Mounting:
Mounts in any position in the return air duct next to the
furnace blower compartment. Airflow must be in the direction
of the arrow on the filter. Cabinet is sturdy enough to support
weight of a residential furnace and evaporator coil.

Underwriters Laboratories, Inc.:
UL 900, Class 2 listed.

Upgrade Path:
The F35 uses the same cabinet as the F50 Electronic Air
Cleaner. Upgrade requires installing the cell key, electronic
cells, protective screens, and power box installation and wiring.

Accessory:
S830A Clogged Filter Indicator.

Replacement Parts:
Replace Expandapac media filter annually or more often if
reduced airflow results in lower heating/cooling equipment
performance. See Replacement Parts section for Media Filter
and Frame/Comb replacement part numbers.

PLANNING THE INSTALLATION

Location

Install the media air cleaner  where all the air passing through
the system is circulated through it. The best location is in the
return air duct next to the blower compartment so the media air
filter can help to keep the blower motor and evaporator coils
clean. Do not mount in the supply air duct.

For most efficient air cleaning, spread airflow evenly across
the face of the media. If the duct is a different size than the
media air cleaner cabinet, gradual transitions are required. If
the duct turns sharply just before the air filter, turning vanes
are required (Fig.12).

Choose a location that is readily accessible for checking and
replacing the filter. Allow at least 26 in. (660 mm) clearance in
front of the unit for removal of the filter.

Install the media air cleaner where the temperature will not
exceed the ratings in the Specifications section.

Applications with Air Conditioning

Mount the media air filter upstream of the evaporator coil in a
cooling system. The filter will help to keep the coil clean and
reduce maintenance.

Applications with a Charcoal Filter

Add an activated charcoal filter to the air handling system to
remove gaseous (nonparticulate) contaminants from the
circulated air. A common residential application is to remove
odors that cannot be removed by mechanical air filters. The
activated charcoal filter, if used, should be installed
downstream from the media air cleaner to protect the
charcoal filter from lint and other particles.

Fig. 3. Highboy furnace, with side installation.

Media air cleaner is mounted vertically

where return enters side inlet of furnace.

Fig. 4 Highboy furnace, with installation

beneath furnace. Media air cleaner is mounted

horizontally where return enters from below.

M939A

M940A

Applications with a Humidifier

The media air filter is compatible with humidifiers. Avoid
applications where water mist can reach the media. If an
atomizing humidifier is used, the filter media will require
replacement more often because of minerals in the water.

Choose Mounting Position

The media air cleaner can be mounted in any position, but the
arrow on the cartridge must point in the same direction as the
airflow. See Fig. 3-10 for proper location of the media air
cleaner for a variety of furnace installations. Note that the
media air filter cabinet is sturdy enough to easily support the
weight of the furnace and evaporator coil. See Fig. 4.

Summary of Contents for F35F

Page 1: ...ing combs Combs are located down stream from filter so they stay clean Efficiency and arrestance ratings based on the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE Standard 52 1 92 Initial Atmospheric Dust Spot Efficiency 25 8 Average Atmospheric Dust Spot Efficiency 32 0 Average Synthetic Dust Weight Arrestance 92 0 ASHRAE Dust Holding Capacity 55g The above data...

Page 2: ...hree sizes to fit most air ducts Compact packaging makes replacement media filters easy to fit on service trucks or mail to customers Replacement filter comes with bag to dispose of old filter FC35B Kit available to upgrade an F25F to an F35F requires FC35A Replacement Media Replacement Media Filter Order Number Size FC35A1001 16 x 25 FC35A1019 20 x 20 FC35A1027 20 x 25 Applicable to all gas oil a...

Page 3: ...ospheric Dust Spot Efficiency 32 0 Average Synthetic Dust Weight Arrestance 92 0 ASHRAE Dust Holding Capacity 55g The above data is for a 16 x 25 in filter The F35F removes particles as small as 1 0 microns Dimensions Fig 1 Installation dimensions in in mm of air cleaner Filter Media Expandapac Temperature Rating 40 F to 125 F 40 C to 52 C Capacity and Pressure Drop 400 600 800 1000 1200 1400 1600...

Page 4: ...least 26 in 660 mm clearance in front of the unit for removal of the filter Install the media air cleaner where the temperature will not exceed the ratings in the Specifications section Applications with Air Conditioning Mount the media air filter upstream of the evaporator coil in a cooling system The filter will help to keep the coil clean and reduce maintenance Applications with a Charcoal Filt...

Page 5: ...ening in closet door Fig 6 Lowboy furnace with media air cleaner mounted horizontally in return plenum just above furnace and opposite heating plenum Fig 7 Counterflow furnace with media air cleaner mounted horizontally in return duct or plenum just above furnace Fig 8 Central fan installation with media air cleaner mounted horizontally in central return duct M942A M943A M944A M6932 A ...

Page 6: ...rease efficiency See Fig 11 2 Use no more than 20 degrees about 4 in per running ft 100 mm per 300 linear mm of expansion on each side of a transition fitting Turning Vanes If the media air cleaner is installed next to an elbow or angle fitting add turning vanes inside the angle to distribute airflow more evenly across the face of the media See Fig 12 Offsets If the duct connection to the furnace ...

Page 7: ...der the cabinet as necessary to make sure the unit is seated securely Create an opening in the furnace to match the cabinet opening Attach the cabinet securely to the furnace Attach the unit directly or fit a starting collar in the furnace opening Either drill holes and fasten with sheet metal screws or rivets or use slip joints If you are drilling holes use a locking pliers to help hold the unit ...

Page 8: ... filter is installed downstream from an atomizing humidifier or if the installation includes both heating and cooling more frequent replacement may be necessary Clogged media filter must be replaced promptly to avoid restricting airflow and reducing efficiency of the heating cooling system Record the replacement date in the space provided on the replacement media filter Replace the Expandapac Medi...

Page 9: ...l Guarantee Protects your expensive HVAC equipment No on going filter replacements necessary because cells can be washed and restored to top efficiency Increases home comfort Easy to maintain And it s by Honeywell a leader in indoor air quality products for over 30 years High Efficiency Cleaning F50 Electronic Air Cleaner REPLACEMENT PARTS F35F part numbers are keyed to parts list F35F Replacement...

Page 10: ...F35F Expandapac MEDIA AIR CLEANER 68 0178 2 10 ...

Page 11: ...F35F Expandapac MEDIA AIR CLEANER 68 0178 2 11 ...

Page 12: ...Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Region 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 68 0178 2 L C Rev 2 98 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www ho...

Reviews: