EXCEL 12 MODULES 

EN1B-0201GE51 R0905C 

 

6

Binary Outputs 

The triac outputs or relay outputs can be configured for 
different functions. 
 

Example: Floating Drives 

You can choose to use two triac outputs or two relays to 
connect a floating drive (no mixing of triac outputs and relays 
allowed). Once the outputs have been configured using 
Honeywell's LNS plug-in, floating actuators can be directly 
connected to them. 
 

Relay Outputs 

The Excel 12 is equipped with up to two change-over relays 
and up to three normally-open relays. 
 

Hardware Limits 

  A min. current of 50 mA is required to ensure a reliable 

contact. 

  The normally-open contacts are designed for a max. 

continuous current of 6 A. The normally-closed contacts 
are designed for a max. continuous current of 1 A. 

  The max. combined allowable current flowing through all 

relays simultaneously is 24 A (continuous). 

  The max. peak in-rush current (20 ms) at the normally-

open contact is 80 A. 

 

NOTE:

  If inductive components are to be connected to the 

relays and if these relays switch more often than 
once every two minutes, they must be prevented 
from causing harmful interference to radio or tele-
vision reception (conformance with EN 45014). 

 

NOTE: 

Fluorescent lamps with electronic control gear often 
have high switching currents. To reduce this 
switching current, you could use current limiters (e.g. 
EBN2 Schalk electronics) or install 10 m cable 
(25 mm

2

) between the Excel 12 controller's relays 

and the electronic ballast. If the analog input of a 
dimmable electronic load is not a protective low-
voltage signal or if the analog signal is wired in the 
same cable as the dimmable electronic ballast's 
power supply, the Excel 12 system ground must be 
earthed. 

 

Triac Outputs 

The Excel 12 is equipped with up to six triac outputs. 
 

Hardware Limits for Excel 12 with Line Power Supply 

  Low signal: 0 V; high signal: 24 Vac

 

 

Maximum 250 mA

 continuous current in sum for all triac 

outputs together

 

  550 mA for max. 10 sec.

 

 cos 

ϕ

 > 0.5

 

Hardware Limits for Excel 12 with 24 Vac Power Supply 

  Low signal: 0 V; high signal: 24 Vac

 

 

Maximum 500 mA

 continuous current in sum for all triac 

outputs together

 

  800 mA for max. 10 sec.

 

 cos 

ϕ

 > 0.5

 

 

Analog Inputs 

The Excel 12 is equipped with up to seven analog inputs, all 
of which can be configured as slow binary inputs (in which 
case the signal must be stable for at least 1.25 seconds) for 
the detection of slow signals (e.g. from a window contact). 
The analog inputs are configured using Honeywell's LNS 
plug-in. 

Table 2. Analog input usage 

analog input  voltage 

NTC 

wall module 

AI1 X 

humidity 

AI2

4

  

room 

temperature

1

 

AI3

4

 

 

 

fan speed or bypass

2

 

AI4

4

   

set-point

3

 

AI5 X 

 

AI6

5

  

 

AI7

4

 X 

 

1

  For all NTC inputs, temperatures of 

 -50...-45 °C are interpreted as 

being due to a sensor break, and temperatures of 

 +145...+155 °C 

are interpreted as being due to a sensor short-circuit. 

2

  A contact open for 

 10 seconds is interpreted as a sensor failure. 

3

  A resistance of > 15 k

 is interpreted as being due to a sensor 

break, a resistance of < 100 

 is interpreted as being due to a 

sensor short-circuit. 

4

  Not supported by the W7704E1005 

5

  In the case of the W7704D1024 and W7704E1005, AI6 is not a true 

analog input, but rather is suitable for reading input from LESST 
wall modules, only 

 

Analog Outputs 

The Excel 12 is equipped with two 0...11 Vdc analog outputs 
(with the exception of the W7704E1005, which supports only 
a single such analog output), each of which can drive a max. 
of 1.1 mA. 

Summary of Contents for EXCEL 12 W7704B1002

Page 1: ...nly 100 Vac power supply length 180 mm five relays incl three normally open relays and two changeover relays and six triac outputs four binary inputs six analog inputs plus AI6 which is suitable for reading input from LESST wall modules only two analog outputs 0 10 V one LED output W7704E1005 for Japan only 24 Vac power supply length 126 mm two relays both normally open and three triac outputs fou...

Page 2: ...out tabs and snap by hand the covers available in packs of 8 into place onto the housing To remove a cover place a screwdriver in the leverage slot see Fig 9 on page 7 and pry it loose Terminal Assignment The terminal blocks are arranged on two sides of the controller the relay side and the low voltage side The relay side consists of a single row of terminal blocks for the connection of cables to ...

Page 3: ...th Line Power Supply Models with line i e 100 Vac or 230 Vac power supply are equipped with a built in 24 Vac transformer the secondary side of which can be used to power external devices The max current at the field device supply terminals and all triac outputs together must not exceed 300 mA continuous NOTE Do not connect external 24 Vac on models with line power supply These models have a long ...

Page 4: ...D When either a T7460 and T7560 Wall Module has been hardwired to the Excel 12 its LED can be configured using Honeywell s LNS plug in to provide information about e g overrides or effective occupancy modes Further in the case of a T7560 Wall Module its LCD can likewise be configured to display such information Configuration of the LED to Display Info on Overrides The wall module s LED can indicat...

Page 5: ... The unit is connected to the LONWORKS network as shown in Fig 8 via terminal pins 3 and 4 black screw type T terminal plug underneath the terminal protection cover if present located on the low voltage side Terminal 24 and 25 are used to connect further devices to the LONWORKS network Excel 12 Excel 12 24V 22 24V 0 23 24V 1 24V 0 2 LON 1 3 LON 2 4 LON 1 24 LON 2 25 24V 22 24V 0 23 24V 1 24V 0 2 L...

Page 6: ...mable electronic ballast s power supply the Excel 12 system ground must be earthed Triac Outputs The Excel 12 is equipped with up to six triac outputs Hardware Limits for Excel 12 with Line Power Supply Low signal 0 V high signal 24 Vac Maximum 250 mA continuous current in sum for all triac outputs together 550 mA for max 10 sec cos ϕ 0 5 Hardware Limits for Excel 12 with 24 Vac Power Supply Low s...

Page 7: ...leverage slot LonWorks service button LonWorks service LED ventilation slits Fig 9 Housing top view Accessories Swivel Label Holders For short or long housings required for modules equipped with manual override switches Packs of eight 24 Vac models short order no XAL_LAB_S line power supply models long order no XAL_LAB_L Terminal Protection Covers For short or long housings required for wall ceili...

Page 8: ...d custom node Application less firmware state exported 6c OFF duration is 1 15 sec depending on the application size and the system clock Afterwards the service LED begins flashing ON and OFF at 0 5 Hz First power up with a new PROM on a Neuron 3150 Chip based custom node Unconfigured firmware state exported 6d OFF duration is indefinite 1 15 sec to load internal EEPROM remains OFF First power up ...

Reviews: