![Honeywell DR4300 Series Product Manual Download Page 116](http://html.mh-extra.com/html/honeywell/dr4300-series/dr4300-series_product-manual_151814116.webp)
DR4300 Circular Chart Recorder
104
DR4300 Circular Chart Recorder Product Manual
4/00
4.3.13 Setpoint Ramp/Program Set Up Group
Introduction
All models supporting control can be configured to ramp the setpoint between the current local setpoint and
a final local setpoint over a timer interval of from 1 minute to 255 minutes.
If the optional Setpoint Program feature is specified at time of purchase, then in addition to this single ramp
capability, you can also configure a ramp/soak profile containing up to twelve segments, each with its own
time interval.
Setpoint ramp/program group prompts
Table 4-11 lists all the function prompts in the setpoint ramp group. The additional prompts associated with
the optional twelve-segment Setpoint Program are described in Appendix C.
For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface. Press
FUNC to select channel.
Press SETUP key until “SPRAMP” appears in the lower display.
Press FUNC key to select the parameters.
Table 4-11 Setpoint Ramp Parameter Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
SP RAMP
ENAB
DIS [factory setting]
SINGLE SETPOINT RAMP — Make selection to enable or
disable the setpoint ramp function. Make sure you
configure a ramp time and a final setpoint value. “SP
PROG” must be disabled.
ENABLE SETPOINT RAMP — Allows the single setpoint
ramp prompts to be shown.
DISABLE SETPOINT RAMP — Disables the setpoint
ramp. Allows “SPPROG” option to be selected.
TI MIN
0 minutes to 255 minutes
[factory setting = 0]
SINGLE SETPOINT RAMP TIME — Enter the number of
minutes desired to reach the final setpoint or a single
setpoint ramp.
A ramp time of “0” implies and immediate change of
setpoint to the final setpoint.
FINL SP
Within SP limits
[factory setting = 0]
SETPOINT RAMP FINAL SETPOINT — Enter the value
desired for the final setpoint. The controller will operate at
the setpoint set here when ramp is ended.
SP PROG
ENAB
DIS [factory setting]
SETPOINT RAMP/SOAK PROGRAM
Available only with controllers that contain this option.
For reasons of convenience, the information for the
prompts when SPPROG is enabled are included in
Appendix C.
ATTENTION
“SP RAMP” must be disabled for
SPPROG to be available.
Summary of Contents for DR4300 Series
Page 1: ...Sensing and Control DR4300 Circular Chart Recorder Product Manual 44 01 25 14E 4 00 ...
Page 12: ...DR4300 Circular Chart Recorder DR4300 Circular Chart Recorder Product Manual 4 00 xii ...
Page 82: ...DR4300 Circular Chart Recorder 70 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 152: ...DR4300 Circular Chart Recorder 140 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 168: ...DR4300 Circular Chart Recorder 156 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 202: ...DR4300 Circular Chart Recorder 190 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 210: ...DR4300 Circular Chart Recorder 198 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 214: ...DR4300 Circular Chart Recorder 202 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 224: ...DR4300 Circular Chart Recorder 212 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 238: ...DR4300 Circular Chart Recorder 226 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 244: ...DR4300 Circular Chart Recorder 232 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 246: ...DR4300 Circular Chart Recorder 234 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 248: ...DR4300 Circular Chart Recorder 236 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 250: ...DR4300 Circular Chart Recorder 238 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 252: ...DR4300 Circular Chart Recorder 240 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 254: ...DR4300 Circular Chart Recorder 242 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 258: ...DR4300 Circular Chart Recorder 246 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 264: ...252 DR4300 Circular Chart Recorder Product Manual 4 00 ...
Page 265: ......