HONEYWELL 7000 SOLID STATE ALARM SYSTEM
69-1192—1
7
Connect loop wiring but do not run wiring within 12 in. (305
mm) of house ac wiring.
IMPORTANT
Do not run any wires or cabling behind or across the
control panel printed circuit board.
Point Expansion Module (PEM) Installation
The PEM provides additional hardwire points for the
Honeywell 7000 System and can be used in place of, or in
conjunction with, the RF transmitters and receivers. The PEM
DRYWALL
OR PLYWOOD
NOT
SUPPLIED
PEM (COVER
REMOVED)
ANCHORS
M10912
MOUNTING SLOTS
ON BACK OF RFEM
can support normally open (NO) or normally closed (NC)
sensor contacts. The PEM has eight hardwire point
connections and two relay output connections.
Mount the PEM plastic box within 250 feet (76 meters) of the
control panel if using 22 AWG wire or 500 feet (152 meters) if
using 18 AWG wire.
Remove the PEM circuit board from the PEM plastic box (if
installed) and use the PEM plastic box to mark the mounting
screw locations on the wall or plywood. Use two screws (not
supplied) to mount the PEM plastic box. Insert the PEM
circuit board into the PEM plastic box. See Fig. 5.
Fig. 5. Installing the PEM plastic box.