background image

Photocell Control

 

 

 

 

i)  Regulating Photocell
 

Regulating photocell control tries to maintain a constant level of total illumination in the space controlled by 
dimming  and  brightening  the  controlled  luminaires  to  compensate  for  changes  in  illumination  from  other 
sources.

With the photocell configured as DISABLED the Regulating Control module is influenced only by the BRIGHT-
OUT setting. BRIGHT-OUT = YES allows it to hold-off the lights at the start of occupancy if natural light already 
exceeds SET-POINT LOW and to extinguish the lights during occupancy if total light, after the controlled 
luminaires have been dimmed to minimum, exceeds SET-POINT HIGH continuously for a period equal to the 
OFF DELAY . The lighting is restored immediately if the illumination level subsequently drops below SET-
POINT LOW.

If the photocell is configured for ACTIVE or PASSIVE control of the relay switched load, then the Regulating 
Control module adopts the decision made by the Switching Control module in the case of turn-on inhibit on 
entry, but still obeys the BRIGHT-OUT YES/NO setting with regard to turn-off during occupancy.   

ii)  Switching Photocell  (PHOTOCELL: ACTIVE or PASSIVE)

Both   ACTIVE or PASSIVE modes   hold off the controlled lighting on entry when natural light is sufficient,     
i.e. SET-POINT LOW is exceeded, but only ACTIVE mode will extinguish the lighting if natural light increases 
sufficiently during occupancy, i.e. SET-POINT HIGH is exceeded continuously for a period equal to OFF 
DELAY. The lighting is restored immediately if the illumination level subsequently drops below SET-POINT 
LOW.

iii)  Photocell DISABLED

If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of 
that load, which will be ON continuously during periods of occupancy unless commanded OFF via manual 
switch or infrared control. The photocell readings are still available for use by the Regulating Control module 
while in this mode.

Programming  the Photocell Set-points

The parameters SET-POINT LOW and SET-POINT HIGH programme the detector’s photocell response.   
The SET-POINTS can be manually programmed as numbers between 1 (darkest) and 1023 (brightest). This 
number is not scaled  to correlate with ‘lux’ measurements made using a light meter, but nevertheless is a true 
representation of the light level perceived by the detector. To assist with finding the appropriate SET-POINT 
settings, the light level currently perceived by the photocell can be viewed on the QuickSet Pro screen briefly, 
following a download operation. The number represents the light level read immediately before the download 
took place. 

Tip: Turn the lights off  with the QuickSet Pro (UTILITIES / LIGHTSPOT/MLS/LCM / IR REMOTE / HC5) to 
measure the perceived light level with no contribution from the controlled lighting.

 

Alternatively the SET-POINTS can be configured semi-automatically;

 

i) The Primary Interest is the Regulating Control Output.

With the photocell configured as DISABLED:-

Using QuickSet Pro (UTILITIES / LIGHTSPOT/MLS/LCM / SET LIGHT LEVEL) or HC5A (+,- Scene 1) set 
the required light output from the controlled luminaires and then press and hold   OK (QuickSet Pro) or 
Scene 1 (HC5A) until the controlled lights "blink" to indicate that a new SET-POINT LOW has been stored 
and a calculated SET-POINT HIGH has also been inserted. Using the QuickSet Pro the photocell can now 
be re-configured as ACTIVE or PASSIVE if required.

5

Summary of Contents for Ex-Or MLS2500D

Page 1: ...kSet Pro required for commissioning MLS2500D MLS2500DF MLS2500DWL MLS2500DWLF MLS2500DALI ML2500DALIF MLS2500DALIWL MLS2500DALIWLF Digital Mid Range Series Detector with Wireless OneSwitch facility MLS2500D WL MLS2500DALI WL MLS2500D WL F MLS2500DALI WL F ...

Page 2: ... 3mm of thread is visible and then twisting the detector off the back box Note the arrow symbol moulded into the bottom of the back box The fixing holes allow for mounting on a BESA box or direct to a rigid surface Secure the back box firmly to a rigid surface so that the arrow points into the controlled area 4b MLS2500DF Semi flush version Use a hole saw to drill a 76mm hole into the ceiling tile...

Page 3: ...control circuit will not affect the operation of those lights that remain powered and under the control of the detector When switching via the relay output multiple MLS2500Ds relay outputs may be connected in parallel provided the controlled load does not exceed 10 Amps If digital ballasts are also being controlled the digital outputs from different detectors must never be connected one to another...

Page 4: ...can be re programmed any number of times Factory Default Settings These are the settings to which the units have been programmed before they leave the factory Parameter Power Up Response Off Delay On Sensitivity Off Sensitivity Bus Connect 1st Zone 2nd Zone 3rd Zone 4th Zone Corridor 1 Begin End Corridor 2 Begin End Global 1 Rx Global 2 Rx Manual I P Start Lamps Entry Scene Lamp Max Dimming Fade t...

Page 5: ...SABLED If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control The photocell readings are still available for use by the Regulating Control module while in this mode Programming the Photocell Set points The parameters...

Page 6: ...ts to be on and above which you would not want the lights to be on 3 Start the internal self programming mechanism by pressing UTILITIES LIGHTSPOT MLS LCM SET LIGHT LEVEL OK QuickSet Pro or Scene 1 HC5A The detector takes a photocell reading adds a small amount and stores the value in SET POINT HIGH Then it turns the lights off makes another measurement and stores the value in SET POINT LOW The li...

Page 7: ...antargets 4 Please note that although configurable as a regulating photocell closed loop dimming according to daylight due to the probable corner of roomlocation where there will be excessive influence by daylight reflected from the walls this productis not intendedto achievepreciselightlevelregulationmeasuredon the workingplane 5 This equipment switches lights no more frequently than would a resp...

Page 8: ...at 230V MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT 3 5m RANGE Adjustable up to 20m OFF DELAY 1 min 96 hours plus 10 second walk test mode PHOTOCELL Passive Active Regulating adjustable 50 5000 lux MATERIAL Flame retardant PC ABS COLOUR White RAL9010 WEIGHT 180g flush version 160g surface version IP RATING 4X o o OPERATING TEMPERATURE 0 C to 40 C Contact Ex Or...

Reviews: