background image

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

66-2060—01

2

Approvals

Components are individually approved by the nationally rec-

ognized agencies. Please see component literature for 

details. The panel has UL 508A flame control panel 

approval. Panel is assembled and wired to the UL Stan-

dards.

INSTALLATION

When Installing This Product…

1.

Read these instructions and the appropriate product lit-

erature carefully. Failure to follow them could damage 

the product or cause a hazardous condition.

2.

Refer to the installation manuals and wiring diagrams 

provided with this panel for the embedded products.

3.

Check the ratings given in the instructions and on the 

product to make sure that the product is suitable for your 

application.

4.

Installer must be a trained, experienced combustion ser-

vice technician.

5.

Disconnect the power supply before beginning installa-

tion to prevent electrical shock and equipment damage. 

More than one disconnect may be involved.

6.

All wiring must comply with the National Electric Code 

(NEC) and any applicable local electrical codes, ordi-

nances and regulations.

7.

After installation is complete, check out product opera-

tion as provided in the appropriate product installation 

instructions.

WARNING

Fire or Explosion Hazard. Can cause severe injury, 

death or property damage.

To prevent possible hazardous burner operation, verify 

safety requirements each time a controller is installed 

on a burner.

WIRING

WARNING

Electrical Shock Hazard. Can cause serious injury, 

death or equipment damage.

Disconnect the power supply before beginning wiring 

to prevent electrical shock, equipment and control 

damage. More than one disconnect may be involved.

Ground Connection

Earth ground is required for proper operation of the 

ControLinks system. The earth ground must be capable of 

conducting enough current to blow the fuse or breaker in the 

event of an internal short. Ensure the panel is bonded to a 

substantial earth ground. Make sure that mechanically 

tightened joints along the ground path are free of 

nonconductive coatings and protected against corrosion on 

mating surfaces.

Electrical Connections

1.

Refer to the appropriate product data sheet for details.

2.

Wire size and length will vary, depending on the compo-

nent. Refer to the component literature for specific wire 

lengths, sizes and type recommendations.

3.

Wire according to specifications, following all local ordi-

nances and requirements.

4.

Field knockouts are required for the wiring. When drill-

ing holes, take care to protect the electronics from metal 

pieces and debris. 

IMPORTANT

Run line voltage and low voltage wiring in separate 

conduit to avoid signal interference. 

Carefully check field wiring and terminal designa-

tions in this document and the associated wiring dia-

gram. They are different from those of the individual 

components.

Panel Inspection

After mounting and wiring, but before powering the panel, 

inspect all internal panel wire connections. Each panel is fully 

tested at the factory; however, wires may loosen during transit. 

Verify that all internal wire connections are secure from the 

Q7999 subbase to the components mounted on the door and 

the S7999D touchscreen interface.

Final Wiring Check and Static 

Checkout

All wiring shall be in accordance with the National Electric 

Codes (NEC) and local electrical codes.

1.

Check the power supply circuit. The voltage and fre-

quency must match the specification listed.

2.

Check wiring terminations and routing to ensure proper 

connections.

3.

Follow any system checkout recommendations for indi-

vidual components as found in the component literature.

4.

Restore power to the panel.

CAUTION

Test each limit and interlock to ensure system 

operates correctly as defined in the 7800 Series 

“Checkout and Test” document (Form #65-0229).

WARNING

Explosion and Electrical Shock Hazard. 

Can cause serious injury, death or equipment 

damage.

1.

Close all manual fuel shutoff valves before starting 

these tests.

2.

Use extreme care while testing the system. Line voltage 

is present on most terminal connections when power is 

on.

3.

Replace all limits and interlocks that are not operating 

properly. Do not bypass limit and interlocks. 

Summary of Contents for ControLinks YP7999A1000

Page 1: ...eady to install Includes the R7999A control wiring subbase and S7999D1048 touchscreen display Commission monitor and control ControLinks through the touchscreen interface Fuel selector switch Alarm light Reset button Unit shutdown Emergency stop button Auto manual switch Manual operation potentiometer S7999D touchscreen display is Modbus ready SPECIFICATIONS Electrical Ratings 100 120 Vac 50 60 Hz...

Page 2: ...tightened joints along the ground path are free of nonconductive coatings and protected against corrosion on mating surfaces Electrical Connections 1 Refer to the appropriate product data sheet for details 2 Wire size and length will vary depending on the compo nent Refer to the component literature for specific wire lengths sizes and type recommendations 3 Wire according to specifications followi...

Page 3: ...t from ControLinks controller to burner control 11 HF High Fire drive command input from burner controller 12 MV Main Valve command input from burner controller 13 LF Low Fire drive command input from burner controller 14 LCI Limit Control Input from burner limit string including on off control LWCO high limit etc 15 LCO Limit Control Output from ControLinks controller to burner control demand int...

Page 4: ...xxL burner control and or Modbus enabled UDC2500 3200 3500 controls in a daisy chain fashion to the customer terminals for dis play on the S7999D Refer to the S7999D S7800A or S7810M and UDC control product manuals for further information on wir ing and S7999D display set up 6 Installation operation and maintenance shall conform with National Fire Protection Association standards national and loca...

Page 5: ...ED 20 POLYVINYL FSG RESET CONTROLINKS RESET POTENTIOMETER BELDEN 8760 18 AWG TWISTED PAIR ACTUATOR INTERFACE BELDEN 9535 24 AWG 5 CONDUCTOR DISPLAY TO TERMINAL STRIP BELDEN 9535 24 AWG 5 CONDUCTOR DISPLAY COM1 COM2 FROM TERM STRIP TO DEVICES BELDEN 8770 18 AWG 3 CONDUCTOR TEMP CTRL MODBUS BELDEN 8770 18 AWG 3 CONDUCTOR TWIST TO START PUSH TO STOP M34890 24 610 24 610 MANUAL OPERATOR 5K OHMS MANUAL...

Page 6: ...YP7999A1000 CONTROLINKS FUEL AIR RATIO CONTROL PANEL 66 2060 01 6 Fig 2 Wiring diagram part 1 M34891 ...

Page 7: ...tion only It is the responsibility of the end user to provide appropriate protection on the service to this control panel Refer to the National Electric Code and UL Stan dard 1077 for more information 2 Wire to the firing rate actuator must be run in separate conduit L N M34892 Indicates terminals and wiring in control panel main terminal block Indicates external wiring Indicates terminals in valv...

Page 8: ... 66 2060 01 M S 06 13 Printed in United States 3 Ground shield to subbase earth ground screw on low voltage side of subbase 4 Installation operation and maintenance shall conform with National Fire Protection Association standards national and local codes and authorities having jurisdic tion Fig 4 Equipment mounting panel dimensions in in mm 21 533 21 533 3A FU100 FU121 5A 1 FUEL AIR CONTROL SPARE...

Reviews: