Honeywell Fire-Lite Alarms MMF-302-6 Installation And Maintenance  Instruction Download Page 3

In Class B operation, the remaining modules are automatically assigned to the 
next five higher addresses. For example, if the base address switch is set to 28, 
the next five  modules will be addressed to 29, 30, 31, 32 and 33.

The module is shipped in Class B position, remove shunts for Class A. When 
operating in Class A, alternate modules are paired together (+0/+1, +2/+3, 
+4/+5), resulting in a total of three modules. For example, if the base ad

-

dress switch is set to 28, then 30 and 32 will be automatically assigned to the 
modules while 29, 31 and 33 are available to be used for other modules on the 
SLC. For Class A and B operation, DO NOT set the lowest address above 154, 

as the other modules will be assigned to nonexistent addresses.

NOTE: Some panels support extended addressing. In 
order to set the module above address 99 on compat

-

ible systems, carefully remove the stop on the upper 
rotary  switch  (see  Figure  7).  If  the  panel  does  not 
support extended addressing, do not set the lowest 
address above 94.
4.    A shunt is provided to disable a maximum of 

two  unused  modules  in  Class  B  operation  and 
Class A operation. Modules are disabled from the highest address and 
work downward.  If two modules are disabled, the lowest four addresses 
will be functional, while the highest two will be disabled. For example, 
in Class B operation, if the shunt for Address Disable is placed on “two” 
and the base switch is set to 28, the modules will be assigned to 28, 29, 

30 and 31 while disabling the highest two positions.

NOTE: Place unused shunts on single pin to store on board for   future use.
NOTE: Power must not be applied to the unit when changing functionality of 

the shunts.

wIRING NOTES

 Power-limited  circuits  must  employ  type  FPL,  FPLR,  or  FPLP  cable  as 

• 

required by Article 760 of the NEC.

 All wiring must be in accordance with the NEC, NFPA 72 and all other 

• 

applicable  codes  and  standards.  All  external  power  supplies  must  be 
power  limited  with  battery  back-up.  All  external  power  supplies  and 
detectors must be UL listed for fire protection signaling applications.

PROGRAMMING

The MMF-302-6 module operates with the following Fire Alarm Control Pan

-

els:   MS-9200;  MS-9600

The modules are programmed as devices in each system according to the pro

-

gramming instructions in the appropriate FACP manual.  

F200-22-00 

I56-1900-005

The  steps  in  Figures  6a  and  6b  describe  and  illustrate  module  installation 
when the rear chassis position and the position in front of it will be filled.  

Front  position  installation  is  possible  only  if  the  rear  position  is  filled  with 

another module.

FIGuRE 6A: INSTALLATION OF MMF-302-6 MODuLE IN A REAR 
ChASSIS POSITION, METhOD TwO

1

Step 1: 

 Insert the bottom edge of the MMF-302-6 module down into a rear 
slot of the chassis.

Step 2: 

 Carefully swing the upper edge of the board towards the back of the 

chassis until it touches the short standoff attached to the chassis.

Step 3: 

 Align the long standoff with the short standoff and tighten.

FIGuRE 6B: INSTALLATION OF MMF-302-6 MODuLE IN FRONT 
ChASSIS POSITION

2

3

1

Step 1: 

 Insert the bottom edge of the MMF-302-6 module down into a front 
slot of the chassis.

Step 2: 

 Carefully swing the upper edge of the board towards the back of 
the chassis until it touches the 11/4˝ (31.75mm) standoffs installed 

on the rear module.

Step 3: 

 Align two 4-40 screws with the two standoffs and tighten.

Step 4: 

 Address and wire the modules according to the instructions in this 

manual.

wIRING

NOTE:  All  wiring  must  conform  to  applicable  local  codes,  ordinances,  and 

regulations.
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.   All  wiring  to  the  MMF-302-6  is  done  via  terminal  blocks.  In  order  to 

properly make electrical connections strip approximately 1/4˝ of insula

-

tion  from  the  end  of  wire,  sliding  the  bare  end  of  the  wire  under  the 

clamping plate screw.  

3.   Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module (between 01 and 154).

TENS

0

7 8

6

5

4

3

2

1

9

10

11

12

13

14

15

 Figure 7.

C0225-00

C0226-00

C0227-00

firealarmresources.com

Summary of Contents for Fire-Lite Alarms MMF-302-6

Page 1: ...451 A SYSTEM SENSOR B401 20 1100 A SYSTEM SENSOR N A 20 1400 A SYSTEM SENSOR N A 20 2100AT A SYSTEM SENSOR N A 20 2100B A SYSTEM SENSOR N A 20 2100D A SYSTEM SENSOR N A 20 2100S A SYSTEM SENSOR N A 20 2100TB A SYSTEM SENSOR N A 20 2100TD A SYSTEM SENSOR N A 20 2100TS A SYSTEM SENSOR N A 20 2300B A SYSTEM SENSOR N A 20 2300TB A SYSTEM SENSOR N A 20 2400 A SYSTEM SENSOR N A 20 2400TH A SYSTEM SENSOR...

Page 2: ...The BB 2 cabinet houses one or two MMF 302 6 modules on the internal chas sis that is part of the cabinet Refer to cabinet installation documents for dimensions C0235 00 INSTALLATION STEPS 1 Cabinet Mounting In a clean dry area mount the backbox using the four holes provided in the back surface of the cabinet Figure 3 2 Chassis Installation The CH 6 chassis is mounted in the BB 6 cabinet It is att...

Page 3: ... All external power supplies and detectors must be UL listed for fire protection signaling applications PROGRAMMING The MMF 302 6 module operates with the following Fire Alarm Control Pan els MS 9200 MS 9600 The modules are programmed as devices in each system according to the pro gramming instructions in the appropriate FACP manual F200 22 00 3 I56 1900 005 The steps in Figures 6a and 6b describe...

Page 4: ...ove the two shunts from the A B select positions 2 To use a common power supply between multiple MMF 302 6 modules connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent MMF 302 6 module 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS IN OUT 0 1 2 3 4 5 IDC ADDRESS IDC ADDRESS IDC ADDRESS SLC FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO LISTED COMPATIBLE...

Page 5: ...his equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential in stallation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harm...

Reviews: