Parameter

Power up
Response
Off delay
On Sensitivity
Bus Connect
1st Zone
2nd Zone
3rd Zone
4th Zone
Corridor 1
Corridor 2
Global 1 Rx
Global 2 Rx
Manual I/P
Start Lamps
Entry Scene
Lamp Max
Dimming
Fade to Off
Vacant
Bright-Out
Photocell
Set Point Low
Set Point High

Default
Setting

ON
AUTO
20 min
100
YES
-
-
-
-
-
-
NO
NO
LOCAL
MAX
Scene 1
100%
100%
NO
OFF
NO
Disabled
1023
1023

Options

ON/OFF
Auto, Manual/Bus, Manual Only
1min - 96hrs, Disabled
0-100
YES/NO
1-100 addresses
1-100 addresses
1-100 addresses
1-100 addresses
1-100, Building Zone Span
1-100, Building Zone Span
YES/NO
YES/NO
LOCAL/SHARE
MAX/MIN
Scene 1-6
10% - 100%
Regulate 100% to 50%
YES/NO
(10 Alternative Exit Scenes)
YES/NO
Active, Passive, Disabled
1-1023
1-1023 

Notes

Each of these settings
can be re-programmed,
if desired, by use of the
infrared programming
tool QuickSet Pro. 
All settings are retained 
in the event of a power 
failure.

Commissioning

The units are supplied with the factory default settings shown below which make further 
commissioning unnecessary in many applications.   To make use of the programmable 
settings, an infrared commissioning tool is required (QuickSet Pro). A ten-second time 
delay is selectable from programmer to aid commissioning. 

Sensitivity to Movement

While the factory settings will be correct for many applications, the sensitivity can be 
adjusted  if  required.    The  ON  RANGE  setting  controls  the  sensitivity,  with  higher 
numbers  giving  greater  sensitivity.  Like  all  programmable  parameters,  the  sensitivity 
setting will be retained in the event of a power failure and can be re-programmed any 
number of times.  

Factory Default Settings

These are the settings to which the units have been programmed before they leave 
the factory.

4

Summary of Contents for Ex-Or MLS2021DF

Page 1: ...uctions Note QuickSet Pro required for commissioning 1 MLS2021DSM MLS2021DALISM MLS2021DF MLS2021DSM for DSI ballasts MLS2021DALIF MLS2021DALISM for DALI ballasts Digital Gold PIR Detector with regulating photocell MLS2021DF MLS2021DALIF ...

Page 2: ...or DALI luminaires a switched load of up to 6 Amps or a combination of the two When controlling DSI or DALI ballasts the ballast type must not be mixed The DSI or DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity Free Digital Output terminals on the rear of the detector Each DSI or DALI luminaire is controlled completely by its digital input a...

Page 3: ... maintained NC NC 2 x MLS2021D In Parallel using Switched Output only LOAD Max 6Amps N E L Permanent or switched supply VOLT FREE OUTPUT VOLT FREE OUTPUT LIVE IN LIVE IN NEUTRAL NEUTRAL EARTH EARTH Any connection not shown is NO CONNECTION ONE SWITCH NC NC ONE SWITCH Relay outputs may be connected together in parallel to cover larger areas however the total load on all combined relay outputs must ...

Page 4: ...ogrammed if desired by use of the infrared programming tool QuickSet Pro All settings are retained in the event of a power failure Commissioning The units are supplied with the factory default settings shown below which make further commissioning unnecessary in many applications To make use of the programmable settings an infrared commissioning tool is required QuickSet Pro A ten second time delay...

Page 5: ...rolled lighting on entry when natural light is sufficient i e SET POINT LOW is exceeded but only ACTIVE mode will extinguish the lighting if natural light increases sufficiently during occupancy i e SET POINT HIGH is exceeded continuously for a period equal to OFF DELAY The lighting is restored immediately if the illumination level subsequently drops below SET POINT LOW iii Photocell DISABLED If t...

Page 6: ...ready on switch them on manually by pressing UTILITIES LIGHTSPOT MLS LCM IR REMOTE Luminaire OK QuickSet Pro or HC5A Fluorescent lights do not reach full output until up to 15 minutes after being switched on so ensure that the lights are fully warmed up before continuing 2 Wait until the time of day when the natural light level is at the point below which you would want the lights to be on and abo...

Page 7: ...neSwitch Dimming and the HC5A ImportantAdditional Notes 1 All terminals on this product are provided for final connections It is not intended that the productbe used as a junction box for loopingcables 2 A means for disconnection must be incorporated in the fixed wiring in accordance with the currentwiringregulations 3 Although nominally 12V the dimming output is not SELV and therefore should be t...

Page 8: ...NDED LOAD VOLT FREE 6 Amps MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts COLOUR White RAL9010 MATERIAL Flame retardant PC ABS WEIGHT 210g flush version 187g surface version IP RATING 3X o o OPERATING TEMPERATURE 0 C to 40 C W4426G 6 0m 2 5m Fascia 10mm deep 8 100mm Honeywell Ex Or St Marks Court North Street Horsham West Sussex RH12 1BW UK Tel 44 0 1942 719229 Fax 44 0 1942 508753 Email technicals...