Btn Enable Yes
(Ack/Step button functions normally) and
Ack Btn Enable No
(Ack/Step button never functions).
The Silence Button Enable (
SIL BTN ENABLE
) option allows the programmer to select whether the
Silence button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing
1
while viewing the ANN-80 Options Screen #2 causes the display to toggle between
Sil
Btn Enable Yes
(Silence button functions normally) and
Sil Btn Enable No
(Silence button never
functions).
The Reset Button Enable (
RST BTN ENABLE
) option allows the programmer to select whether the
Reset button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing
2
while viewing the ANN-80 Options Screen #2 causes the display to toggle between
Rst
Btn Enable Yes
(Reset button functions normally) and
Rst Btn Enable No
(Reset button never func-
tions).
The Drill Button Enable (
DRL BTN ENABLE
) option allows the programmer to select whether the
Drill button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing
3
while viewing the ANN-80 Options Screen #2 causes the display to toggle between
Drl
Btn Enable Yes
(Drill button functions normally) and
Drl Btn Enable No
(Drill button never func-
tions).
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-80 OPTIONS
1=SIL BTN ENABLE
2=RST BTN ENABLE
3=DRL BTN ENABLE
ANN-80 Options Screen #2