Honeywell Ex-Or CDH4U5 Installation And Commissioning Instructions Download Page 2

DIMMING CHANNELS

MAINS  INPUT

N

L

N1

3

L

E

N

Electrical Connections

The connections to this equipment should be made only by a suitably 

qualified person and in accordance with the current wiring regulations.  
A  means  of  disconnection  must  be  incorporated  in  the  fixed  mains 

wiring to this box in accordance with the current wiring regulations.  

All the connections should be routed ensuring adequate strain relief on the 

cable before termination to the unit’s pluggable connectors. 

CAUTION: DO NOT CONNECT MAINS TO THE MLS BUS OR DIMMING 

OUTPUTS. 

Connecting the Luminaires

Variants of the CDH4U5 are provided to control DSI, DALI and 1-10V ballasts.  (See Part Numbers section for more details.) 

Note: Dimming ballast types CANNOT BE MIXED on a single CDH4U5.

The CDH4U5 is equipped with 4 two-wire pluggable terminals for dimming outputs, 2 three-wire and 2 two-wire pluggable terminals for volt-free outputs.
The CDH4U5 has provision to connect more than one supply from different phases in three different scenarios: a) Single Supply,  b) Essential and non-essential 

supplies and c) Two  supplies equally likely to drop out .

Aux 3

RELAY OUTPUTS

a) Single Supply

Introduction

The  CDH4U5  is  an  intelligent  LCM  providing  connections  for  multiple 

luminaires*, up to 5 presence detectors and up to 5 SELV inputs. The product 

simplifies installation whilst providing an intelligent lighting control system. 

Provision  is  made  for  4  volt-free  power  outputs  rated  for  415V  isolation. 

Additionally, the unit features a switched output for Maintained Live to allow 

initiation of Emergency Lighting Test.  The CDH4U5 has the ability to operate 

from dual supplies with the capability to modify its operating behaviour when 

failure is detected on one of the supplies. This feature is described in greater 

detail in application note AN4027.   
*Note: Refer to Technical Data section to find out maximum allowable number

of luminaires.     

Fixing 

The CDH4U5 should be mounted in an enclosure with a DIN-rail.

Consideration should be given to access for installation and maintenance 

when selecting the enclosure and location. The external enclosure DIN-rail 

should comply with EN 60715. 

Ballast

N

L

E

D

D

Ballast

N

L

E

D

D

Ballast

Ballast

Ballast

N

N

N

L

L

L

E

E

E

D

D

D

D

D

D

1

DETECTOR PORTS

2

3

4

5

B  COM  A

B  COM  A

B  COM  A

B  COM  A

B  COM  A

1

2

3

4

5

SELV SWITCH INPUTS

VOLT FREE CHANNELS

1  -  1       2  -  2

COMMS BUS

+   4   -

+   3   -

+   2   -

+   1   -

DIMMING CHANNELS

N

L

MAINS INPUT

VOLT FREE CHANNELS

N2   L2

N1   L1

CH2

ML

CH3

CH1

CH4

D

D

CH4
CH3

CH2

CH1

CH1

CH2

CH3

CH4

L

N

Do Not

Connect

Do Not

Connect

Earth not shown

for clarity

Dimming

Emergency 

Luminaire

Maintained 

Live

As shown above, the unit can be powered from a single supply; one or more luminaires may be connected to each channel.  

-2-

Dimming

Dimming

Dimming

Dimming

Note: + and - 

relevant for 

analogue 

versions only.

Dimming

Summary of Contents for Ex-Or CDH4U5

Page 1: ...CDH4U5 4 Channel Programmable Intelligent Lighting Control Module Installation and Commissioning Instructions ...

Page 2: ...uct simplifies installation whilst providing an intelligent lighting control system Provision is made for 4 volt free power outputs rated for 415V isolation Additionally the unit features a switched output for Maintained Live to allow initiation of Emergency Lighting Test The CDH4U5 has the ability to operate from dual supplies with the capability to modify its operating behaviour when failure is ...

Page 3: ...wn in the diagram one or more channels may be powered from either of the supplies Ballast N L E D D Ballast N L E D D Ballast Ballast Ballast N N N L L L E E E D D D D D D 1 DETECTOR PORTS 2 3 4 5 B COM A B COM A B COM A B COM A B COM A 1 2 3 4 5 SELV SWITCH INPUTS VOLT FREE CHANNELS 1 1 2 2 COMMS BUS 4 3 2 1 DIMMING CHANNELS N L MAINS INPUT VOLT FREE CHANNELS N2 L2 N1 L1 CH2 ML CH3 CH1 CH4 D D CH...

Page 4: ... the unit an external change over contactor is required Line terminals from each of the supplies N1 L1 and N2 L2 are connected via the change over contactor The Live and Neutral outputs from the contactor are connected to the mains input of the unit In the case of failure of one of the supplies the change over contactor switches to the alternative supply to ensure continuous supply to the unit As ...

Page 5: ...k comprising a common and two returns from normally open contacts Four plugs are provided with each CDH4U5 additional plugs can be ordered using the code CDHIP 5 pieces per pack Note that if the SELV status of any one of the switches is compromised by reason of inadequate insulation or segregation of the cabling then the SELV status of all other switchesAND OF THE DETECTORS will also be compromise...

Page 6: ...ns 6 PARAMETERS OPTIONS Per Box Parameters Switch A 1 5 Switch B 1 5 Switch 6A 6B 7A 7B User may choose any option for Switch A or Switch B from following Sustain Brighten Dim Off Scene 01 06 On Partition OneSwitch On Dim Off Brighten On Brighten Off Dim Emergency Test Emergency End See separate table for detailed description of Switch Input options Detector 1 5 Range Max 100 Max 75 Max 50 High 10...

Page 7: ...r example 20 Ballasts Maintained live output 6A Mains supply terminal capacity 2x2 5mm or 1x4mm Override switch input connector 2 5mm MLS bus connector 2 5mm MLS bus cable 1 5mm unscreened twisted pair seeApplication NoteAN4001 Case material Self extinguishing blend PC ABS Case finish Gray RAL7035 IPrating 20 Dimensions 9 m 1m 62mm 3m 21 m Volt free Channels Volt free Channels Dimming Channels Com...

Page 8: ... Power Supply Unit Wireless switch enabled DSI Dimming CDH4U5 RBDALIWL 4 Channel LCM with MLS Bus Power Supply Unit Wireless switch enabled DALI Dimming Plug in Cards CDHDC Plug in Digital Dimming Card CDHAC Plug in Analogue Dimming Card CDHBC Plug in MLS Bus Interface CDHRB Plug in MLS Bus Power Supply Unit CDHWL Plug in Wireless EnOcean Card Presence Detectors with photocell MLS2500CDR Corner mo...

Reviews: