Honeywell Ex-Or CDH8U5 Installation And Commissioning Instructions Download Page 3

The diagram above shows Maintained Live generated from the internal link of 
the mains supplied to the unit.  Alternatively, the external shorting link can be 
removed and an external supply (from the same phase) can be connected to 
create a Maintained Output.

Connecting Presence Detectors

The following SELV detectors are designed to interface to the CDH8U5:
MLS2500CDR 

Corner-mount  Microwave  presence  detector  with 

photocell, semi-flush mounted.   Available with surface 
mount (SM suffix).

MLS2401CDR 

360° Microwave presence detector with photocell, flush 

mounted.    Available  in  surface  mount  version  (SM 
suffix).

MLS3000CDRF 

360°  PIR  presence  detector  with  photocell,  flush 

mounted.    Available  in  surface  mount  version  (SM 
suffix).

MLS3003CDRF 

360°  PIR  presence  detector  with  photocell  and  tilting 

lens,    flush  mounted.    Available  in  surface  mount 
version (SM suffix).

MLS3003CDRMBF Mid-Bay 360° PIR presence detector with photocell and 

tilting lens, flush mounted.   Available in surface mount 
version (SM suffix). 

MLS3003CDRHBF Hi-Bay 360° PIR presence detector with photocell and 

tilting lens, flush mounted.   Available in surface mount 
version (SM suffix).

MLSM2002CDR 

Controller for a 360° PIR detector with photocell.  Used 

with the DHS OR DHW mini-head to form an integral 
luminaire-mounted unit.  

Each  connects  to  the  CDH8U5  by  means  of  an  Ethernet-style  RJ45 
connector terminated patch lead which are available ready-made in 3m, 5m 
and 10m lengths.  Up to five detectors may be connected to a CDH8U5. 

Positioning Presence Detectors

For  information  on  installing  and  positioning  detectors,  please  refer  to  the 
installation instructions provided with the particular detector.

Note that if the SELV status of any one of the switches 
is compromised by reason of inadequate insulation or 
segregation of the cabling, then the SELV status of all 
other switches AND OF THE DETECTORS will also 
be compromised. 

Connecting Switches 

The CDH8U5 is equipped with  SELV switch inputs which will typically be two 
way,  centre  off,  momentary  rockers,(e.g.  the  MK  K4900  range). The  logical 
function of a switch can be configured from a wide range of options and its 
action  can  be  associated  with  any  combination  of  channels.    The  switch 
connection consists of a 3-pole pluggable terminal block comprising a common 
and two returns from normally open contacts. Six plugs are provided with each 
CDH8U5.   The plug type is common with the Aux output channel.   Additional 
plugs can be ordered using the code CDHIP (5 pieces per pack).

The  recommended  cable  for  use  with  the  SELV  switches  is  3-core  3183Y 
Stranded PVC Mains Power Cable H05VV-F, 0.75 mm² CSA 6 A 100m, 300 V, 
500 V.

 The maximum allowable cable length between the switch mechanism 

and the CDH8U5 terminal block is 100m. 

Three separate single wires should not be used.

Connecting Switches with High Density Connector

The CDH8U5 also has provision to connect 5 additional SELV switch inputs in 
order to meet the requirement of additional inputs.  Unlike the 3-pole connector, 
this provides two terminals A&B for each of the 5 inputs.  The high density input 
plug (not supplied) can be ordered using the code CDHHDIP. 

 

Note: For the switches on the High Density Connector (SW 8-12) use any of the 
‘C’ common connectors from switches 1-5.

For HD switches 8-12, use any of the ‘COM’ connections from switch inputs 1-5.

Connecting SELV Output, Aux 1

The CDH8U5 has a single SELV change-over output for signalling purposes 
only.   This can be used to signal an external system e.g. BMS. Connection is 
made via a 3-pole pluggable terminal block (supplied) of the same type used for 
SELV inputs 1-5 (CDHIP).

Note: The external voltage connected to Aux 1 must never exceed 24V 
AC/DC.   The  SELV Output must be used only for signalling purposes. 
Maximum current shall not exceed 1A.  

B Com A

-3-

Live  in  from 
same Phase

Switched Live

Internal Link

Maintained 
Output

External

shorting

Links

Wiring for HD SELV Input:

External BMS

Signal In

24V AC/DC

Summary of Contents for Ex-Or CDH8U5

Page 1: ...CDH8U5 8 Channel Programmable Intelligent Lighting Control Module Installation and Commissioning Instructions Product option shown here for illustrative purposes only ...

Page 2: ... cable before termination to the unit s pluggable connectors CAUTION DO NOT CONNECT MAINS TO THE MLS BUS OR DIMMING OUTPUTS Connecting the Luminaires Variants of the CDH8U5 are provided to control DSI available on configuration only DALI and 1 10V ballasts See Part Numbers section for more details Note Dimming Ballast types CANNOT BE MIXED on a single CDH8U5 The CDH8U5 is equipped with 8 two wire ...

Page 3: ...lso be compromised Connecting Switches The CDH8U5 is equipped with SELV switch inputs which will typically be two way centre off momentary rockers e g the MK K4900 range The logical function of a switch can be configured from a wide range of options and its action can be associated with any combination of channels The switch connection consists of a 3 pole pluggable terminal block comprising a com...

Page 4: ...trol Module provides a gateway to the wider MLS system but connecting directly to a CDW12U5 CDH4U5 or CDH8U5 LCM also allows use in non MLS applications Easy touch screen control of AV and lighting User interface panels or touch screens from the Ex Or Scene Select II range can also be used Connecting to the MLS Digital Network It is imperative that the MLS Bus be wired in the correct type of cable...

Page 5: ...rmines different actions when the area is vacant dependent on time of day Background Tmr 10 seconds to 96 hours or none Applies to Alt Exit Scenes and some Background Level scenes i e not XTN and BLD options When Background Timer expires channel s output turns off Fade to Off Yes No Bus Connect Yes No Zones 1 4 None Zone number 1 100 Common 1 2 3 Zones 1 4 TRX Tx Rx Tx Only Rx Only Determines how ...

Page 6: ...splays the CDH 8 Channels V2 screen 4 Scroll down to Ballast and press OK This displays a sub menu with multiple operations 5 Scroll down to DSI 1 and press OK The selected operation is applied 6 Use the RightArrow Key to navigate across all the channels and repeat steps 4 to 5 to edit the Ballast to DSI 1 operation for each channel 7 Stand directly below the unit and press Upload wait for about 5...

Page 7: ...mm or 1x4mm Override switch input connector 2 5mm MLS bus connector 2 5mm MLS bus cable Two core multi stranded twisted pair Cross sectional area 1 5mm unscreened 600 1000V rated LSOH insulated see Application Note AN4001 Case material Self extinguishing blend PC ABS Case finish Gray RAL7035 IP rating 20 Dimensions Enclosure An enclosure K5612S MET is available for this product It provides integra...

Page 8: ...Module Plasterboard Fixing Kit MLS2001CDR 360 PIR detector Obsolete no longer made Detector Patch Leads BT5E030GY 3m Patch Lead BT5E050GY 5m Patch Lead BT5E100GY 10m Patch Lead Connectors CDHHDIP 10 way Plug green SELV switch input 1 piece CDHDOP 2 way Plug blue dimming outputs 2 pieces CDHSLOP 2 way Plug black switched live outputs 2 pieces CDHIP 3 way Plug green SELV switch inputs and auxiliary ...