XC5010C/XC6010/Excel 100C, only
If shielded cable is used then both ends of the shield must be connected to terminal
15 and 18, or 33 and 36, per following figure:
C
B
-0
4
9
2
-X
1
15
16
17
18
15
16
17
18
15
16
17
18
33
34
35
36
XC5010C
XC6010
XC5010C
XC6010
XC5010C
XC6010
Excel 100
Repeaters
Each repeater extends the bus length by the amount of the single bus length. The
table below summarizes the number of repeaters allowed. Note that the maximum
length depends on the cable specification as described under the cables chapter.
Table 17. Max. baud rate in relation to cable length and no. of repeaters
max. baud rate
max. no. of
repeaters
resulting max. bus length
(depends upon cable specifications)
76.8 Kbaud
5
7,200 m (24,000 ft.)
The ordering information is as follows:
Table 18. Ordering information for repeater
description
OS no.
repeater with housing
XD509