background image

5

Photocell Control

 

 

 

 

i)  Regulating Photocell
 

Regulating photocell control tries to maintain a constant level of total illumination in the 
space controlled by dimming and brightening the controlled luminaires to compensate 
for changes in illumination from other sources.

With  the  photocell  configured  as  DISABLED  the  Regulating  Control  module  is 
influenced only by the BRIGHT-OUT setting. BRIGHT-OUT = YES allows it to hold-off 
the lights at the start of occupancy if natural light already exceeds SET-POINT LOW 
and to extinguish the lights during occupancy if total light, after the controlled luminaires 
have been dimmed to minimum, exceeds SET-POINT HIGH continuously for a period 
equal to the OFF DELAY . The lighting is restored immediately if the illumination level 
subsequently drops below SET-POINT LOW.

If the photocell is configured for ACTIVE or PASSIVE control of the relay switched load 
then the Regulating Control module adopts the decision made by the Switching Control 
module in the case of turn-on inhibit on entry, but still obeys the BRIGHT-OUT YES/NO 
setting with regard to turn-off during occupancy.   

ii)  Switching Photocell  (PHOTOCELL: ACTIVE or PASSIVE)

Both  ACTIVE or PASSIVE modes  hold off the controlled lighting on entry when natural 
light  is  sufficient,  i.e.  SET-POINT  LOW  is  exceeded,  but  only  ACTIVE  mode  will 
extinguish the lighting if natural light increases sufficiently during occupancy, i.e. SET-
POINT HIGH is exceeded continuously for a period equal to OFF DELAY. The lighting 
is restored immediately if the illumination level subsequently drops below SET-POINT 
LOW.

iii)  Photocell DISABLED

If the photocell is configured as DISABLED for relay Switching Control it will have no 
effect  on  the  control  of  that  load,  which  will  be  ON  continuously  during  periods  of 
occupancy unless commanded OFF via manual switch or infrared control. The photocell 
readings are still available for use by the Regulating Control module while in this mode.

Programming  the Photocell Set-points.

The parameters SET-POINT LOW and SET-POINT HIGH programme the detector’s 
photocell  response  The  SET-POINTS  can  be  manually  programmed  as  numbers 
between 1 (darkest) and 1023 (brightest). This number is not scaled   to correlate with 
‘lux’ measurements made using a light meter, but nevertheless is a true representation 
of the light level perceived by the detector. To assist with finding the appropriate SET-
POINT settings, the light level currently perceived by the photocell can be viewed on the 
QuickSet Pro screen briefly, following a download operation. The number represents the 
light level read immediately before the download took place. 

Summary of Contents for Ex-Or MLS2021DF

Page 1: ...uctions Note QuickSet Pro required for commissioning 1 MLS2021DSM MLS2021DALISM MLS2021DF MLS2021DSM for DSI ballasts MLS2021DALIF MLS2021DALISM for DALI ballasts Digital Gold PIR Detector with regulating photocell MLS2021DF MLS2021DALIF ...

Page 2: ...or DALI luminaires a switched load of up to 6 Amps or a combination of the two When controlling DSI or DALI ballasts the ballast type must not be mixed The DSI or DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity Free Digital Output terminals on the rear of the detector Each DSI or DALI luminaire is controlled completely by its digital input a...

Page 3: ... maintained NC NC 2 x MLS2021D In Parallel using Switched Output only LOAD Max 6Amps N E L Permanent or switched supply VOLT FREE OUTPUT VOLT FREE OUTPUT LIVE IN LIVE IN NEUTRAL NEUTRAL EARTH EARTH Any connection not shown is NO CONNECTION ONE SWITCH NC NC ONE SWITCH Relay outputs may be connected together in parallel to cover larger areas however the total load on all combined relay outputs must ...

Page 4: ...ogrammed if desired by use of the infrared programming tool QuickSet Pro All settings are retained in the event of a power failure Commissioning The units are supplied with the factory default settings shown below which make further commissioning unnecessary in many applications To make use of the programmable settings an infrared commissioning tool is required QuickSet Pro A ten second time delay...

Page 5: ...rolled lighting on entry when natural light is sufficient i e SET POINT LOW is exceeded but only ACTIVE mode will extinguish the lighting if natural light increases sufficiently during occupancy i e SET POINT HIGH is exceeded continuously for a period equal to OFF DELAY The lighting is restored immediately if the illumination level subsequently drops below SET POINT LOW iii Photocell DISABLED If t...

Page 6: ...ready on switch them on manually by pressing UTILITIES LIGHTSPOT MLS LCM IR REMOTE Luminaire OK QuickSet Pro or HC5A Fluorescent lights do not reach full output until up to 15 minutes after being switched on so ensure that the lights are fully warmed up before continuing 2 Wait until the time of day when the natural light level is at the point below which you would want the lights to be on and abo...

Page 7: ...neSwitch Dimming and the HC5A ImportantAdditional Notes 1 All terminals on this product are provided for final connections It is not intended that the productbe used as a junction box for loopingcables 2 A means for disconnection must be incorporated in the fixed wiring in accordance with the currentwiringregulations 3 Although nominally 12V the dimming output is not SELV and therefore should be t...

Page 8: ...NDED LOAD VOLT FREE 6 Amps MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts COLOUR White RAL9010 MATERIAL Flame retardant PC ABS WEIGHT 210g flush version 187g surface version IP RATING 3X o o OPERATING TEMPERATURE 0 C to 40 C W4426G 6 0m 2 5m Fascia 10mm deep 8 100mm Honeywell Ex Or St Marks Court North Street Horsham West Sussex RH12 1BW UK Tel 44 0 1942 719229 Fax 44 0 1942 508753 Email technicals...

Reviews: