F150E MEDIA AIR CLEANER

68-0245EF-3

6

Determining Sheetmetal Requirements

The media air cleaner is adaptable to all new or existing 

forced air heating and cooling systems used in residential 

applications. Transitions or turning vanes may be required in 

some applications for effective media air cleaner operation.

Transitions

Transitions are needed when the duct is a different size than 

the media air cleaner cabinet. When fabricating:

1.

Use gradual transitions to reduce air turbulence and 

increase efficiency. See Fig. 11.

2.

Use no more than 20 degrees (about 4 in. per running ft. 

(100 mm per 300 linear mm) of expansion on each side 

of a transition fitting.

Turning Vanes

If the media air cleaner is installed next to an elbow or angle 

fitting, add turning vanes inside the angle to distribute airflow 

more evenly across the face of the media. See Fig 12.

Offsets

If the duct connection to the furnace in a side installation 

allows less than 7 in. (178 mm) for mounting media air cleaner 

cabinet, attach an offset to the elbow. See Fig. 13.

Fig. 11. Duct size changed gradually to prevent 

turbulence.

Fig. 12. Turning vanes installed in bend help distribute 

airflow evenly over face of media.

Fig. 13. Typical use of duct offset to make room for

media air cleaner.

INSTALLATION 

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them 

could damage the media air filter or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

media air cleaner to make sure the product is suitable 

for your application.

3.

Installer must be a trained, experienced service techni-

cian.

Remove Furnace Filter And Clean Blower 

Compartment

Before starting the installation, remove and discard the 

existing furnace filter (if used). Thoroughly clean the blower 

compartment. If possible, power vacuum the ductwork to 

remove accumulated dust in an occupied home or remove 

construction dirt in a new home. The media air cleaner cannot 

remove dirt that has settled in the blower compartment and 

distribution ducts.

Install The Cabinet

The following procedure describes a typical side installation 

on an existing highboy furnace. Alternate procedures are 

noted as appropriate. Other changes in installation 

procedures may be necessary to complete your installation.

Review The Installation Plan

Temporarily place the cabinet on the floor, oriented as it will be 

when installed. Insert and remove the cartridge to make sure 

the plan allows adequate clearance for easy removal and 

replacement of the cartridge.

Make sure that shop-fabricated sheetmetal components, such 

as turning vanes, are available.

20 DEGREE EXPANSION PER SIDE PER 
FITTING (4 IN. PER RUNNING FOOT 
[100 MM PER 300 LINEAR MM])

RETURN AIR
DUCT

TRANSITION FITTING

MEDIA AIR CLEANER CABINET

M947B

DUCT SIZE CHANGED GRADUALLY TO PREVENT TURBULENCE.

TURNING
VANES

M5651

M948A

LESS
THAN
7 in.
(178 mm)

OFFSET

AT LEAST
7 in.
(178 mm)

1

1   REQUIRED TURNING VANES HELP DISTRIBUTE AIRFLOW EVENLY.

Summary of Contents for F150E

Page 1: ...ditioning Engineers Standard 52 2 1999 Applicable to all gas oil and electric forced warm air furnaces and to compressor cooling up to 5 tons Mounts in the return air duct Cabinet can support weight of residential furnace and evaporator coil Requires no electrical connections Mounts in any position Requires no maintenance except periodic media filter replacement Quick and easy media filter replace...

Page 2: ...d with heat pumps if filter is changed regularly to prevent excessive pressure drop Not recommended for applications where pressure drop may be critical Pressure Drop Initial pressure drop at 492 fpm 0 23 in wc Dust fed to 0 5 in wc pressure drop 72 grams Efficiency Efficiency Ratings Based on American Society of Heating Refrigerating and Air Conditioning Engineers Standard 52 2 1999 Minimum Effic...

Page 3: ...ation that is readily accessible for checking and replacing the filter Allow at least 26 in 660 mm clearance in front of the unit for removal of the cartridge Install the media air filter where the temperature will not exceed the ratings in the Specifications M22578 F150E SIZE IN 16 X 25 20 X 25 16 X 20 20 X 20 MM 406 X 635 508 X 635 406 X 508 508 X 508 DIM A 14 7 16 18 7 16 14 7 16 18 7 16 367 46...

Page 4: ... position but the arrow on the cartridge must point in the same direction as the airflow See Figs 3 10 for proper location of the media air cleaner for a variety of furnace installations Note that the media air cleaner cabinet is sturdy enough to easily support the weight of the furnace and evaporator coil See Fig 4 Fig 3 Highboy furnace with side installation Media air filter is mounted verticall...

Page 5: ...furnace with media air cleaner mounted horizontally in return duct or plenum just above furnace Fig 8 Central fan installation with media air cleaner mounted horizontally in central return duct Fig 9 Horizontal furnace with media air filter mounted vertically in return duct near furnace Fig 10 Two or more media air cleaners used in a high capacity system M942A M943A M944A M945A M946A ...

Page 6: ...air filter or cause a hazardous condition 2 Check the ratings given in the instructions and on the media air cleaner to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian Remove Furnace Filter And Clean Blower Compartment Before starting the installation remove and discard the existing furnace filter if used Thoroughly clean the blo...

Page 7: ... off left when a device is not installed NOTE The UV air treatment system and the humidifier set tings are set for one year The air cleaner settings are selectable according to homeowner activities and schedule Set the air cleaner filter time DIP switches for 3 6 9 or 12 months according to the information on the back of the device Leave the factory default DIP switch settings to change the filter...

Page 8: ...eries need changing Changing batteries within 30 seconds of removing old batteries to maintain correct indicator time Air Cleaner Media filter needs replacing Pressing and holding reset button for 10 seconds or until arrow is no longer displayed UV Air Treatment UV Lamps need replacing in UV air treatment system Pressing and holding reset button for 10 seconds or until arrow is no longer displayed...

Page 9: ...ating Refrigerating and Air Conditioning Engineers Convient à tous les systèmes de chauffage à air pulsé au gaz au mazout ou à l électricité et aux compresseurs derefroidissement allant jusqu à 5 tonnes S installe dans la gaine de reprise d air Le boîtier peut recevoir le poids d un appareil dechauffage résidentiel et d un serpentin d évaporation Ne requiert aucun raccordement électrique S install...

Page 10: ...our éviter une trop grande chute de pression Non recommandé dans les systèmes ou une chute de pression peut nuire Chute de pression Chute de pression initiale à 492 pi3 min 0 23 po c e Chute de pression à 72 grammes d accumulation de poussière 0 5 po c e Efficacité Efficacité établie d après la norme 52 2 1999 de l American Society of Heating Refrigerating and Air Conditioning Engineers Rendement ...

Page 11: ...as les mêmes dimensions il est préférable d installer des raccords de transition Si la gaine présente un angle aigu juste avant le filtre à air il est recommandé d utiliser MF22578 TAILLE F150E 16 X 25 20 X 25 16 X 20 20 X 20 406 X 635 508 X 635 406 X 508 508 X 508 DIM A 14 7 16 18 7 16 14 7 16 18 7 16 367 468 367 468 DIM B 16 3 16 20 3 16 16 3 16 20 3 16 411 513 411 513 23 1 4 23 1 4 18 1 4 18 1 ...

Page 12: ... du filtre Le filtre à air à élément filtrant à fibres peut être installé dans n importe quelle position mais les flèches figurant sur la cartouche doivent pointer dans le même sens que celui de l écoulement de l air Voir les Fig 3 à 10 pour observer l emplacement adéquat du filtre à air à élément filtrant à fibres selon le type d appareil de chauffage Il est à noter que le boîtier du filtre à air...

Page 13: ...nstallé à l horizontale dans la gaine de reprise d air ou dans le plénum juste au dessus de l appareil de chauffage Fig 8 Appareil de ventilation centrale Filtre à air installé à l horizontale dans une gaine de reprise centrale Fig 9 Appareil de chauffage horizontal Le filtre à air est monté à la verticale à l endroit où entre l air repris près de l appareil de chauffage Fig 10 Deux filtres à air ...

Page 14: ...nférieur à 178 mm 7 po pour le boîtier du filtre à air ajouter un raccord de dérivation au coude Voir la Fig 13 Fig 11 Modification graduelle de la taille de la gaine air en vue de réduire la turbulence Fig 12 Utilisation de déflecteurs pour contribuer à assurer une distribution d air plus uniforme la surface du filtre Fig 13 Utilisation typique d un raccord de dérivation pour assurer un dégagemen...

Page 15: ... de reprise d air entre le filtre à air et l appareil de chauffage pour empêcher la poussière de pénétrer dans le courant d air propre Installer la cartouche du filtre Faire glisser la cartouche du filtre dans le boîtier et vérifiant que la flèche figurant sur la cartouche correspond bien au sens d écoulement de l air Remettre la porte d accès en place insérer la languette au bas de la porte dans ...

Page 16: ...urront être nécessaires Il faut remplacer un filtre obstrué le plus rapidement possible pour éviter d empêcher l écoulement de l air et de réduire l efficacité du système de chauffage refroidissement Inscrire la date du remplacement dans l espace prévu à cet effet sur le filtre à fibres de rechange Indication Si la flèche clignote ou si l appareil émet un bip Ce qu il faut faire Battery pile Il fa...

Reviews: