25
31-00083—02
Reheat Type:
Elec_ThreeStage or (Elec_ThreeStageBin),
(Elec_OneStage).
Proportional Reheat Flow:
Enable.
Fig. 23. VAV box modes for Reheat Type Elec_ThreeStage
- Proportional.
Refer to Fig. 24 to see VAV box modes for Reheat type
Elec_ThreeStage - Non-Proportional.
Pressure Type:
Pressure Independent or (Pressure_Dependent).
Reheat Type:
Elec_ThreeStage or (Elec_ThreeStageBin),
(Elec_OneStage), (Elec_TwoStage).
Proportional Reheat Flow:
Disable.
Fig. 24. VAV box modes for Reheat Type Elec_ThreeStage
- Non-Proportional.
Reheat Type:
Float_Periph_Reheat or (PWM_Periph_Reheat).
Proportional Reheat Flow:
Enable.
Periph Min Pos:
0% or greater.
Fig. 25. VAV box modes for Reheat type Peripheral
Heating Then Reheat - Proportional
(Float_Periph_Reheat/PWM_Periph_Reheatl).
Refer to Fig. 26 to see VAV box modes for Reheat type
ReheatThenPeriph - Proportional.
Pressure Type:
Pressure Independent or (Pressure_Dependent).
Reheat Type:
Float_Reheat_Periph or (PWM_Reheat_Periph).
Proportional Reheat Flow:
Enable.
Periph Min Pos:
0% or greater.
Fig. 26. VAV box modes for Reheat Type Reheat Then
Peripheral Heating Proportional (Float_Reheat_Periph/
PWM_Reheat_Periph).
Reheat Type:
FloatHotDuctPrDep.
Proportional Reheat Flow:
Disable.
Periph Min Pos:
0% or greater.
REHEAT
FLOW
M11829
ON
ON
ON
STAGE 3
STAGE 2
STAGE 1
HeatOccSpt
CoolOccSpt
MAX
FLOW
(POS)
MIN
FLOW
(POS)
REHEAT
MODE
COOLING MODE
REHEAT
FLOW
M11830
ON
ON
ON
STAGE 3
STAGE 2
STAGE 1
HeatOccSpt
CoolOccSpt
REHEAT
MODE
COOLING MODE
MAX
FLOW
(POS)
MIN
FLOW
(POS)
REHEAT
FLOW
MIN
FLOW
M11831
PERIPHERAL
HTG
REHEAT
HeatOccSpt
CoolOccSpt
100
PERCENT
OPEN
REHEAT
MODE
COOLING MODE
MAX
FLOW
(POS)
MIN
FLOW
(POS)
Periph Min Pos
REHEAT
FLOW
MIN
FLOW
M11832
PERIPHERAL
HTG
REHEAT
100
PERCENT
OPEN
REHEAT
MODE
COOLING MODE
HeatOccSpt
CoolOccSpt
Periph Min Pos
MAX
FLOW
(POS)
MIN
FLOW
(POS)