CN20, CN34 SERIES DAMPER ACTUATOR FOR MODULATING AND FLOATING CONTROL 

EN0B-0341CH33 R0803A 

Stroke Limitation with Mechanical End Limits 

The mechanical end limits enable the stroke to be limited 

from 0...90° in increments of 5°. 

 

Wiring 

Connecting to the Power Supply 

In order to comply with protection class II, the power source of 

24 V actuators must be reliably separated from the network 

power supply circuits as per DIN VDE 0106, part 101. 

 

Access cover 

To facilitate wiring the actuator to the controller, the access 

cover can be detached from the actuator. 

 

IMPORTANT 

Remove power before detaching the access cover. 

Once the access cover has been removed, please 

take care to avoid damaging any of the parts now 

accessible. 

 

Fig. 12. Access cover(models with internal switches) 

 

Depending upon the model, the access cover may have one 

or two terminal strips, including a layout with a description for 

each of the terminals. 

 

 

Fig. 13. Actuator with access cover removed 

(

models with internal switches)

 

OPTIONAL ACCESSORIES 

The following optional accessories can be ordered separately. 

 

Auxiliary Switch Kit 

Order no.: SW2 

 

S1

S2

S3

A
B

S4
S5

S6

C
D

45

0

90

90

0

A

B

C

D

 

 

The auxiliary switches are field-installable parts providing two 

SPDT freely-adjustable switches. 

 

SPARE PARTS 

Spare Parts Kit 

Order no.: A7209.2071 

The spare parts kit contains the following items: 

 

 

Anti-rotation bracket and screws 

 

Access cover screw 

 

Plastic protective cap for protection standard IP54 

 

Mechanical end limit screw and retainer 

 

Anti-Rotation Bracket Kit 

Order no.: A7209.2073 

The anti-rotation bracket kit can be ordered separately. 

 

Contains: 

 

10 anti-rotation brackets 

 20 

screws 

 

 

Summary of Contents for CN34 Series

Page 1: ...Supply voltage 24 Vac dc 15 50 60 Hz Nominal voltage 24 Vac dc 50 60 Hz All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN7220A2007 6 VA 3 W CN7234A2008 6 VA 3 W Ambient limits Ambient operating limits 20 60 C 5 140 F Ambient storage limits 40 80 C 40 175 F Relative humidity 5 95 non condensing Safety Protection standard IP54 as per EN 60529 Prot...

Page 2: ...liary Switches 2 Two Internal Auxiliary Switches XX System Controlled Numbers C N 72 20 A 2 0 XX Fig 1 Product Identification System OPERATION FUNCTIONS Legend for Fig 2 1 Self centering shaft adapter 2 Retainer clip 3 Rotational angle scales 0 90 90 0 4 Mechanical end limits 5 Declutch button 6 Anti rotation bracket 7 Function Selection Switch 8 Access cover Contents of Package The delivery packa...

Page 3: ... function selection switch setting Table 2 describes the actuator behavior stops rotates CCW or rotates CW for the 2 position mode in relation to the control signals applied to terminals 3 and 4 and to the function selection switch setting Table 3 describes the actuator behavior stops rotates CCW rotates CW runs in proportional position or runs to 0 of max stroke for the modulating mode in relatio...

Page 4: ... see Fig A1 the control signal s value rises up into the upper dead band i e to more than the max control signal minus 0 14V or drops down into the lower dead band i e to less than the min control signal plus 0 14V and if the shaft adapter can remain at the respective upper or lower mechanical end limit at least 3 seconds the actuator will recognize the new position automatically and auto adaption...

Page 5: ...d Internal End Switches NOTE Applicable to models with internal switches only The internal end switches are set to change from common to normally open at angles of 5 and 85 respectively from the totally counterclockwise position 5 10 15 92 5 0 90 2 5 85 80 75 85 80 75 2 5 90 0 92 5 5 10 15 5 10 15 0 90 85 80 75 CCW internal end switch CW internal end switch actuator scale clockwise end switch scal...

Page 6: ...le Fig 12 Access cover models with internal switches Depending upon the model the access cover may have one or two terminal strips including a layout with a description for each of the terminals Fig 13 Actuator with access cover removed models with internal switches OPTIONAL ACCESSORIES The following optional accessories can be ordered separately Auxiliary Switch Kit Order no SW2 S1 S2 S3 A B S4 S...

Page 7: ...d in the preceding wiring diagrams Function selection switch Terminal Modulating Floating 2 position 1 24 V power unused unused 2 common common common 3 0 2 10 V control 24 V control signal 24 V control signal 4 24 V override 24 V control signal 24 V control signal 5 0 2 10 V feedback unused unused NOTE All cables connected to these terminals must be equipped with spark suppression Connecting cabl...

Page 8: ...stion Controls Division of Honeywell Technologies Sàrl Ecublens Route du Bois 37 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell International Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C EN0B 0341CH33 R0803A DIMENSIONS ...

Reviews: