Honeywell F35F Product Data Download Page 6

F35F Expandapac™ MEDIA AIR CLEANER

68-0178—2

6

M945A

M946A

Fig. 9. Horizontal furnace, with media air cleaner mounted

vertically in return duct near furnace.

Fig. 10. Two or more media air cleaners

used in a high capacity system.

Determining Sheet Metal Requirements

The media air cleaner is adaptable to all new or existing
forced air heating and cooling systems used in residential
applications. Transitions or turning vanes may be required in
some applications for effective media air cleaner operation.

Transitions

Transitions are needed when the duct is a different size than
the media air filter cabinet. Follow these guidelines when
fabricating:

1. Use gradual transitions to reduce air turbulence and

increase efficiency. See Fig. 11.

2. Use no more than 20 degrees (about 4 in. per running ft

[100 mm per 300 linear mm]) of expansion on each side
of a transition fitting.

Turning Vanes

If the media air cleaner is installed next to an elbow or angle
fitting, add turning vanes inside the angle to distribute airflow
more evenly across the face of the media. See Fig 12.

Offsets

If the duct connection to the furnace in a side installation
allows less than 7 in. (178 mm) for mounting media air
cleaner cabinet, attach an offset to the elbow. See Fig. 13.

20 DEGREE EXPANSION PER SIDE PER 
FITTING (4 IN. PER RUNNING FOOT 
[100 MM PER 300 LINEAR MM])

RETURN AIR
DUCT

TRANSITION FITTING

MEDIA AIR FILTER CABINET

M947A

DUCT SIZE CHANGED GRADUALLY TO PREVENT TURBULENCE.

Fig. 12. Turning vanes installed in bend help

distribute airflow evenly over face of media.

TURNING
VANES

M5651

Fig. 11. Duct size changed gradually

to prevent turbulence.

Summary of Contents for F35F

Page 1: ...ing combs Combs are located down stream from filter so they stay clean Efficiency and arrestance ratings based on the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE Standard 52 1 92 Initial Atmospheric Dust Spot Efficiency 25 8 Average Atmospheric Dust Spot Efficiency 32 0 Average Synthetic Dust Weight Arrestance 92 0 ASHRAE Dust Holding Capacity 55g The above data...

Page 2: ...hree sizes to fit most air ducts Compact packaging makes replacement media filters easy to fit on service trucks or mail to customers Replacement filter comes with bag to dispose of old filter FC35B Kit available to upgrade an F25F to an F35F requires FC35A Replacement Media Replacement Media Filter Order Number Size FC35A1001 16 x 25 FC35A1019 20 x 20 FC35A1027 20 x 25 Applicable to all gas oil a...

Page 3: ...ospheric Dust Spot Efficiency 32 0 Average Synthetic Dust Weight Arrestance 92 0 ASHRAE Dust Holding Capacity 55g The above data is for a 16 x 25 in filter The F35F removes particles as small as 1 0 microns Dimensions Fig 1 Installation dimensions in in mm of air cleaner Filter Media Expandapac Temperature Rating 40 F to 125 F 40 C to 52 C Capacity and Pressure Drop 400 600 800 1000 1200 1400 1600...

Page 4: ...least 26 in 660 mm clearance in front of the unit for removal of the filter Install the media air cleaner where the temperature will not exceed the ratings in the Specifications section Applications with Air Conditioning Mount the media air filter upstream of the evaporator coil in a cooling system The filter will help to keep the coil clean and reduce maintenance Applications with a Charcoal Filt...

Page 5: ...ening in closet door Fig 6 Lowboy furnace with media air cleaner mounted horizontally in return plenum just above furnace and opposite heating plenum Fig 7 Counterflow furnace with media air cleaner mounted horizontally in return duct or plenum just above furnace Fig 8 Central fan installation with media air cleaner mounted horizontally in central return duct M942A M943A M944A M6932 A ...

Page 6: ...rease efficiency See Fig 11 2 Use no more than 20 degrees about 4 in per running ft 100 mm per 300 linear mm of expansion on each side of a transition fitting Turning Vanes If the media air cleaner is installed next to an elbow or angle fitting add turning vanes inside the angle to distribute airflow more evenly across the face of the media See Fig 12 Offsets If the duct connection to the furnace ...

Page 7: ...der the cabinet as necessary to make sure the unit is seated securely Create an opening in the furnace to match the cabinet opening Attach the cabinet securely to the furnace Attach the unit directly or fit a starting collar in the furnace opening Either drill holes and fasten with sheet metal screws or rivets or use slip joints If you are drilling holes use a locking pliers to help hold the unit ...

Page 8: ... filter is installed downstream from an atomizing humidifier or if the installation includes both heating and cooling more frequent replacement may be necessary Clogged media filter must be replaced promptly to avoid restricting airflow and reducing efficiency of the heating cooling system Record the replacement date in the space provided on the replacement media filter Replace the Expandapac Medi...

Page 9: ...l Guarantee Protects your expensive HVAC equipment No on going filter replacements necessary because cells can be washed and restored to top efficiency Increases home comfort Easy to maintain And it s by Honeywell a leader in indoor air quality products for over 30 years High Efficiency Cleaning F50 Electronic Air Cleaner REPLACEMENT PARTS F35F part numbers are keyed to parts list F35F Replacement...

Page 10: ...F35F Expandapac MEDIA AIR CLEANER 68 0178 2 10 ...

Page 11: ...F35F Expandapac MEDIA AIR CLEANER 68 0178 2 11 ...

Page 12: ...Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Region 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 68 0178 2 L C Rev 2 98 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www ho...

Reviews: