EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER

3

95-7520—02

Fig. 3. W7753A DIN rail mounting.

Wiring

All wiring must comply with applicable electrical codes and 

ordinances or as specified on installation wiring diagrams. 

Controller wiring on the W7753A is terminated to the screw 

terminal blocks located on the top and the bottom of the 

controller.

NOTES:

For multiple controllers operating from a single 

transformer, the same side of the transformer 

secondary must be connected to the same power 

input terminal in each controller. The ground 

terminal (1 on the W7753A) must be connected to 

a verified earth ground for each controller in the 

group (see Fig. 5). (Controller configurations are 

not necessarily limited to three controllers, but the 

total power draw including accessories cannot 

exceed 100 VA when powered by the same 

transformer (U.S. only). See System Engineering 

form 74-2964 for power wiring recommendations.)

All loads on an Excel 10 W7753A Controller must 

be powered by the same transformer that powers 

the Excel 10 W7753A Controller. A W7753A 

Controller can use separate transformers for 

controller power and load power.

Keep the earth ground connection (terminal 1) 

wire run as short as possible. Refer to Fig. 9 

through 14.

Do 

not

 connect the analog or digital ground 

terminals (5, 8, 11, 27 and 30) to earth ground. 

Refer to Fig. 9 through 14.

Power

The 24 Vac power from an energy-limited Class II Power 

Source must be provided to each W7753A Controller. To 

conform to Class II restrictions (U.S. only), transformers must 

not be larger than 100 VA.

A transformer that meets CE mark requirements and that 

meets the Low Voltage Directive (LVD) requirements must be 

used in Europe for all installations of this product. More than 

one W7753A Controller can be powered by a single 

transformer. Fig. 4 shows power wiring details for a single 

controller and Fig. 5 depicts multiple controllers using one 

transformer.

IMPORTANT

Use the heaviest gauge wire available, up to 14 

AWG (2.0 mm

2

) with a minimum of 18 AWG 

(1.0 mm

2

), for all power and earth ground wiring.

Screw type terminal blocks are designed to accept 

up to two 14 AWG (2.0 mm

2

) conductors, one on 

each side of the terminal screw. More than two wires 

that are 14 AWG (2.0 mm

2

) can be connected with a 

wire nut. Include a pigtail with this wire group and 

attach the pigtail to one side of the terminal block.

Fig. 4. Power wiring details; one Excel 10 per transformer.

NOTES:

Unswitched 24 Vac power wiring can be run in the 

same conduit as the E-Bus cable.

Maintain at least three-inch (76 mm) separation 

between Triac outputs and E-Bus wiring 

throughout the installation.

See the following 

IMPORTANT

 on 

Heating and Cooling 

Equipment (UL 1995, U.S. only)

.

IMPORTANT

If the W7753A Controller is used on Heating and 

Cooling Equipment (UL 1995, U.S. only) and the 

transformer primary power is more than 150 volts, 

connect the transformer secondary to earth ground 

(see Fig. 6). For these applications, only one 

W7753A Excel 10 controller can be powered by each 

transformer.

M6857

1

2

3

M12681

CONNECT POWER TO 

TERMINALS 24 AND 25

TRIAC LINES

TO ACTUATORS

AND 

CONTACTORS

TRANSFORMER

W7753A

EARTH

GROUND

20

22

24

25

1

OUTPUT

DEVICE

POWER

Summary of Contents for EXCEL 10 W7753A

Page 1: ...7753A Controller communicates via the 78 kilobaud Echelon LonWorks E Bus Network Allowable input output connections consist of wall module points plus two additional resistive sensor inputs two voltage current inputs four digital inputs and eight digital Triac outputs For the W7753A any hardware driven by the Triac outputs must have a minimum current draw when energized of 25 mA and a maximum curr...

Page 2: ...lastic cover Use the screws appropriate for the mounting surface The W7753A can be mounted in any orientation Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation The W7753A can also be mounted using DIN rail obtain locally If using DIN rail also purchase from Augat Inc part number 2TK2D DIN rail adapter two each See Fig 3 Fig 2 ...

Page 3: ...II restrictions U S only transformers must not be larger than 100 VA A transformer that meets CE mark requirements and that meets the Low Voltage Directive LVD requirements must be used in Europe for all installations of this product More than one W7753A Controller can be powered by a single transformer Fig 4 shows power wiring details for a single controller and Fig 5 depicts multiple controllers...

Page 4: ...o pair can be used Unswitched 24 Vac power wiring can be run in the same conduit as the E Bus cable Do not bundle output wires with sensor digital input or communications E Bus wires Do not use different wire types or gauges on the same E Bus segment The step change in line impedance characteristics would cause unpre dictable reflections on the E Bus When using dif ferent types is unavoidable use ...

Page 5: ... Wiring Details The W7753A Controller has the terminal arrangements shown in Fig 9 through 14 Connection for operator access to the E Bus is provided by plugging the Serial LonTalk Adapter SLTA connector into the E Bus jack NOTE If an Excel 10 Controller or Zone Manager is not connected to a good earth ground the controller internal transient protection circuitry is compromised and the function of...

Page 6: ...ET 2 7 8 5 6 9 10 LED SET PT FAN BYPASS 1 2 3 4 5 6 7 8 E BUS 24 VAC W7753A UNIT VENTILATOR CONTROLLER 1 2 1 2 3 3 3 EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM USE THE HEAVIEST GAUGE WIRE AVAILABLE UP TO 14 AWG 2 O MM2 WITH A MINIMUM OF 18 AWG 1 O MM2 FOR EARTH GROUND WIRE TO ASSURE PROPER ELECTRICAL CONTACT WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK CONTACTS...

Page 7: ...1 OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT 2 DI 2 DI 4 DI 1 DI 3 GROUND PNEUMATIC VALVE M12693 GROUND M B M 1 2 3 4 5 6 7 8 E BUS 24 VAC W7753A UNIT VENTILATOR CONTROLLER 1 2 E BUS E GND GND SNSR SETPT LED BYPASS GND GND 9 10 11 12 14 J3 15 31 30 29 28 27 26 25 24 23 22 21 20 24 VAC COM E BUS JACK 22 VDC OUT 19 18 17 16 AI 1 OHM AI 2 OHM AI 4 V mA OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT...

Page 8: ...nd ordinances or as specified on installation wiring diagrams Fig 14 Typical 2 to 10 Volt DC humidity sensor to W7753A For note 2 refer to Fig 8 1 2 3 4 5 6 7 8 E BUS 24 VAC 1 2 E BUS E GND GND SNSR SETPT LED BYPASS GND GND 9 10 11 12 14 J3 15 31 30 29 28 27 26 25 24 23 22 21 20 24 VAC COM E BUS JACK 22 VDC OUT 19 18 17 16 AI 1 OHM AI 2 OHM AI 4 V mA OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT 2...

Page 9: ...roadcasting the Service Message The Service Message allows a device on the E Bus to be positively identified The Service Message contains the controller ID number and therefore can be used to confirm the physical location of a particular Excel 10 in a building There is one method of broadcasting the Service Message from an Excel 10 W7753A Controller This uses a hardware push button on the side of ...

Page 10: ...cycled or the node is reset The alarm is not issued until FanFailTime seconds have elapsed since the loss of flow condition was first reported DIRTY_FILTER 7 The pressure drop across the filter exceeds the limit and the filter requires maintenance The control runs normally SMOKE_ALARM 8 The smoke detector has detected smoke and the node has entered an emergency state IAQ_OVERRIDE 9 The indoor air ...

Page 11: ...EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER 11 95 7520 02 ...

Page 12: ...nal Inc 95 7520 02 K K Rev 03 09 Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 Honeywell GmbH Böblinger Straße 17 D 71101 Schönaich customer honeywell com ...

Reviews: