F150E MEDIA AIR CLEANER
3
68-0245EF-3
Fig. 1. Installation dimensions in in. (mm) of air cleaner.
Fig. 2. Capacity, Pressure Drop and Area of
F150E Filter Media.
PLANNING THE INSTALLATION
Location
The media air cleaner should be installed where all the air
passing through the system is circulated through it. The best
location is in the return air duct next to the blower compart-
ment so the media air cleaner can help to keep the blower
motor and evaporator coils clean. Do not mount in the supply
air duct.
For most efficient air cleaning, spread airflow evenly across
the face of the media. If the duct is a different size than the
media air filter cabinet, gradual transitions are required. If the
duct turns sharply just before the air filter, turning vanes are
required.
Choose a location that is readily accessible for checking and
replacing the filter. Allow at least 26 in. (660 mm) clearance in
front of the unit for removal of the cartridge.
Install the media air filter where the temperature will not
exceed the ratings in the Specifications.
M22578
F150E SIZE
IN.
16 X 25
20 X 25
16 X 20
20 X 20
MM
406 X 635
508 X 635
406 X 508
508 X 508
DIM. A
14-7/16
18-7/16
14-7/16
18-7/16
367
468
367
468
DIM. B
16-3/16
20-3/16
16-3/16
20-3/16
411
513
411
513
23-1/4
23-1/4
18-1/4
18-1/4
DIM. C
591
591
457
457
DIM. D
25-1/2
25-1/2
20-1/2
20-1/2
648
648
521
521
DIM. C (SEE TABLE)
DIM. D (SEE TABLE)
DIM. B
(SEE TABLE)
DIM. A
(SEE TABLE)
7
8
(22)
5
8
(16)
6
3
4
(172)
7
8
(22)
IN.
MM
IN.
MM
IN.
MM
IN.
MM
1
1
8
(29)
0
500
1000
1500
2000
0.000
0.050
0.100
0.150
0.200
0.250
0.300
16 X 20
16 X 25
20 X 20
20 X 25
FILTER SIZE
PRESSURE DROP (IN. WC)
AIRFLOW (CFM)
M14709A
WHEN FIRST INSTALLED. PRESSURE DROP INCREASES AS FILTER
BECOMES LOADED. REPLACE FILTER WHEN PRESSURE DROP
REACHES 0.5 IN. WC. (0.1 kPa).