0
1
2
3
4
5 6
7 8 9
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IN
OUT
+0
+1
+2
+3
+4
+5
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
3.9K EOL
RESISTOR
(INCLUDED)
ELR-47K
CONNECT MODULES TO
LISTED COMPATIBLE
FIRE•LITE CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
CLASS B IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
0
1
2
3
4
5 6
7 8 9
10
11
12
13
14
15
+
–
+
–
T6
T5
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
(–)
(+)
TO PANEL CONTROLLED
RESETTABLE POWER SUPPLY
EXTERNAL
SUPPL
Y
POWER-LIMITED
AND SUPERVISED
1. To use a common power supply between multiple MMF-302-6 modules,
connect a long power supply jumper from T5 or T6 to T5 or T6 on the
adjacent MMF-302-6 module.
1. To select Class A, remove the two shunts from the
“A/B select” positions.
2. To use a common power supply between multiple MMF-302-6 modules,
connect a long power supply jumper from T5 or T6 to T5 or T6 on the
adjacent MMF-302-6 module.
0
1
2
3
4
5 6
7 8 9
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IN
OUT
+0
+1
+2
+3
+4
+5
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
FIRE•LITE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
CLASS A IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
0
1
2
3
4
5 6
7 8 9
10
11
12
13
14
15
T6
T5
IDC 2
IDC 3
(–)
(+)
EXTERNAL
SUPPL
Y
POWER-LIMITED
AND SUPERVISED
+
–
+
–
TO PANEL CONTROLLED
RESETTABLE POWER SUPPLY
FIGuRE 8. INTERFACE TwO-wIRE CONvENTIONAL DETECTORS – CLASS B, STyLE B:
FIGuRE 9. INTERFACE TwO-wIRE CONvENTIONAL DETECTORS – CLASS A, STyLE D:
F200-22-00
4
I56-1900-005
Detectors must be UL listed compatible with the module. Install detectors per
manufacturers installation instructions.
C0779-03
C0780-03