background image

Photocell Control

 

 

 

 

i)  Regulating Photocell
 

Regulating photocell control tries to maintain a constant level of total illumination in the space controlled by 
dimming  and  brightening  the  controlled  luminaires  to  compensate  for  changes  in  illumination  from  other 
sources.

With  the  photocell  configured  as  DISABLED  the  Regulating  Control  module  is  influenced  only  by  the 
BRIGHT-OUT setting. BRIGHT-OUT = YES allows it to hold-off the lights at the start of occupancy if natural 
light already exceeds SET-POINT LOW and to extinguish the lights during occupancy if total light, after the 
controlled luminaires have been dimmed to minimum, exceeds SET-POINT HIGH continuously for a period 
equal to the OFF DELAY . The lighting is restored immediately if the illumination level subsequently drops 
below SET-POINT LOW.

If the photocell is configured for ACTIVE or PASSIVE control of the relay switched load then the Regulating 
Control module adopts the decision made by the Switching Control module in the case of turn-on inhibit on 
entry, but still obeys the BRIGHT-OUT YES/NO setting with regard to turn-off during occupancy.   

ii)  Switching Photocell  (PHOTOCELL: ACTIVE or PASSIVE)

Both  ACTIVE or PASSIVE modes  hold off the controlled lighting on entry when natural light is sufficient, i.e. 
SET-POINT LOW is exceeded, but only ACTIVE mode will extinguish the lighting if natural light increases 
sufficiently during occupancy, i.e. SET-POINT HIGH is exceeded continuously for a period equal to OFF 
DELAY. The lighting is restored immediately if the illumination level subsequently drops below SET-POINT 
LOW.

iii)  Photocell DISABLED

If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of 
that load, which will be ON continuously during periods of occupancy unless commanded OFF via manual 
switch or infrared control. The photocell readings are still available for use by the Regulating Control module 
while in this mode.

Programming  the Photocell Set-points

The parameters SET-POINT LOW and SET-POINT HIGH program the detector’s photocell response The 
SET-POINTS can be manually programmed as numbers between 1 (darkest) and 1023 (brightest). This 
number is not scaled  to correlate with ‘lux’ measurements made using a light meter, but nevertheless is a true 
representation of the light level perceived by the detector. To assist with finding the appropriate SET-POINT 
settings, the light level currently perceived by the photocell can be viewed on the programmer’s screen briefly, 
following a download operation. The number represents the light level read immediately before the download 
took place. 

Tip: Turn the lights off  with the QuickSet Pro (UTILITIES/IR REMOTE/HC5) to measure the perceived light 
level with no contribution from the controlled lighting.

 

Alternatively the SET-POINTS can be configured semi-automatically;

 

i) The Primary Interest is the Regulating Control Output.

With the photocell configured as DISABLED:-

Using QuickSet Pro (UTILITIES /  LIGHTSPOT/MLS/LCM / SET LIGHT LEVEL) or HC5A (+,- Scene 1),    
set the required light output from the controlled luminaires and then press and hold OK (QuickSet Pro) or 
Scene 1 (HC5A) until the controlled lights "blink" to indicate that a new SET-POINT LOW has been stored 
and a calculated SET-POINT HIGH has also been inserted. Using the QuickSet Pro, the photocell can now 
be re-configured as ACTIVE or PASSIVE if required.

5

Summary of Contents for Ex-Or Digital Gold Series

Page 1: ...mmissioning Instructions Note QuickSet Pro required for commissioning MLS2421DF MLS2421DSM for DSI ballasts MLS2421DALIF MLS2421DALISM for DALI ballasts Digital Gold Series Detector with regulating photocell MLS2421DF MLS2421DALIF MLS2421DALIFXAA ...

Page 2: ...eration it is essential that units of the same colour code do not occupy adjacent positions in open plan areas or in adjoining rooms see below Yellow Blue Red Green Red Green Yellow Blue Red Green Yellow Blue Yellow Green Green Yellow Green Yellow Yellow Blue Red Green Red Green Yellow Blue Red Green Yellow Blue Blue Red Red Blue Red Blue Yellow Blue Red Green Red Green Yellow Blue Red Green Yello...

Page 3: ...ts are also being controlled the digital outputs from each detector must not be mixed even if they are of the same type Wiring Examples Digital Output MLS BUS These Connections are Polarity Free 1 2 1 2 Using OneSwitch MLS Switched and Digital Outputs N E L Permanent or switched supply VOLT FREE OUTPUT LIVE NEUTRAL EARTH ONESWITCH DIMMING Digital output MLS Bus Connection Some MLS devices require ...

Page 4: ...ned in the event of a power failure and can be re programmed any number of times Factory Default Settings These are the settings to which the units have been programmed before they leave the factory Parameter Power up Response Off Delay On Sensitivity Off Sensitivity Bus Connect 1st Zone 2nd Zone 3rd Zone 4th Zone Corridor 1 Begin End Corridor 2 Begin End Global 1 Rx Global 2 Rx Manual I P Start L...

Page 5: ...hotocell DISABLED If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control The photocell readings are still available for use by the Regulating Control module while in this mode Programming the Photocell Set points The...

Page 6: ... the difference between them is equal to slightly more than the contribution made by the electric lighting This is the perfect amount of hysteresis to ensure that the lights will not oscillate OneSwitch OneSwitch Dimming affords local control to the end user whereby a simple momentary push to make wall switch can be used to raise or lower the lighting level or toggle the output of the unit ON or O...

Page 7: ... that the photocellis on the ceilinglookingdown it is not possiblefor measurementsmade with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent Therefore products of this type should be regarded as capable of maintaining an APPROXIMATE lightlevelonly 6 This equipment switches lights no more frequently than would a re...

Page 8: ...Europe PRODUCT RATING AND RECOMMENDED CIRCUIT PROTECTION 10 Amps MAXIMUM RECOMMENDED LOAD VOLT FREE 10 Amps MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT 3 0m RANGE Approx 7m dia at 2 4m ceiling height OFF DELAY 1 min 96 hours plus 10 second walk test mode PHOTOCELL Passive Active Regulating adjustable 50 5000 lux MATERIAL Flame retardant PC ABS COLOUR White RAL...

Reviews: