Electrical Schematics & Drawings
Part No.: 44200004 - Revision 2
SVP Controller Operation Manual
6-5
6.2.2 CONDAT CIU
The Condat Interface Unit (CIU aka PIU) connects to the SVP controller
using cable (Honeywell PN 44108889). The cable features a connector
that attaches to the CIU at the connector labeled “Control”. The opposite
end of the cable has colored leads for connection in the terminals in the
Customer Connect Box. Please refer to the PROVEit Manuals for further
connection instructions.
Note: The pin numbers listed adjacent to the colors signify the pin
locations on the CIUs “Control” connector.
Within the Customer Connection Box, the terminals 12 and 15 are
provided to securely land customer provided voltage or ground leads
as needed. For the CIU the ground (earth) reference is Black (Customer
Connection Box Terminal 17) and the nominal 15VDC supply is Red
(Customer Connection Box Terminal 12).
While idle, Green (Customer Connection Box Terminal 14) will read
nominal 15VDC and White (Customer Connection Box Terminal 16) will
read nominally 5 VDC. When the run command is given, the CIU will drop
Green to ground (earth) and the SVP controller starts the proving run.