![Honeywell DR4300 Series Product Manual Download Page 93](http://html.mh-extra.com/html/honeywell/dr4300-series/dr4300-series_product-manual_151814093.webp)
Configuration, Startup, and Operation
of Recorder with Display
4/00
DR4300 Circular Chart Recorder Product Manual
81
4.3.5.3 Setting SW6 Burnout Switch
Overview
What happens to the displayed input value when the input signal to the recorder fails depends on several
factors: the input type, the setting of SW6 switch 2, and the value of the “BRNOUT” parameter in the input
set up group.
SW6 switch 2 OFF for RTD
If the input to the pen channel is from an RTD, SW6 switch 2 must always be set to OFF.
CAUTION
If SW6 switch 2 is ON for an RTD input, the recorder will not be able to process the input correctly,
even when the input sensor is providing a valid input signal.
SW6 switch 2 setting unimportant for Volt, mV, and mA inputs
It does not matter whether SW6 switch 2 is ON or OFF if the pen channel uses a Volt, mV, or mA input
signal. In case of input failure, the displayed input value will show little change, regardless of the setting of
SW6 switch 2 or the value assigned to the “BRNOUT” parameter. (However, the value of “BRNOUT” is
still important to implementing your control strategy because the value of “BRNOUT” affects the output
used in case of input failure. See Subsection 4.3.11 for details.)
SW6 switch 2 setting determines displayed thermocouple input if BRNOUT = NONE
If the value of “BRNOUT” is “NONE” when a thermocouple input fails, then the setting of SW6 switch 2
determines whether the displayed input value will be under range or over range. The recorder can display
1 % over or under range for thermocouples.
•
If SW6 switch 2 is ON, the displayed value will be under range.
•
If SW6 switch 2 is OFF, the displayed value will be over range.
If the pen is configured to trace the input value (“PENIN” pen set up parameter value is “INP”), then the
pen will also be driven over or under range.
Note that the over range or under range input will have no effect on output. When “BRNOUT” = “NONE”,
the recorder uses the configured failsafe value as the output in case of input failure, rather than a calculated
value based on input.
SW6 switch 2 setting for thermocouple inputs should match BRNOUT if BRNOUT = UP OR DOWN
We recommend that, in the case of thermocouple inputs, SW6 switch 2 be set to OFF if “BRNOUT” =
“UP” and ON if “BRNOUT” = “DOWN”.
When the input failure first occurs, the displayed input for a thermocouple input will briefly be driven
according to the hardware switch setting. However, as soon as the software recognizes that it has received
an out-of-range input signal, the displayed input will be driven according to the value, “UP” or “DOWN”,
configured for “BRNOUT”. The displayed value (over range or under range) as configured in “BRNOUT”,
will remain on the display until a valid input is restored.
Summary of Contents for DR4300 Series
Page 1: ...Sensing and Control DR4300 Circular Chart Recorder Product Manual 44 01 25 14E 4 00 ...
Page 12: ...DR4300 Circular Chart Recorder DR4300 Circular Chart Recorder Product Manual 4 00 xii ...
Page 82: ...DR4300 Circular Chart Recorder 70 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 152: ...DR4300 Circular Chart Recorder 140 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 168: ...DR4300 Circular Chart Recorder 156 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 202: ...DR4300 Circular Chart Recorder 190 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 210: ...DR4300 Circular Chart Recorder 198 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 214: ...DR4300 Circular Chart Recorder 202 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 224: ...DR4300 Circular Chart Recorder 212 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 238: ...DR4300 Circular Chart Recorder 226 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 244: ...DR4300 Circular Chart Recorder 232 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 246: ...DR4300 Circular Chart Recorder 234 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 248: ...DR4300 Circular Chart Recorder 236 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 250: ...DR4300 Circular Chart Recorder 238 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 252: ...DR4300 Circular Chart Recorder 240 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 254: ...DR4300 Circular Chart Recorder 242 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 258: ...DR4300 Circular Chart Recorder 246 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 264: ...252 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 265: ......