Honeywell Ex-Or CDH8U5 Installation And Commissioning Instructions Download Page 7

Connections

-7-

Width (W) = 213 mm
Height(H) = 62 mm
Depth(D)  = 91 mm
Weight 

= 0.62kg approx

Technical Data

Operational supply: 

230VAC ~50Hz/60Hz 

Power consumption: 

18W maximum

Product rating & recommended circuit protection:  16A or 20A MCB
Maximum switched live load (per channel): 

 6

  A

Max total switched live load: 

16A

Digital dimming ballasts per channel: 

 10 maximum

Digital dimming ballasts per LCM: 

 40 maximum

1-10V dimming ballasts per channel:   

20mA (sinking only). See manufacturer's specification: worst case 10 Ballasts but Philips HF-R, for example,

  

   20 Ballasts. Observe switched live load limit above.  

Maintained live output:  

6A

VF output: 

 6A

SELV output: 

 1A @ 24V  AC/DC

Mains supply terminal capacity:    

2x2.5mm² or 1x4mm²

Mains switched live output connection:    

1x2.5mm² or 1x4mm²

Override switch input connector:  

2.5mm²

MLS bus connector: 

 2.5mm²

MLS bus cable: 

Two-core multi-stranded twisted pair Cross-sectional area 1.5mm² unscreened 600/1000V rated 

                                                                             LSOH insulated: see Application Note AN4001
Case material: 

Self-extinguishing blend PC/ABS

Case finish: 

Gray RAL 7035

IP rating: 

 20

 

Dimensions

Enclosure 

An enclosure (K5612S MET) is available for this product.  
It provides integral connection bars fitted with link and features a robust galvanized metal base, lid and door.  
The DIN rail embodies a useful alignment and fixing mechanism that allows quick installation.  
Cable entry points are located on top, bottom, side and rear surfaces.
Colour: 

White

Dimensions: 

 310mm x 244mm x 116mm

Protection: 

BS EN 60529 to IP 2XC

Dimming
Channels

Mains
Input

Switched
Live Outputs

Volt-free 
Channels

Additional

Switches

Switches 

1-3

View on top side of unit

View on bottom side of unit

Comms Bus (MLS)

Aux 1

Detectors

91mm

62mm

213mm

Summary of Contents for Ex-Or CDH8U5

Page 1: ...CDH8U5 8 Channel Programmable Intelligent Lighting Control Module Installation and Commissioning Instructions Product option shown here for illustrative purposes only ...

Page 2: ... cable before termination to the unit s pluggable connectors CAUTION DO NOT CONNECT MAINS TO THE MLS BUS OR DIMMING OUTPUTS Connecting the Luminaires Variants of the CDH8U5 are provided to control DSI available on configuration only DALI and 1 10V ballasts See Part Numbers section for more details Note Dimming Ballast types CANNOT BE MIXED on a single CDH8U5 The CDH8U5 is equipped with 8 two wire ...

Page 3: ...lso be compromised Connecting Switches The CDH8U5 is equipped with SELV switch inputs which will typically be two way centre off momentary rockers e g the MK K4900 range The logical function of a switch can be configured from a wide range of options and its action can be associated with any combination of channels The switch connection consists of a 3 pole pluggable terminal block comprising a com...

Page 4: ...trol Module provides a gateway to the wider MLS system but connecting directly to a CDW12U5 CDH4U5 or CDH8U5 LCM also allows use in non MLS applications Easy touch screen control of AV and lighting User interface panels or touch screens from the Ex Or Scene Select II range can also be used Connecting to the MLS Digital Network It is imperative that the MLS Bus be wired in the correct type of cable...

Page 5: ...rmines different actions when the area is vacant dependent on time of day Background Tmr 10 seconds to 96 hours or none Applies to Alt Exit Scenes and some Background Level scenes i e not XTN and BLD options When Background Timer expires channel s output turns off Fade to Off Yes No Bus Connect Yes No Zones 1 4 None Zone number 1 100 Common 1 2 3 Zones 1 4 TRX Tx Rx Tx Only Rx Only Determines how ...

Page 6: ...splays the CDH 8 Channels V2 screen 4 Scroll down to Ballast and press OK This displays a sub menu with multiple operations 5 Scroll down to DSI 1 and press OK The selected operation is applied 6 Use the RightArrow Key to navigate across all the channels and repeat steps 4 to 5 to edit the Ballast to DSI 1 operation for each channel 7 Stand directly below the unit and press Upload wait for about 5...

Page 7: ...mm or 1x4mm Override switch input connector 2 5mm MLS bus connector 2 5mm MLS bus cable Two core multi stranded twisted pair Cross sectional area 1 5mm unscreened 600 1000V rated LSOH insulated see Application Note AN4001 Case material Self extinguishing blend PC ABS Case finish Gray RAL7035 IP rating 20 Dimensions Enclosure An enclosure K5612S MET is available for this product It provides integra...

Page 8: ...Module Plasterboard Fixing Kit MLS2001CDR 360 PIR detector Obsolete no longer made Detector Patch Leads BT5E030GY 3m Patch Lead BT5E050GY 5m Patch Lead BT5E100GY 10m Patch Lead Connectors CDHHDIP 10 way Plug green SELV switch input 1 piece CDHDOP 2 way Plug blue dimming outputs 2 pieces CDHSLOP 2 way Plug black switched live outputs 2 pieces CDHIP 3 way Plug green SELV switch inputs and auxiliary ...