Honeywell Ex-Or CDH4U5 Installation And Commissioning Instructions Download Page 6

Commissioning

The LCM is commissioned using a dedicated programme running on a Windows-based computer.  Commissioning settings may then be directly uploaded from 

the computer to the LCM or transferred to an HP2000 hand-held programmer for easy upload on site.
Communication from the PC can be by means of a USB infrared transceiver which can signal directly to the LCM’s on-board infrared port over a short range or via 

any attached presence detector from beneath (range: 1-3m).
The main parameters for configuration are tabulated below.  These parameters may be re-programmed any number of times and all settings will be retained in 

the event of a power loss.  

SELV Switch Options

Description

Sustain

Causes assigned channels to act as if an occupancy detector continues to detect occupancy

Brighten 

Raises light level .  Works only with dimmable ballasts. 

Dim

Lowers Light level .  Works only with dimmable ballasts. 

Off

Turns lamp OFF

Scene 01..06

Recalls Scene assigned (any scene 01 to 06 as configured)

On

Turns lamp ON

Partition

Initiates logical partition of a room. Refer to AN4002 for more details

OneSwitch

Simple momentary push-to-make wallswitch that can be used to raise or lower the lighting level or toggle the output of 
the unit ON or OFF.  Short press toggles output ON and OFF; long press will ramp the light level Up or Down.

On-Dim

Short Press will turn the output ON, long press will lower the light level

Off-Brighten

Short Press will turn the output OFF, long press will raise the light level

On-Brighten

Short Press will turn the output ON, long press will raise the light level

Off-Dim

Short Press will turn the output OFF, long press will lower the light level

Emergency Tst

Initiates manual test of emergency luminaire by turning OFF the Maintained Live

Emergency End

Restores Maintained Live to end the Emergency Test

Description of Switch Input Options:

-6-

PARAMETERS

OPTIONS

Per Box Parameters:

Switch A: 1-5, Switch B: 1 -5,  
Switch 6A*, 6B*, 7A*, 7B*

User may choose any option for Switch A or Switch B from following: 

Sustain / Brighten / Dim / Off / Scene 01..06 / On / Partition / OneSwitch / On-Dim / Off-Brighten / On-Brighten / Off-Dim / 
Emergency Test / Emergency End  (See separate table for detailed description of Switch Input options)

Detector 1-5: Range

Max 100%, Max 75%, Max 50%
High 100%, High 75%, High 50%
Med 100%, Med 75%, Med 50%
Low 100%, Low 75%, Low 50%
Min 100%, Min 75%

Per Channel Parameters:

Ballast Type

Non-Dimming, 1% DSI, 3% DSI, 10% DSI, 1% DALI, 3% DALI, 10% DALI

Assigned Detectors

Detectors 1-5: Assigned or not assigned to this channel

Assigned Photocell

Photocell 1-5 (in Detectors 1-5): Assigned or not assigned to this channel

Assigned Switches

Switch A & B: Assigned or not assigned to this channel

Power Up

On / Off

Response

Auto, Manual/Bus, Manual only

Off Delay (Main Time Delay)

10 seconds to 96 hours / Disabled

Bus Connect

Yes / No

Zones 1-4

Zone number 1-100 

Corridor 1-2: Begin

Zone number 1-100 

Corridor 1-2: End

Zone number 1-100 

Global 1-2 Rx

Yes / No

Manual I/P (Local/Share for Each Switch)

Obey locally only / Obey locally and transmit command on MLS bus

Start Lamps

Max / Min

Entry Scene

Scene 1-6

Lamp Max

100%, 90%, 80%, 70%, 50%, 45%, 40%, 35%, 30%, 25%, 20%, 15%, 10%  

Note: Not required for VF or SELV Outputs

When Vacant

Off until next occupancy detection

(Turn-Off Options)

Minimum, 25% or Scene 6 until next occupancy detection
Minimum, 25% or Scene 6 for 3 x Off Delay
Minimum, 25% or Scene 6 until the building is empty

Fade to Off

Yes / No

Bright Out

Yes / No

Photocell

Regulate (100%, 90%, 80%, 70%, 60%, 50%) / Passive / Active / Disabled  

Note: Not required for VF or SELV Outputs

Set-Point Low (Photocell Lower Threshold)

0-1024 (used in Regulating Scene 1)  

Note: Not required for VF or SELV Outputs

Set-Point High (Photocell Upper Threshold)

0-1024 (used in Regulating Scene 1)  

Note: Not required for VF or SELV Outputs

Scene 2

Output 0-100%

Scene 3

Output 0-100%

Scene 4

Output 0-100%

Scene 5

Output 0-100%

Scene 6

Output 0-100%

100 Hour Burn-in 

Burn-in 100hrs/Cancel/Resume - See Application Note AN4028

* Planned

Summary of Contents for Ex-Or CDH4U5

Page 1: ...CDH4U5 4 Channel Programmable Intelligent Lighting Control Module Installation and Commissioning Instructions ...

Page 2: ...uct simplifies installation whilst providing an intelligent lighting control system Provision is made for 4 volt free power outputs rated for 415V isolation Additionally the unit features a switched output for Maintained Live to allow initiation of Emergency Lighting Test The CDH4U5 has the ability to operate from dual supplies with the capability to modify its operating behaviour when failure is ...

Page 3: ...wn in the diagram one or more channels may be powered from either of the supplies Ballast N L E D D Ballast N L E D D Ballast Ballast Ballast N N N L L L E E E D D D D D D 1 DETECTOR PORTS 2 3 4 5 B COM A B COM A B COM A B COM A B COM A 1 2 3 4 5 SELV SWITCH INPUTS VOLT FREE CHANNELS 1 1 2 2 COMMS BUS 4 3 2 1 DIMMING CHANNELS N L MAINS INPUT VOLT FREE CHANNELS N2 L2 N1 L1 CH2 ML CH3 CH1 CH4 D D CH...

Page 4: ... the unit an external change over contactor is required Line terminals from each of the supplies N1 L1 and N2 L2 are connected via the change over contactor The Live and Neutral outputs from the contactor are connected to the mains input of the unit In the case of failure of one of the supplies the change over contactor switches to the alternative supply to ensure continuous supply to the unit As ...

Page 5: ...k comprising a common and two returns from normally open contacts Four plugs are provided with each CDH4U5 additional plugs can be ordered using the code CDHIP 5 pieces per pack Note that if the SELV status of any one of the switches is compromised by reason of inadequate insulation or segregation of the cabling then the SELV status of all other switchesAND OF THE DETECTORS will also be compromise...

Page 6: ...ns 6 PARAMETERS OPTIONS Per Box Parameters Switch A 1 5 Switch B 1 5 Switch 6A 6B 7A 7B User may choose any option for Switch A or Switch B from following Sustain Brighten Dim Off Scene 01 06 On Partition OneSwitch On Dim Off Brighten On Brighten Off Dim Emergency Test Emergency End See separate table for detailed description of Switch Input options Detector 1 5 Range Max 100 Max 75 Max 50 High 10...

Page 7: ...r example 20 Ballasts Maintained live output 6A Mains supply terminal capacity 2x2 5mm or 1x4mm Override switch input connector 2 5mm MLS bus connector 2 5mm MLS bus cable 1 5mm unscreened twisted pair seeApplication NoteAN4001 Case material Self extinguishing blend PC ABS Case finish Gray RAL7035 IPrating 20 Dimensions 9 m 1m 62mm 3m 21 m Volt free Channels Volt free Channels Dimming Channels Com...

Page 8: ... Power Supply Unit Wireless switch enabled DSI Dimming CDH4U5 RBDALIWL 4 Channel LCM with MLS Bus Power Supply Unit Wireless switch enabled DALI Dimming Plug in Cards CDHDC Plug in Digital Dimming Card CDHAC Plug in Analogue Dimming Card CDHBC Plug in MLS Bus Interface CDHRB Plug in MLS Bus Power Supply Unit CDHWL Plug in Wireless EnOcean Card Presence Detectors with photocell MLS2500CDR Corner mo...

Reviews: