BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate Fire•Lite control panel installation manual for detailed sys
-
tem information. If the modules will be installed in an existing operational
system, inform the operator and local authority that the system will be tempo
-
rarily out of service. Disconnect the power to the control panel before install
-
ing the modules. This system contains static sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits so that
static charges are removed from the body. The module housing should also
be grounded.
F200-22-00
1
I56-1900-005
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
2 mA
Alarm Current:
40 mA (assumes all six LEDs solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8˝H x 5.8˝W x 1.25˝D
Accessories:
CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet
Wire Gauge:
12-18 AWG
Maximum IDC Wiring Resistance:
25 Ohms
External Power Supply Voltage:
Regulated 24VDC
Ripple Voltage:
0.1 volts RMS maximum
IDC (supervised and power limited)
DC Voltage:
18-28 volts power limited
Frequency:
DC
Current:
90mA per circuit
MMF-302-6 Six Zone Interface Module
DET.
DETECTOR
MODEL
COMP. ID
MANUFACTURER
BASE MODEL
MAX DET.
1151
A
SYSTEM SENSOR
B110LP,B401
20
1451
A
SYSTEM SENSOR
B401, B401B
20
1451DH
A
SYSTEM SENSOR
DH400
20
2151
A
SYSTEM SENSOR
B110LP, B401
20
2451
A
SYSTEM SENSOR
DH400, B401B,B401
20
2451TH
A
SYSTEM SENSOR
B401, B401B
20
5451
A
SYSTEM SENSOR
B401
20
1100
A
SYSTEM SENSOR
N/A
20
1400
A
SYSTEM SENSOR
N/A
20
** 2100AT
A
SYSTEM SENSOR
N/A
20
2100B
A
SYSTEM SENSOR
N/A
20
2100D
A
SYSTEM SENSOR
N/A
20
2100S
A
SYSTEM SENSOR
N/A
20
2100TB
A
SYSTEM SENSOR
N/A
20
2100TD
A
SYSTEM SENSOR
N/A
20
2100TS
A
SYSTEM SENSOR
N/A
20
2300B
A
SYSTEM SENSOR
N/A
20
2300TB
A
SYSTEM SENSOR
N/A
20
2400
A
SYSTEM SENSOR
N/A
20
2400TH
A
SYSTEM SENSOR
N/A
20
* 2W-B
A
SYSTEM SENSOR
N/A
20
* 2W-TB
A
SYSTEM SENSOR
N/A
20
DH100LP
A
SYSTEM SENSOR
N/A
20
* Class B, Style B Only
** No Accessory will be supported by 2100AT
COMPATIBLE TwO-wIRE SySTEM SENSOR SMOkE DETECTORS FOR uSE wITh MMF-302-6 wITh ZONE A IDENTIFIER
GENERAL DESCRIPTION
The MMF-302-6 Six Zone Interface Module is intended for use in an intelli-
gent alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super
-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two
unused modules to release the addresses to be used elsewhere. Each mod
-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
I56-1900-00
5
INSTALLATION AND MAINTENANCE INSTRuCTIONS
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
NOTICE: This manual should be left with the owner/user of the equipment.
firealarmresources.com