TP970 SERIES CONVERTASTAT

®

 KITS 

Changeover 

TP971 and TP972 thermostats have changeover 
features. The TP971 has day/night changeover and the 
TP972 has summer/winter changeover. TP971 controls 
direct acting at day setting with 13 psi (90 kPa) main air 
pressure and direct acting at the lower night setting with 
18 psi (124 kPa) main air pressure. The TP972 controls 
reverse acting (RA) for summer cooling at 13 psi 
(90 kPa) main air pressure and direct acting (DA) for 
winter heating at 18 psi (124 kPa) main air pressure. 

The branchline pressure (BLP) drops as the temperature 
drops when the thermostat is operating DA. The BLP 
drops as the temperature rises when the thermostat is 
operating RA. 

Changeover Conversion 

On some systems the lower main air pressure is higher 
(14 or 15 psi [97 or 103 kPa]) so the changeover point 
must be raised. On these systems, turn the changeover 
adjustment screw (Fig. 9) one-half turn clockwise for 
each 1 psi (7 kPa) over 13 psi (90 kPa). 

TP971 or TP972 thermostats used on systems having 
16/21 psi (110/145 kPa) or 13/16/21 psi (90/110/145 kPa) 
main air pressure require a different spring for proper 
changeover operation. Change the spring as follows: 

1.   Remove thermostat from backplate if mounted. 
2.   Remove changeover adjustment screw (Fig. 9) 

from thermostat back. 

3.   Replace gold-colored spring with silver-colored 

spring furnished in TP971 kit. Order 14002373-001 
Spring for TP972 conversion. 

4.   Reinstall changeover adjustment screw and set 

flush with spring chamber top. 

5.   Mount thermostat on backplate again. 
6.   Follow procedures in Changeover Calibration 

Check section and recalibrate if necessary. 

FILTER COVER 

THERMOSTAT 
MULTISTAGE FILTER 

B

C5411 

CHANGEOVER 
ADJUSTMENT SCREW 

SPRING CHAMBER 

DAY/AUTO LEVER 
(TP971 ONLY) 

Fig. 9. TP970 Series Thermostat—Back View. 

Changeover Calibration Check 

1.   Set main air pressure to higher pressure setting 

(night for TP971, winter for TP972A2192, and 
summer for TP972A2200). 

2.   Using gage adapter, insert gage into gage tap (see 

Fig. 8). If results in Steps 3 or 5 are incorrect, go to 
the Changeover Calibration section. 

3.   TP971: 

Turn day setpoint adjustment until setpoint 
indicator reads approximately 10F (5.5C) degrees 
above space temperature and set night setpoint 
dial below space temperature. The gage should 
indicate main air pressure. Push day/auto lever to 
day (left) position; it should stay there and BLP 

should go to 0 psi (0 kPa). 
TP972: 
Turn setpoint adjustment until setpoint indicator 
reads approximately 10F (5.5C) degrees above 
space temperature. BLP should go to 0 psi (0 kPa). 

4.   Set main air pressure to lower pressure setting 

(day for TP971, summer for TP972A2192, and 
winter for TP972A2200). Use 16 psi (110 kPa) on 
13/16/21 psi (90/110/145 kPa) systems. 

5.   TP971: 

With day setpoint indicator and night setpoint dial 
set as in Step 3, BLP should go to zero. Push 
day/auto lever to day (left) position, it should return 
to auto position when released. 
TP972: 
With setpoint indicator set as in Step 3, BLP should 
go to main air pressure. 

Changeover Calibration 

1.   Remove thermostat from wall. 
2.   Loosen screws. Remove backplate from wall but 

do not disconnect tubes from backplate. 

3.   Plug thermostat into backplate. 
4.   Use following changeover procedures for calibra­

tion with or without a branch line pressure gage. 

WITH BRANCHLINE PRESSURE GAGE 

If thermostat changeover point was not correct at Step 3 
of the Changeover Calibration Check procedure: 

1.   Use screwdriver end of thermostat tool to turn 

changeover adjustment screw one-quarter turn 
counterclockwise (see Fig. 10)

2.   Make a calibration check. 
3.   Continue with one-quarter turn adjustments 

followed by a calibration check until changeover 
point is correct. 

If thermostat changeover point was not correct at Step 5 
of the Changeover Calibration Check procedure: 

1.   Use TP970 Series thermostat tool to turn 

changeover adjustment screw (Fig. 10) one­
quarter turn clockwise. 

2.   Make a calibration check. 
3.   Continue with one-quarter turn adjustments 

followed by a calibration check until changeover 
point is correct. 

CHANGEOVER 
ADJUSTMENT 
SCREW 

C183-3 

Fig. 10. Location of Calibration Adjustment Screw 

with Backplate Attached. 

WITHOUT BRANCHLINE PRESSURE GAGE (TP971 ONLY) 

1.   Set system pressure to 18 psi (124 kPa) (night 

pressure). 

2.   Hold the day/auto lever in day (left) position. Turn 

changeover adjustment screw counterclockwise 
until lever holds in place. 

3.   Release lever and slowly turn changeover 

adjustment screw clockwise until lever snaps back 
to auto position. 

5  

85-0210EF—1 

Summary of Contents for CONVERTASTAT TP970A2145

Page 1: ...mponents needed to create a cover to meet building requirements are included INSTALLATION When the old mounting plate is removed retain the screws to use for mounting the adapter plate Cut the existing tubes as close as possible to the thermostat Do not remove the antikink springs from cut tubes Do not allow tubes to slip inside the wall after removing the old thermostat Remove Johnson Thermostat ...

Page 2: ...3 3011 T27 301 T27 3011 2214 121c 2214 131c 2216 126 2216 136 2216 526d TP971A2183 Same as TP971A2102 except plastic cover is beige T4506 6203c T4506 6204c 2214 521d TP972A2192 Single temp two pipe proportioning 60 to 90 F 16 to 32 C range RA Summer 13 psi 90 kPa or 9 psi 62 kPa unit vent DA Winter 18 psi 124 kPa changeover field adjustable T4756 205 T4756 206 T4756 217 T4756 6205 T4756 6206 T4756...

Page 3: ...s and separate see Fig 5 e Align and attach backplate and adapter plate to mounting screw holes using screws retained from stripping adapter plate threads f Proceed to Step 7 NOTE When adapting to a Johnson thermostat if wall holes are out of alignment with adapter plate holes use any available hole for an additional wall anchor HOLES 10 CODED PER MANUFACTURER J JOHNSON P POWERS R ROBERTSHAW TUBIN...

Page 4: ...at 4 F 2 2 K and should not require any change under normal operating conditions If a change is necessary use following procedures to reset throttling range to values specified on job drawings NOTE Changing throttling range requires recalibration 1 Remove cover and install 0 to 30 psi 0 to 210 kPa gage with gage adapter in gage tap Fig 8 2 Slide throttling range adjustment to desired position on t...

Page 5: ...reads approximately 10F 5 5C degrees above space temperature and set night setpoint dial below space temperature The gage should indicate main air pressure Push day auto lever to day left position it should stay there and BLP should go to 0 psi 0 kPa TP972 Turn setpoint adjustment until setpoint indicator reads approximately 10F 5 5C degrees above space temperature BLP should go to 0 psi 0 kPa 4 S...

Page 6: ...Pa 4 Turn calibration screw in opposite direction until gage indicates 8 1 psi 56 7 kPa The thermostat is now calibrated 5 Remove gage and replace cover TP971 1 Remove cover and install a 30 psi 210 kPa gage into gage tap 2 Turn setpoint adjustment until setpoint indicator reads indicated temperature 3 With 13 psi 90 kPa day main air pressure turn day left calibration screw Fig 8 until gage indica...

Page 7: ... notice explique comment retirer le thermostat selon le fabricant et installer le nouveau thermostat de série TP970 Une fois l ancienne plaque de montage retirée conserver les vis qui serviront à l installation de la plaque d adaptation Couper le tuyau existant aussi près que possible du thermostat Ne pas retirer des tuyaux le ressort antitortillement Ne pas laisser les tuyaux glisser à l intérieu...

Page 8: ...e TP971A2102 mais avec couvercle de plastique beige T4506 6203c T4506 6204c 2214 521d TP972A2192 Une seule temp deux canalisations à action proportionnelle gamme de 60 à 90 F 16 à 32 C action inverse en été à 13 psi 90 kPa ou 9 psi 62 kPa ventilo convecteur action directe en hiver inversion à 18 psi 124 kPa réglable sur place T4756 205 T4756 206 T4756 217 T4756 6205 T4756 6206 T4756 6217 TH192 208...

Page 9: ... plaque d adaptation et les fixer aux ouvertures des vis de montage à l aide des vis qui ont servi à aléser les filets de la plaque d adaptation f Passer à l étape 7 REMARQUE Lors du remplacement d un thermostat Johnson si les trous dans le mur ne corre spondent pas aux ouvertures de la plaque d adaptation utiliser n importe quel autre trou pour insérer une cheville additionnelle TROU DE GUIDAGE 2...

Page 10: ...couvercle et installer un manomètre de 0 à 30 psi 0 à 210 kPa dans la prise de manomètre Fig 8 2 Faire glisser le curseur de la bande proportionnelle à la valeur désirée 3 Vérifier mécaniquement la bande proportionnelle en déplaçant le réglage du point de consigne jusqu à ce que la pression de la canalisation princi pale soit de 3 psi 21 kPa Prendre note du point de consigne 4 Déplacer ensuite le ...

Page 11: ...uto à la position jour à gauche il devrait rester en position et la pression de la canalisation secondaire devrait passer à 0 psi 0 kPa TP972 Faire tourner le réglage du point de consigne jusqu à ce que l indicateur marque environ 10 F 5 5 C au dessus de la température ambiante La pression de la canalisation secondaire devrait passer à 0 psi 0 kPa B M S DU COUVERCLE DU FILTRE FILTRE DES ÉTAGES DU ...

Page 12: ...opposé jusqu à ce que le manomètre indique 8 psi 1 psi 56 kPa 7 psi Le thermostat est maintenant étalonné 5 Retirer le manomètre et remettre le couvercle TP971 1 Retirer le couvercle et installer un manomètre de 30 psi 210 kPa dans la prise de manomètre 2 Faire tourner le réglage du point de consigne jusqu à ce que l indicateur du point de consigne marque la température indiquée 3 Avec une pressio...

Reviews: