Fixing 

                                              

Only suitably qualified personnel should install this equipment.            

1.   This is an extremely sensitive movement detector; it is essential therefore that it be installed on a rigid   
surface that will not itself be subject to any movement or vibration.

2.    Before isolating the circuits to be switched, check that all lighting is fully operational and that there is no 

moving equipment or machinery within the monitored area which may cause nuisance switching.

3.    Position the detector where it has a good forward “view” of the area to be controlled.   Ideal mounting 

location is normally in a corner by the entrance or at one end of a corridor at a height of 2.5 to 4m.  Do not 
mount within 25cm of a fluorescent fitting. 

 

Please note that this product uses microwave technology to detect occupancy and is not recommended 
for applications where there are large areas of metal, e.g. metal ceiling or panelling, as unpredictable 
sensitivity may result. 

 

Also, microwave presence detection is not completely attenuated by materials such as plasterboard, 
wood and glass, so the possibility of unwanted presence detection through office partitions should be 
considered when determining detector positioning and sensitivity settings within the intended application. 

4a.  

MLS2500D - Surface version

 

Separate the detector from its back-box by loosening the locking screw so that approximately 3mm of 
thread is visible and then twisting the detector off the back-box.  Note the arrow symbol moulded into the 
bottom of the back-box.   The fixing holes allow for mounting on a BESA box or direct to a rigid surface.  
Secure the back-box firmly to a rigid surface so that the arrow points into the controlled area.

4b.  

MLS2500DF- Semi-flush version

 

Use a hole saw to drill a 76mm hole into the ceiling tile.  The flush ring is designed to clamp the tile between 
its two halves.  Loosen the locking screw so that approximately 3mm of thread is visible and remove the 
bottom half of the flush ring.  With the detector in the ceiling, pointing towards the area to be controlled, fit 
the bottom half of the flush ring to the assembly.   Depending on the thickness of the ceiling tile, screws 
longer than those supplied may be required to hold the two halves of the flush ring together.   

It is recommended that Mid Range detectors be ceiling mounted. Where this is not possible, the wall-mounting 
kit (WMK - see below)  must be used.

Digital Mid Range Series Detector

WMK Wall-mounting Kit

           

(Supplied assembled)

Vertical installation

Use this method of mounting for racking aisle 
applications and where adjustment in the 
vertical plane will give improved control over 
the precise point of entry detection.

Horizontal installation

For general applications where 
ceiling mounting is not 
convenient and wide angle 
coverage in the horizontal plane 
is desirable.  The WMK can be 
screwed to a hard surface or the 
lid of a conduit stop-end box.

Exploded view of detector
 for fixing into ceiling tiles.

2

Summary of Contents for Ex-Or MLS2500D

Page 1: ...kSet Pro required for commissioning MLS2500D MLS2500DF MLS2500DWL MLS2500DWLF MLS2500DALI ML2500DALIF MLS2500DALIWL MLS2500DALIWLF Digital Mid Range Series Detector with Wireless OneSwitch facility MLS2500D WL MLS2500DALI WL MLS2500D WL F MLS2500DALI WL F ...

Page 2: ... 3mm of thread is visible and then twisting the detector off the back box Note the arrow symbol moulded into the bottom of the back box The fixing holes allow for mounting on a BESA box or direct to a rigid surface Secure the back box firmly to a rigid surface so that the arrow points into the controlled area 4b MLS2500DF Semi flush version Use a hole saw to drill a 76mm hole into the ceiling tile...

Page 3: ...control circuit will not affect the operation of those lights that remain powered and under the control of the detector When switching via the relay output multiple MLS2500Ds relay outputs may be connected in parallel provided the controlled load does not exceed 10 Amps If digital ballasts are also being controlled the digital outputs from different detectors must never be connected one to another...

Page 4: ...can be re programmed any number of times Factory Default Settings These are the settings to which the units have been programmed before they leave the factory Parameter Power Up Response Off Delay On Sensitivity Off Sensitivity Bus Connect 1st Zone 2nd Zone 3rd Zone 4th Zone Corridor 1 Begin End Corridor 2 Begin End Global 1 Rx Global 2 Rx Manual I P Start Lamps Entry Scene Lamp Max Dimming Fade t...

Page 5: ...SABLED If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control The photocell readings are still available for use by the Regulating Control module while in this mode Programming the Photocell Set points The parameters...

Page 6: ...ts to be on and above which you would not want the lights to be on 3 Start the internal self programming mechanism by pressing UTILITIES LIGHTSPOT MLS LCM SET LIGHT LEVEL OK QuickSet Pro or Scene 1 HC5A The detector takes a photocell reading adds a small amount and stores the value in SET POINT HIGH Then it turns the lights off makes another measurement and stores the value in SET POINT LOW The li...

Page 7: ...antargets 4 Please note that although configurable as a regulating photocell closed loop dimming according to daylight due to the probable corner of roomlocation where there will be excessive influence by daylight reflected from the walls this productis not intendedto achievepreciselightlevelregulationmeasuredon the workingplane 5 This equipment switches lights no more frequently than would a resp...

Page 8: ...at 230V MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT 3 5m RANGE Adjustable up to 20m OFF DELAY 1 min 96 hours plus 10 second walk test mode PHOTOCELL Passive Active Regulating adjustable 50 5000 lux MATERIAL Flame retardant PC ABS COLOUR White RAL9010 WEIGHT 180g flush version 160g surface version IP RATING 4X o o OPERATING TEMPERATURE 0 C to 40 C Contact Ex Or...

Reviews: