Honeywell Ex-Or CDH8U5 Installation And Commissioning Instructions Download Page 4

-4-

In

In

Out

Out

MLS Bus 1

MLS Bus 2

Easy integration of lighting and AV systems

The  AVINTCDR  provides  an  interface  between  MLS  Connect  Digital 
Intelligent  Lighting  Control  Module  (i.e.  CDW12U5-B,  CDH4U5-B  or 
CDH8U5-B) or from any Audio Visual system that uses Dynet commands 
via RS232 or RS485.
When the Ex-Or interface receives a command from the AV system, the 
decoded  signal  is  then  sent  to  the  CD  Box  where  it  is  translated  (a 
command can recall scenes 1 to 6 of a zone in the range 1 to 100) and can 
be forwarded on to the MLS Digital Network if connected to it.
The AVINTCDR allows the AV system to adjust lighting and recall lighting 
scenes and behaviors via the Ex-Or MLS Digital Network System. In this 
way, initiating a projector presentation, for example, would automatically 
adjust the lighting to a suitable scene without needing any separate action 
to dim the lights.
The MLS Connect Digital Lighting Control Module provides a gateway to 
the wider MLS system but connecting directly to a CDW12U5, CDH4U5 or 
CDH8U5 LCM also allows use in non-MLS applications.

Easy touch screen control of AV and lighting 

User interface panels or touch screens from the Ex-Or Scene Select II 
range can also be used.

Connecting to the MLS Digital Network

It is imperative that the MLS Bus be wired in the correct type of cable. 
Normally
it  should  be  Two-core  multi-stranded  twisted  pair  Cross-sectional  area 
1.5mm2  unscreened  600/1000V  rated  LSOH  insulated.  Please  see 
AN4001  from  our  website  to  learn  further  details  on  the  MLS  Digital 
Network regarding cable needs as it differs according to different designs. 
This can make your installation easier.
A MLS Digital Network will need a specific power supply. We offer this MLS
Digital Network power supply integrated in the Model CDH8U5-RB and its
variants CDH8U5-RBA and CDH8U5-RBDALI. Alternatively you can use 
the
Rb2000, RB2000LT plus variants on the CDH4U5.

Do not connect Mains to the MLS Bus.

For connection of Bus Power Supply variants, see also Application Note 
AN4030 from our website.

 

Summary of Contents for Ex-Or CDH8U5

Page 1: ...CDH8U5 8 Channel Programmable Intelligent Lighting Control Module Installation and Commissioning Instructions Product option shown here for illustrative purposes only ...

Page 2: ... cable before termination to the unit s pluggable connectors CAUTION DO NOT CONNECT MAINS TO THE MLS BUS OR DIMMING OUTPUTS Connecting the Luminaires Variants of the CDH8U5 are provided to control DSI available on configuration only DALI and 1 10V ballasts See Part Numbers section for more details Note Dimming Ballast types CANNOT BE MIXED on a single CDH8U5 The CDH8U5 is equipped with 8 two wire ...

Page 3: ...lso be compromised Connecting Switches The CDH8U5 is equipped with SELV switch inputs which will typically be two way centre off momentary rockers e g the MK K4900 range The logical function of a switch can be configured from a wide range of options and its action can be associated with any combination of channels The switch connection consists of a 3 pole pluggable terminal block comprising a com...

Page 4: ...trol Module provides a gateway to the wider MLS system but connecting directly to a CDW12U5 CDH4U5 or CDH8U5 LCM also allows use in non MLS applications Easy touch screen control of AV and lighting User interface panels or touch screens from the Ex Or Scene Select II range can also be used Connecting to the MLS Digital Network It is imperative that the MLS Bus be wired in the correct type of cable...

Page 5: ...rmines different actions when the area is vacant dependent on time of day Background Tmr 10 seconds to 96 hours or none Applies to Alt Exit Scenes and some Background Level scenes i e not XTN and BLD options When Background Timer expires channel s output turns off Fade to Off Yes No Bus Connect Yes No Zones 1 4 None Zone number 1 100 Common 1 2 3 Zones 1 4 TRX Tx Rx Tx Only Rx Only Determines how ...

Page 6: ...splays the CDH 8 Channels V2 screen 4 Scroll down to Ballast and press OK This displays a sub menu with multiple operations 5 Scroll down to DSI 1 and press OK The selected operation is applied 6 Use the RightArrow Key to navigate across all the channels and repeat steps 4 to 5 to edit the Ballast to DSI 1 operation for each channel 7 Stand directly below the unit and press Upload wait for about 5...

Page 7: ...mm or 1x4mm Override switch input connector 2 5mm MLS bus connector 2 5mm MLS bus cable Two core multi stranded twisted pair Cross sectional area 1 5mm unscreened 600 1000V rated LSOH insulated see Application Note AN4001 Case material Self extinguishing blend PC ABS Case finish Gray RAL7035 IP rating 20 Dimensions Enclosure An enclosure K5612S MET is available for this product It provides integra...

Page 8: ...Module Plasterboard Fixing Kit MLS2001CDR 360 PIR detector Obsolete no longer made Detector Patch Leads BT5E030GY 3m Patch Lead BT5E050GY 5m Patch Lead BT5E100GY 10m Patch Lead Connectors CDHHDIP 10 way Plug green SELV switch input 1 piece CDHDOP 2 way Plug blue dimming outputs 2 pieces CDHSLOP 2 way Plug black switched live outputs 2 pieces CDHIP 3 way Plug green SELV switch inputs and auxiliary ...

Reviews: