Honeywell EXCEL 12 W7704B1002 Installation Instructions Manual Download Page 7

EXCEL 12 MODULES 

EN1B-0201GE51 R0905C 

7

Troubleshooting 

All models feature a L

ON

W

ORKS

 service LED and 

corresponding L

ON

W

ORKS

 service button (accessible from the 

outside on top of the module) for commissioning and 
troubleshooting. When the service button is pressed, the 
service pin message is broadcasted. 
 
See Table 3 on page 8 for a description of the meaning of the 
various different possible behaviors of the L

ON

W

ORKS

 service 

LED. For more information on standard service LED behavior, 
refer to Motorola L

ON

W

ORKS

 Technology Device Data 

Manual, page AL-190. 
 

Possible Problems and Recommended Actions 

Check if switching the power OFF/ON changes the 
L

ON

W

ORKS

 service LED's behavior. Please contact Honeywell 

if this does not solve the problem. 
 

lo

ng hou

s

ing

 (

w

ith built-

in transformer):

 1

80 m (7-7/8

 in.)

Short

 housing (w

it

hout

 transformer):

 126 mm (4-15/

16 in.

)

leverage slot

LonWorks

service button

LonWorks

service LED

ventilation slits

 

Fig. 9. Housing (top view) 

Accessories 

Swivel Label Holders 

For short or long housings (required for modules equipped 
with manual override switches). Packs of eight. 

  24 Vac models (short), order no.: 

XAL_LAB_S

 

  line power supply models (long), order no.: 

XAL_LAB_L

 

 

Terminal Protection Covers 

For short or long housings (required for wall/ceiling mounting). 
Packs of eight. 

  24 Vac models (short), order no.: 

XAL_COV_S

 

  line power supply models (long), order no.: 

XAL_COV_L

 

 

L

ON

W

ORKS

 Termination 

One or two L

ON

W

ORKS

 terminations are required, depending 

on the given LonWorks bus layout. 
Two different L

ON

W

ORKS

 terminations are available: 

  L

ON

W

ORKS

 termination module, order no.: 

209541B

 

  L

ON

W

ORKS

 connection / termination module (mountable 

on DIN rails and in fuse boxes), order no.: 

XAL-Term 

3

4

L

O
N

Honeywel

l

XAL-Term

L

O
N

removable screw-type

3-pole terminal block

1

5

3

4

0

6

shield

shield

LON

Termination

FTT/LPT Bus

FTT/LPT Free

Park Position

plug-in

jumper

 

Fig. 10. L

ON

W

ORKS

 connection and termination module 

Summary of Contents for EXCEL 12 W7704B1002

Page 1: ...nly 100 Vac power supply length 180 mm five relays incl three normally open relays and two changeover relays and six triac outputs four binary inputs six analog inputs plus AI6 which is suitable for reading input from LESST wall modules only two analog outputs 0 10 V one LED output W7704E1005 for Japan only 24 Vac power supply length 126 mm two relays both normally open and three triac outputs fou...

Page 2: ...out tabs and snap by hand the covers available in packs of 8 into place onto the housing To remove a cover place a screwdriver in the leverage slot see Fig 9 on page 7 and pry it loose Terminal Assignment The terminal blocks are arranged on two sides of the controller the relay side and the low voltage side The relay side consists of a single row of terminal blocks for the connection of cables to ...

Page 3: ...th Line Power Supply Models with line i e 100 Vac or 230 Vac power supply are equipped with a built in 24 Vac transformer the secondary side of which can be used to power external devices The max current at the field device supply terminals and all triac outputs together must not exceed 300 mA continuous NOTE Do not connect external 24 Vac on models with line power supply These models have a long ...

Page 4: ...D When either a T7460 and T7560 Wall Module has been hardwired to the Excel 12 its LED can be configured using Honeywell s LNS plug in to provide information about e g overrides or effective occupancy modes Further in the case of a T7560 Wall Module its LCD can likewise be configured to display such information Configuration of the LED to Display Info on Overrides The wall module s LED can indicat...

Page 5: ... The unit is connected to the LONWORKS network as shown in Fig 8 via terminal pins 3 and 4 black screw type T terminal plug underneath the terminal protection cover if present located on the low voltage side Terminal 24 and 25 are used to connect further devices to the LONWORKS network Excel 12 Excel 12 24V 22 24V 0 23 24V 1 24V 0 2 LON 1 3 LON 2 4 LON 1 24 LON 2 25 24V 22 24V 0 23 24V 1 24V 0 2 L...

Page 6: ...mable electronic ballast s power supply the Excel 12 system ground must be earthed Triac Outputs The Excel 12 is equipped with up to six triac outputs Hardware Limits for Excel 12 with Line Power Supply Low signal 0 V high signal 24 Vac Maximum 250 mA continuous current in sum for all triac outputs together 550 mA for max 10 sec cos ϕ 0 5 Hardware Limits for Excel 12 with 24 Vac Power Supply Low s...

Page 7: ...leverage slot LonWorks service button LonWorks service LED ventilation slits Fig 9 Housing top view Accessories Swivel Label Holders For short or long housings required for modules equipped with manual override switches Packs of eight 24 Vac models short order no XAL_LAB_S line power supply models long order no XAL_LAB_L Terminal Protection Covers For short or long housings required for wall ceili...

Page 8: ...d custom node Application less firmware state exported 6c OFF duration is 1 15 sec depending on the application size and the system clock Afterwards the service LED begins flashing ON and OFF at 0 5 Hz First power up with a new PROM on a Neuron 3150 Chip based custom node Unconfigured firmware state exported 6d OFF duration is indefinite 1 15 sec to load internal EEPROM remains OFF First power up ...