Table 2. Input loop point types.
Fire Circuits
The Honeywell 7000 System directly supports certain
specified two-wire fire detectors. Four-wire detectors require
special wiring and programming arrangements for resetting
smoke detectors.
Two-Wire Smoke Detector Circuit
The Honeywell 7000 System directly supports one two-wire
fire circuit (loop 8 on the control panel). Use the following
approved smoke detector models and refer Fire Marshals to
the compatibility ID shown in Table 3. The compatability ID for
the Honeywell 7000 System is 7K8.
Table 3. Two-wire smoke detectors and compatibility ID.
2.
Use UL-listed 18 AWG energy limited cable (Signal
Cable Co. No. 98804, for example) to wire a maximum
of 10 two-wire smoke detectors within 200 feet of the
control panel.
3.
Attach the 5.1 Kilohm, 1/4 watt EOLR (provided) at the
last smoke detector.
4.
Wire detectors as shown in Fig. 15.
15
16
EOLR
TB1
P8 –
P8 +
M10900
SMOKE
DETECTOR
MAXIMUM OF 10
2 WIRE
SMOKE DETECTORS
5.1 K
5%
1.4W
SMOKE
DETECTOR
–
+
–
+
–
+
–
+
Fig. 15. Wiring diagram for two-wire smoke detectors.
Type
Description
Perimeter
A burglary circuit that instantly alarms on cross or break when violated.
Entry/Exit 1
A burglary circuit that signals a warning for time period 1 before alarming.
Entry/Exit 2
A burglary circuit that signals a warning for time period 2 before alarming.
Interior
A burglary circuit that is ignored during the exit and entry delay periods.
Interior Delay
A burglary circuit that signals a warning for time period 2 when violated and is ignored during the
normal exit and entry delay periods.
Tamper
A burglary circuit that is always on. Violation of this point will be reported but the local audible alarm
can be optioned to be silenced.
Police
A burglary alarm that instantly alarms on cross or break when violated. The audible alarm is
selectable separately.
Fire
A fire circuit that instantly alarms on cross and signals a trouble on break.
Medical/Special
A circuit that instantly alarms with a separate audible sound.
Equipment Supervisory
A circuit that instantly alarms with a separate audible sound.
Strategy (Mode):
An input that invokes a specified security mode.
Smart
A burglary point or zone that can be part of the complete security as well as operated separately by
Special Protection Modes. Used for protecting an isolated door (to let pets out, for example), as well
as protection for the home office, bar, gun rack, workshop, etc. This point alarms instantly when
occupants are away and sounds a warning for time period 2 when persons are at home.
Pool
Violation of the point causes the keypad audible to sound throughout the house for 30 seconds
when occupants are home and the keypads, bell or siren to sound for 30 seconds when occupants
are away. Requires a separate device to be installed to delay the audible on entry or briefly bypass
the audible on exit by an adult. Available from Safeguard Innovations: (612) 784-7786.
Two-Wire Fire Circuit Installation
1.
Install smoke and heat detectors in accordance with
manufacturer instructions.
Manufacturer
Model
Compatibility ID
Sentrol
429A, 429AT
S10A
Detection
Systems
DS250, DS250TH,
DS50HD Detectors
B
MB2W, MB2WL Bases
A