Electrical Connections

These Digital Gold detectors should be connected in accordance with the diagrams below. Both the Digital Output 
and MLS connections are polarity-free however other MLS products require that polarity be maintained. The MLS 
cable should be mains-rated, unscreened, twisted pair of at least 1.5mm CSA.  For further information please refer 
to Wiring Application Guide AN4001. 

Please note that UltraLite versions of these detectors (suffix CWL7) do 

not offer MLS functionality and cannot be connected using MLS cable.

 

These detectors are designed to control up to 25 DSI or DALI luminaires, a switched load of up to 6 Amps or a 
combination of the two. When controlling DSI or DALI ballasts the ballast type must not be mixed. The DSI or 
DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity-Free Digital 
Output terminals on the rear of the detector. Each DSI or DALI luminaire is controlled completely by its digital input 
and therefore would normally have a permanent power supply. Turning the power off to some lights within a control 
circuit will not have affect the operation of those lights that remain powered up and under the control of the detector. 
When switching via the volt-free output multiple detectors may be connected in parallel provided the controlled 
load does not exceed 6 Amps. If digital ballasts are also being controlled the digital outputs from each detector 
must not be mixed even if they are of the same type. 

Wiring Examples

Digital

Output

MLS 
BUS

These Connections are Polarity-Free

1

2

1

2

Using OneSwitch, MLS*, Switched 
and Digital Outputs

N

E

L

Permanent 
or switched
supply

VOLT-
FREE 
OUTPUT

LIVE

NEUTRAL

EARTH

ONESWITCH
DIMMING

Digital output

MLS Bus Connection
(Some MLS devices require
that polarity be maintained)

Momentary
push-to-make
switch

Please note that the Earth terminal has no internal connection 
and is used for termination only. 

Digital

Output

MLS 
BUS

These Connections are Polarity-Free

1

2

1

2

Using Switched Output and MLS*

N

E

L

Permanent 
or switched
supply

VOLT-
FREE 
OUTPUT

LIVE

NEUTRAL

EARTH

ONESWITCH
DIMMING

MLS Bus Connection
(Some MLS devices require
that polarity be maintained)

NC

NC

Please note that the Earth terminal has no internal connection 
and is used for termination only. 

VOLT-
FREE 
OUTPUT

NEUTRAL

LIVE IN

EARTH

ONE

SWITCH

NC

VOLT-
FREE 
OUTPUT

NEUTRAL

LIVE IN

EARTH

ONE

SWITCH

NC

E

L

N

Permanent 
or switched
supply

2 x MLS2421D In Parallel, using 
Switched Output only

Any connection not shown is NO CONNECTION

Relay outputs may be connected together in 
parallel to cover larger areas, however the 
total load on all combined relay outputs 
must not exceed 10 Amps. 

* UltraLite-version detectors (suffix CWL7) 
do not offer MLS functionality and cannot 
be connected using MLS cable. 

* UltraLite-version detectors (suffix CWL7) 
do not offer MLS functionality and cannot 
be connected using MLS cable. 

LOAD

(MAX 10 AMPS)

LOAD

(MAX 10 AMPS)

LOAD

(Max 10 Amps)

Summary of Contents for Ex-Or Digital Gold Series

Page 1: ...mmissioning Instructions Note QuickSet Pro required for commissioning MLS2421DF MLS2421DSM for DSI ballasts MLS2421DALIF MLS2421DALISM for DALI ballasts Digital Gold Series Detector with regulating photocell MLS2421DF MLS2421DALIF MLS2421DALIFXAA ...

Page 2: ...eration it is essential that units of the same colour code do not occupy adjacent positions in open plan areas or in adjoining rooms see below Yellow Blue Red Green Red Green Yellow Blue Red Green Yellow Blue Yellow Green Green Yellow Green Yellow Yellow Blue Red Green Red Green Yellow Blue Red Green Yellow Blue Blue Red Red Blue Red Blue Yellow Blue Red Green Red Green Yellow Blue Red Green Yello...

Page 3: ...ts are also being controlled the digital outputs from each detector must not be mixed even if they are of the same type Wiring Examples Digital Output MLS BUS These Connections are Polarity Free 1 2 1 2 Using OneSwitch MLS Switched and Digital Outputs N E L Permanent or switched supply VOLT FREE OUTPUT LIVE NEUTRAL EARTH ONESWITCH DIMMING Digital output MLS Bus Connection Some MLS devices require ...

Page 4: ...ned in the event of a power failure and can be re programmed any number of times Factory Default Settings These are the settings to which the units have been programmed before they leave the factory Parameter Power up Response Off Delay On Sensitivity Off Sensitivity Bus Connect 1st Zone 2nd Zone 3rd Zone 4th Zone Corridor 1 Begin End Corridor 2 Begin End Global 1 Rx Global 2 Rx Manual I P Start L...

Page 5: ...hotocell DISABLED If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control The photocell readings are still available for use by the Regulating Control module while in this mode Programming the Photocell Set points The...

Page 6: ... the difference between them is equal to slightly more than the contribution made by the electric lighting This is the perfect amount of hysteresis to ensure that the lights will not oscillate OneSwitch OneSwitch Dimming affords local control to the end user whereby a simple momentary push to make wall switch can be used to raise or lower the lighting level or toggle the output of the unit ON or O...

Page 7: ... that the photocellis on the ceilinglookingdown it is not possiblefor measurementsmade with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent Therefore products of this type should be regarded as capable of maintaining an APPROXIMATE lightlevelonly 6 This equipment switches lights no more frequently than would a re...

Page 8: ...Europe PRODUCT RATING AND RECOMMENDED CIRCUIT PROTECTION 10 Amps MAXIMUM RECOMMENDED LOAD VOLT FREE 10 Amps MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT 3 0m RANGE Approx 7m dia at 2 4m ceiling height OFF DELAY 1 min 96 hours plus 10 second walk test mode PHOTOCELL Passive Active Regulating adjustable 50 5000 lux MATERIAL Flame retardant PC ABS COLOUR White RAL...