150
MS-5UD & MS-10UD Series Manual —
P/N 52626:C2 1/24/2012
NFPA Standard-Specific Requirements
NFPA 72 Proprietary Protective Signaling Systems
Figure B.4 Proprietary Protective Signaling System
Form-C relay contact programmed to
activate on Supervisory condition.
Form-C Trouble contact which will
automatically activate on any Trouble
condition.
Form-C Alarm contact programmed to
activate on General Alarm.
FACP Main Board
Fire Alarm Control Panel
Notes:
1. Connection between the MS-5UD/MS-10UD
and the transmitter are supervised by the
transmitter.
2. This MS-5UD/MS-10UD Transmitter
arrangement can be employed for NFPA 72
Proprietary Protective Signaling System.
3. Potter Electric Model EFT-C has
not
been
tested for UL 864 9th Edition and is for use in
retrofit applications only.