Honeywell DeltaNet R7515A Installation Instructions Manual Download Page 11

DELTANET R7515A/B, RP7515A/B, R7516B MICROCEL

 CONTROLLERS 

Figure 17 shows a typical wiring diagram. Refer to job 
drawings for specific wiring diagrams. 

19 

20

10 

11 

12 

13 

14

R1 

D1 

+10  V1 

R2 

D2 

+10  V2 

VOLT

DIG

RTD

VOLT

DIG

RTD 

OUTPUTS 

INPUTS 

RET 

21  22 

23 

25 

26 

27 

28 

29 

30  31 

32 

33 

34

24 

T2 

35 

ANALOG 

RELAY 

T1 

24V AC 

(J11) 

+

-

C-NAP 

(J7) 

J8 

J9 

AO-1 

AO-2 

AO-3 

K1 

K2 

K3 

36 

37 

38 

40 

41

39 

43

42 

T1 

T2

1-2 

COM 

3-4 

TRIAC 

24V AC

COM 

+

-

WALL 

MOD 

24V AC/ 

C-NAP 

BUS 

PNEU 

"B" 

PNEU 

"A" 

500 
OHMS 
1% 

LINE VOLTAGE 

DIGITAL 
INPUT 

SENSOR/ 
TRANSDUCER 
2-10V DC 

SENSOR/ 
TRANSDUCER 
4-20 MA 

TEMPERATURE 
SENSOR OR REMOTE 
SETPOINT (TYPICAL) 

DIGITAL 
INPUT(E.G., 
CLEAFS405, 
R4222) 

PT3000 
TEMP 
SENSOR 
(T7005,6,7,8) 

CLASS II 
EXTERNAL 
TRANSFORMER 
WITH 24V AC 
SECONDARY 
— DO NOT GROUND

 EITHER LEG 

TO POWER AND C-NAP 
COMMUNICATIONS BUS 

LINE 
VOLTAGE 

FAN 
SPEED 
CONTROL 
2-10V DC 

UNIT VENT 
MODULATING 
VALVE 
2-10V DC 

C3205-2 

OUTDOOR AIR DAMPER 
ACTUATOR 2 TO 10V DC 
(N.C. ON POWER FAILURE) 

1K 

3K 

FACTORY PREWIRED 
IF INTEGRAL TO 
CONTROLLER 

C1 

LINE VOLTAGE 

ML6161B 
SERIES 60 
FLOATING 
DAMPER 
ACTUATOR 

SERIES 60 
FLOATING 
VALVE 
ACTUATOR 

CONTACTOR FOR 
ELECTRIC DUCT HEATER 
(STEP OR BINARY CONTROL) 

ALTERNATE C-NAP 
COMMUNICATIONS 
BUS WIRING 

ALTERNATE 
POWER WIRING 

SPACE 
SENSOR CABLE 
ASSEMBLY 

T7515 M-Cel SPACE 

TEMPERATURE 

SENSOR 

AK3326 
T-TAP CABLE 
ASSEMBLY 

C2 

C3 

J2 

COMM 

STEM UP 

STEM DOWN 

M-POT COMMUNICATION CABLE

J1 

CCT2190 M-Cel 

PORTABLE 

OPERATOR 

TERMINAL 

(M-POT) 

BLUE 

RED 

YELLOW 

GROUND 
CASE 

15 

17 

18

16 

CW 

COM 

CCW 

Fig. 17. Typical MicroCel Wiring Diagram. 

11 

95-6083 

Summary of Contents for DeltaNet R7515A

Page 1: ...peration BEFORE INSTALLATION The DeltaNet MicroCel Controller MicroCel shown in Figure 1 is available in five models R7515A MicroCel RP7515B MicroCel with Microbridge Airflow R7515B MicroCel with Microbridge Airflow Sensor Sensor and Electric Pneumatic Transducer RP7515A MicroCel with Electric Pneumatic R7516B MicroCel with Microbridge Airflow Transducer Sensor and Integral Damper Actuator AUXILIA...

Page 2: ...icroCel in a vertical position so that the transducers will be oriented toward the bottom of the case and below the MicroCel PC boards This position prevents damage from condensation possible from main air CW C C W CW CCW 45 60 60 45 HIGH LOW 15 32 12 3 9 32 83 3 31 32 101 2 5 32 55 31 32 24 5 21 32 144 BARBED CONNECTOR 2 FOR DAMPER DAMPER ACTUATOR 1 4 IN 6 MM O D TUBING 3 4 5 1 4 133 11 16 19 6 1...

Page 3: ...16 6 15 16 176 15 16 24 5 8 16 3 11 16 94 8 204 10 1 2 267 2 1 3 4 ACTUATOR SHAFT POSITION R7516B ONLY W 6 5 8 168 D FITTINGS USABLE QUANTITY DEPENDS KNOCKOUT 9 FOR 1 2 INCH CONDUIT 4 15 16 125 ON MODEL 4 13 16 DOUBLE KNOCKOUT 2 FOR 1 2 OR 122 3 4 INCH CONDUIT FITTINGS HOLE 2 FOR BARB CONNECTORS RP7515A B ACTUATOR R7516B ONLY C5653 Fig 3 Standard Case One Output Board MicroCel Approximate Dimensio...

Page 4: ...per Actuator Remove the MicroCel cover by loosening the two cover mounting screws Fig 1 Mount the MicroCel in a location convenient to the equipment being controlled Use No 10 thread forming not thread cutting e g TEK screws obtained locally to secure the MicroCel to the mounting surface through the four key holes inside the case Replace and secure the MicroCel cover after wiring and piping Model ...

Page 5: ... following a Direction the damper shaft moves to open the damper Fig 6 cw or ccw b Size of damper shaft 3 8 or 1 2 in 9 or 12 mm NOTE Damper shaft must extend at least 2 1 2 in 63 mm from damper housing c Degrees of travel for damper to open Fig 6 45 60 or 90 degrees AIRFLOW AIRFLOW CW TO OPEN CCW TO CLOSE 45 DEGREE ROTATION 60 DEGREE ROTATION 90 DEGREE ROTATION CCW TO OPEN CW TO CLOSE C3957 1 Fig...

Page 6: ...nge Stop Pin PIPING Airflow Pickup Where Used Connect the airflow pickup to the two 1 4 in 6 mm barb connectors on the MicroCel case location shown in Fig 2 3 or 4 Connect the high pressure or upstream tube to the plastic restrictor barb labeled HIGH and the low pressure or downstream tube to the plastic restrictor barb labeled LOW When twin tubing is used from the pickup split the tubing a short ...

Page 7: ...rt too much pressure on wiring and can cause a short Power and Communications Bus The MicroCel C NAP communications bus and 24V ac power wiring is normally done with the AK3711 DeltaNet MicroCel Bus Cable Assembly See the Connections Using AK3711 Bus and AK3326 T Tap Cable Assembly section For alternate methods for connecting the C NAP communications bus and 24V ac power wiring see the Connections...

Page 8: ...ectrical connections press down each of four connector buttons with channel lock pliers d Connector buttons should be flush with cover when properly secured BUTTONS RS 485 4 C NAP 24V AC FROM CLASS II POWER SOURCE COVER BASE C3506 4 Fig 11 Installing Bus Conductors in T Tap Connector BLUE RED YELLOW BLACK YELLOW BLACK BLUE RED TO CONTROLLER Connect plug on AK3326 T Tap Cable Assembly into Connecto...

Page 9: ...2 Fig 14 Installing AK3702R or AK3744 Bus Cable Using Screw Terminals 15 through 18 in MicroCel Bus Termination Resistor Insert a Bus Termination Resistor 14501600 028 on all C NAP bus configurations per job drawings If the MicroCel is at the end of a main or secondary trunk mount the resistor on the terminal strip as shown in Figure 15 14501600 028 RESISTOR T1 T2 RED YELLOW BLACK BLUE RED YEL AK3...

Page 10: ... 7 8 9 10 11 12 13 14 4 R1 D1 10 V1 R2 D2 10 V2 VOLT DIG RTD VOLT DIG RTD OUTPUTS INPUTS RET 1 2 3 21 22 23 25 26 27 28 29 30 31 32 33 34 24 T2 35 A B ANALOG RELAY T1 24V AC J11 C NAP J7 J8 J9 AO 1 AO 2 AO 3 K1 K2 K3 36 37 38 40 41 39 43 42 T1 T2 1 1 2 2 3 COM 3 4 4 TRIAC 24V AC COM 15 17 18 16 WALL MOD 24V AC C NAP BUS PNEU B PNEU A A C B A C B A C B A ALL CONTROLLER MODELS 19 20 1 2 3 5 6 7 8 9 ...

Page 11: ...5 R4222 PT3000 TEMP SENSOR T7005 6 7 8 CLASS II EXTERNAL TRANSFORMER WITH 24V AC SECONDARY DO NOT GROUND EITHER LEG TO POWER AND C NAP COMMUNICATIONS BUS LINE VOLTAGE FAN SPEED CONTROL 2 10V DC UNIT VENT MODULATING VALVE 2 10V DC C3205 2 OUTDOOR AIR DAMPER ACTUATOR 2 TO 10V DC N C ON POWER FAILURE 1K 3K FACTORY PREWIRED IF INTEGRAL TO CONTROLLER C1 LINE VOLTAGE ML6161B SERIES 60 FLOATING DAMPER AC...

Page 12: ...Control Home and Building Control Honeywell Inc Honeywell Limited Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P O Box 524 North York Ontario Minneapolis MN 55408 0524 M2H 3N7 95 6083 Rev 2 93 Printed in U S A ...