background image

F100 MEDIA AIR CLEANER

68-0239EF–3

7

Install two AAA alkaline batteries (provided) in the harness on
the back of the device. Observe that the device performs a
self-test, beeping and flashing the LC display individually for
each device (air cleaner, UV air treatment system, humidifier)
installed in the home. Then press and hold the black reset
button on the bottom of the device for five seconds or until the
display stops flashing to start the timers. Observe the battery
LCD: on solidly means that the unit is correctly powered;
flashing indicates that the battery requires replacing.

Checkout

Visually check the installation. Make sure:

Airflow is in the direction of the arrow on the media air filter
cartridge.

Turning vanes and transitions, if used, are properly
installed.

Joints in sheetmetal between media fir filter and fur-nace
are sealed.

All sheetmetal connections are complete.

Original furnace filter has been removed and blower
compartment is cleaned.

Replace any access doors removed during the Installation or
Checkout.

Run the furnace or cooling system through one complete
cycle to make sure the system operates as desired.

Maintenance

The W8600A beeps every fifteen minutes when an LCD is
flashing. Replace the part in the system that corresponds with
the flashing LCD.

NOTE:

When batteries need replacing, replace them within
30 seconds of removal to maintain the correct
indicator time. After 30 seconds of replacing the
batteries, if the LCD is blank, remove and install new
batteries. For other parts, press and hold the black
button on the bottom of the device to reset the timer
after replacing parts.

The media filter must be replaced when pressure drop across
the media filter reaches 0.5 in. w.c. (0.1 kPa). or at least
annually. If the media air cleaner is installed downstream from
an atomizing humidifier or if the installation includes both
heating and cooling, more frequent replacement may be
necessary. Clogged media must be replaced promptly to
avoid restricting airflow and reducing efficiency of the heating-
cooling system. Record the replacement date in the space
provided on the replacement media filter.

LCD

If arrow is flashing or

              

unit is beeping

Reset by

Battery  

Batteries need changing.

Changing batteries within 30 seconds of removing
old batteries to maintain correct indicator time.

Air Cleaner   

Media filter needs replacing.  

Pressing and holding reset button for 10 seconds or
until arrow is no longer displayed.

UV Air Treatment   

UV lamps need replacing in UV air
treatment system.

Humidifier   

Humidifier pad needs replacing.

Summary of Contents for F100

Page 1: ... SPECIFICATIONS IMPORTANT The specifications in this publication do not include normal manufacturing tolerances therefore an individual unit may not exactly match the listed specifications This product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Models F100F Media Air Cleaner includes cabinet...

Page 2: ...ment Cabinet is sturdy enough to support weight of a residential furnace and evaporator coil Approvals Underwriters Laboratories Inc Listed to UL 900 Class 2 Fig 1 Installation dimensions in in mm of air cleaner M14710A F100 SIZE IN 16 X 25 16 X 20 20 X 25 20 X 20 20 X 12 1 2 25 X 20 25 X 22 MM 406 X 635 406 X 508 508 X 635 508 X 508 508 X 318 635 X 508 635 X 559 DIM A 14 7 16 14 7 16 18 7 16 18 7...

Page 3: ... IN WC 0 1 kPa AVAILABLE ONLY IN UNITED STATES 2 1 1 2 Replacement Media For optimum system performance replace the filter every six months before heating season and before cooling season Adjust the schedule to you needs but replace the filter at least annually Fig 2 Capacity Pressure Drop and Area of FC100A Filter Media PLANNING THE INSTALLATION Location The media air cleaner should be installed ...

Page 4: ...ng in closet door Fig 6 Lowboy furnace with media air cleaner mounted horizontally in return plenum just above furnace and opposite heating plenum Fig 7 Counterflow furnace with media air cleaner mounted horizontally in return duct or plenum just above furnace M941A M942A M943A M944A Fig 8 Central fan installation with media air cleaner mounted horizontally in central return duct ...

Page 5: ...of expansion on each side of a transition fitting Turning Vanes If the media air cleaner is installed next to an elbow or angle fitting add turning vanes inside the angle to distribute airflow more evenly across the face of the media See Fig 12 Offsets If the duct connection to the furnace in a side installation allows less than 7 in 178 mm for mounting media air cleaner cabinet attach an offset t...

Page 6: ...de of the media Install them whenever an abrupt 90 degree elbow is installed directly against the media air cleaner cabinet Fasten Cabinet To Ductwork Fasten side of cabinet to the ductwork using sheet metal screws rivets or slip joints as appropriate Connect Ductwork Connect the vertical duct section to the elbow If the vertical drop of the duct is less than 7 in 178 mm from the side of the furna...

Page 7: ...en minutes when an LCD is flashing Replace the part in the system that corresponds with the flashing LCD NOTE When batteries need replacing replace them within 30 seconds of removal to maintain the correct indicator time After 30 seconds of replacing the batteries if the LCD is blank remove and install new batteries For other parts press and hold the black button on the bottom of the device to res...

Page 8: ... paper containing at least 10 post consumer paper fibers Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 429 Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 M18621A ...

Page 9: ...Efficacité du FC100A Efficacité établie d après la norme 52 2 1999 de l American Society of Heating Refrigerating and Air Conditioning Engineers Efficacité initiale 15 particules de 0 3 micron Rendement minimum rapporté 8 à 492 pi3 min Médium filtrant Papier plié en accordéon pour une plus grande capacité Capacité et chute de pression Voir la Fig 2 Chute de pression initiale 0 177 po c e à 492 pi3...

Page 10: ...ez le catalogue TRADELINE ou les tarifs pour obtenir le numéro de pièce Prière d adresser toute question additionnelle demande d information ou commentaires sur les produits et services par écrit ou par téléphone 1 Aux services à la clientèle de Honeywell Honeywell 1885 Douglas Drive North MN10 1461 Golden Valley MN 55422 4386 2 Ou visiter notre site Web à www honeywell com yourhome Au Canada Hone...

Page 11: ...arder le serpentin propre et permettra de réduire la fréquence de l entretien Applications humidificateur Le filtre à air convient aux systèmes avec humidificateurs Éviter les installations où l eau vaporisée peut atteindre le médium filtrant Dans le cas d une installation avec humidificateur atomiseur il faudra remplacer le médium filtrant plus souvent en raison des sédiments que contient l eau C...

Page 12: ...erture de la porte de l armoire Fig 6 Appareil de chauffage à caissons juxtaposés Filtre à air installé à l horizontale dans le plénum d air repris juste au dessus de l appareil de chauffage face au plénum d alimentation Fig 7 Appareil de chauffage à contre courant Filtre à air installé à l horizontale dans la gaine de reprise d air ou dans le plénum juste au dessus de l appareil de chauffage Fig ...

Page 13: ...s Si le filtre à air est installé près d un coude raccord à angle installer les déflecteurs à l intérieur du coude pour assurer une distribution d air plus uniforme à la surface du filtre Voir la Fig 12 Raccords de dérivation Si le raccord entre la gaine et l appareil dans le cas d une installation sur le côté offre un dégagement inférieur à 178 mm 7 po pour le boîtier du filtre à air ajouter un r...

Page 14: ...ntenir l appareil en place pendant cette opération Installer les déflecteurs Installer les déflecteurs pour assurer une distribution uniforme de l air sur toute la surface amont du médium filtrant Il faut les installer à l intérieur du coude à 90 degrés montés directement sur le boîtier du filtre à air Fixer le boîtier au système de gaines Fixer l autre côté du boîtier sur le coude à l aide de riv...

Page 15: ... l entretien appuyer sur le bouton de réarmement au bas du W8600A et le retenir pendant 10 secondes pour réarmer la minuterie Maintenance Le W8600A émet un signal sonore toutes les quinze minutes lorsqu un des indicateurs à cristaux liquides clignote Il faut à ce moment remplacer la pièce du système qui correspond à l indicateur qui clignote REMARQUE Lorsqu il faut remplacer les piles les remplace...

Page 16: ...es contenus dans l air et empêchez les spores de moisissures de croître sur les serpentins de refroidissement Filtre à air pour toute la maison Emprisonnez une bonne partie des particules contenues dans l air Humidificateur pour toute la maison Humidifiez l air trop sec maintenez l humidité ambiante pour réduire les effets négatifs sur la santé Système de régulation par zones Réglez la température...

Reviews: