User Manual Series F-BO-AFE70
Chapter 13 • Set parameters
13
Set parameters
System:
_________________________________________________________________
_________________________________________________________________
SW1 Purging program
0
Setting the time – manual activation not possible
□
1
Once a day at 10:00 and in case of a fault, always with long Purging process
□
2
Twice a day at 09:00 and 14:00 and in case of a fault, always with long Purging
process
□
3
Three times a day at 06:00, 12:00 and 18:00 and in case of a fault, always with
long Purging process
□
4
Four times a day at 5:00, 10:00, 15:00 and 20:00 and in case of a fault, always
with long Purging process
□
5
Six times a day at 4:00, 8:00, 12:00, 16:00, 20:00 and 00:00 and in case of a fault,
always with long Purging process
□
6
Long Purging process in the event of a fault of the evaluation unit of the aspirat-
ing smoke detector
This program is also to be used if the Purging processes are only started by a
push-button, or if the Purging unit operates as „slave“.
□
7
Once a day at 10:00 and in case of a fault, always with short Purging process
□
8
Twice a day at 09:00 and 14:00 and in case of a fault, always with short Purging
process
□
9
Three times a day at 06:00, 12:00 and 18:00 and in case of a fault, always with
short Purging process
□
A
Four times a day at 5:00, 10:00, 15:00 and 20:00 and in case of a fault, always
with short Purging process
□
B
Six times a day at 4:00, 8:00, 12:00, 16:00, 20:00 and 00:00 and in case of a fault,
always with short Purging process
□
C
Short Purging process in the event of a fault of the evaluation unit of the aspirat-
ing smoke detector
D
No Purging program; a fault will be transmitted without delay, manual activation
is not possible
E
No Purging program; a fault will be transmitted without delay, manual activation
is not possible
F
Setting the device number
Device number: ________
– manual activation not possible
Table 9:
Set parameters of the Automatic Purging Unit F-BO-AFE70
Switch position of the rotary switch „Purging program“ SW1 as well as device number
I56-4252-010
D200-104-00
45
Summary of Contents for F-BO-AFE70 Series