Honeywell EXCEL 12 W7704B1002 Installation Instructions Manual Download Page 2

EXCEL 12 MODULES 

EN1B-0201GE51 R0905C 

terminal protection

cover (optional)

terminal protection

cover (optional)

swivel label

holders (optional)

 

Fig. 1. Excel 12 housing (side view) 

 

DIN Rail Mounting/Dismounting 

The unit can be mounted onto a DIN rail simply by snapping it 
into place and securing it with a stopper to prevent sliding. It 
is dismounted by gently pulling the stirrup located in the base 
of the housing (see Fig. 2). 
 

eyelets for

cable binders

eyelet for

cable binders

eyelets for

cable binders

screwing nose

(round hole)

stirrup;

pull to dismount

from rail

screwing nose

(oval hole)

 

Fig. 2. Housing base (view from below) 

Wall/Ceiling Mounting/Dismounting 

 

round hole

(diameter: 4 mm)

short housing: 100 mm; long housing: 154 mm

sh

ort hou

sing

: 10

0 mm

long h

ous

ing: 1

00 mm

oval hole

(4x7 mm)

 

Fig. 3. Drilling template (view from above) 

 
The unit can be mounted on walls or ceilings in any 
orientation desired. In the case of ceiling mounting, however, 
it should not be operated at ambient temperatures exceeding 
45 °C. The unit is mounted by inserting 3.5-mm dowel screws 
through the corresponding screwing noses. 
 

Optional Use of Terminal Covers 

After mounting the Excel 12 onto the wall or ceiling, provide 
for cable access by snipping out the terminal protection 
covers' cut-out tabs and snap (by hand) the covers (available 
in packs of 8) into place onto the housing. To remove a cover, 
place a screwdriver in the leverage slot (see Fig. 9 on page 7) 
and pry it loose. 
 

Terminal Assignment 

The terminal blocks are arranged on two sides of the 
controller: the relay side and the low-voltage side. 
 

  The relay side consists of a single row of terminal blocks 

for the connection of cables to the relays. In the case of 
models with line (i.e. 100 Vac or 230 Vac) power supply, 
the line power is also connected on this side. 

  The low-voltage side consists of two rows of terminal 

blocks for the connection of cables to all other input / 
outputs. In the case of models with 24 Vac power supply, 
the 24 Vac power supply is also connected on this side. 

 

NOTE:

  According to VDE guidelines, it is not allowed to mix 

low-voltage and high-voltage signals on the relays. 

 

NOTE:

  For controlling thermal actuators, we recommend 

using the 24 Vac models, which provide more 
current. 

 
Every Excel 12 is equipped with a terminal assignment label 
on the top of the housing (see Fig. 4). The terminal assign-
ment label is a plastic part displaying the maximum 
complement of I/O's. 
 
The small sticker in the upper left corner provides model-
specific information, e.g. the date code, the type of power 
supply, that terminals 36-38 (triac outputs 5 and 6) are not 
connected, and that terminals 1, 2, 22, and 23 may be used 
as 24 Vac output terminals, only (secondary side of the built-
in transformer). 

Summary of Contents for EXCEL 12 W7704B1002

Page 1: ...nly 100 Vac power supply length 180 mm five relays incl three normally open relays and two changeover relays and six triac outputs four binary inputs six analog inputs plus AI6 which is suitable for reading input from LESST wall modules only two analog outputs 0 10 V one LED output W7704E1005 for Japan only 24 Vac power supply length 126 mm two relays both normally open and three triac outputs fou...

Page 2: ...out tabs and snap by hand the covers available in packs of 8 into place onto the housing To remove a cover place a screwdriver in the leverage slot see Fig 9 on page 7 and pry it loose Terminal Assignment The terminal blocks are arranged on two sides of the controller the relay side and the low voltage side The relay side consists of a single row of terminal blocks for the connection of cables to ...

Page 3: ...th Line Power Supply Models with line i e 100 Vac or 230 Vac power supply are equipped with a built in 24 Vac transformer the secondary side of which can be used to power external devices The max current at the field device supply terminals and all triac outputs together must not exceed 300 mA continuous NOTE Do not connect external 24 Vac on models with line power supply These models have a long ...

Page 4: ...D When either a T7460 and T7560 Wall Module has been hardwired to the Excel 12 its LED can be configured using Honeywell s LNS plug in to provide information about e g overrides or effective occupancy modes Further in the case of a T7560 Wall Module its LCD can likewise be configured to display such information Configuration of the LED to Display Info on Overrides The wall module s LED can indicat...

Page 5: ... The unit is connected to the LONWORKS network as shown in Fig 8 via terminal pins 3 and 4 black screw type T terminal plug underneath the terminal protection cover if present located on the low voltage side Terminal 24 and 25 are used to connect further devices to the LONWORKS network Excel 12 Excel 12 24V 22 24V 0 23 24V 1 24V 0 2 LON 1 3 LON 2 4 LON 1 24 LON 2 25 24V 22 24V 0 23 24V 1 24V 0 2 L...

Page 6: ...mable electronic ballast s power supply the Excel 12 system ground must be earthed Triac Outputs The Excel 12 is equipped with up to six triac outputs Hardware Limits for Excel 12 with Line Power Supply Low signal 0 V high signal 24 Vac Maximum 250 mA continuous current in sum for all triac outputs together 550 mA for max 10 sec cos ϕ 0 5 Hardware Limits for Excel 12 with 24 Vac Power Supply Low s...

Page 7: ...leverage slot LonWorks service button LonWorks service LED ventilation slits Fig 9 Housing top view Accessories Swivel Label Holders For short or long housings required for modules equipped with manual override switches Packs of eight 24 Vac models short order no XAL_LAB_S line power supply models long order no XAL_LAB_L Terminal Protection Covers For short or long housings required for wall ceili...

Page 8: ...d custom node Application less firmware state exported 6c OFF duration is 1 15 sec depending on the application size and the system clock Afterwards the service LED begins flashing ON and OFF at 0 5 Hz First power up with a new PROM on a Neuron 3150 Chip based custom node Unconfigured firmware state exported 6d OFF duration is indefinite 1 15 sec to load internal EEPROM remains OFF First power up ...