CN20, CN34 SERIES DAMPER ACTUATOR FOR MODULATING AND FLOATING CONTROL 

EN0B-0341CH33 R0803A 

MODELS 

Model # 

Description 

CN7220A2007 

20Nm,24Vac/Vdc, Modulating and floating/2-position control, Non-Spring return, Voltage Feedback 
Signal and without aux. Switch 

CN7234A2008 

34Nm,24Vac/Vdc, Modulating and floating/2-position control, Non-Spring return, Voltage Feedback 
Signal and without aux. Switch 

 

 

PRODUCT IDENTIFICATION SYSTEM 

C

 – Direct Coupled Actuator 

N

 – Fail Safe Function (Non-Spring Return) 

61

 – 24V Floating/2-position Control 

72

 – 24V Modulating and Floating/2-position Control 

46

 – 230V Floating/2-position Control 

20

 – 20 Nm (177 lb-in) 

34

 – 34 Nm (300 lb-in) 

A

 – Standard Model 

1

 – No Feedback 

2

 – Voltage Feedback Signal 

0

 – No Internal Auxiliary Switches 

2

 – Two Internal Auxiliary Switches 

XX

 – System Controlled Numbers 

 

C

 

N

 

72

 

20

 

A

 

2

 

0

 

XX

 

 

Fig.1. Product Identification System 

OPERATION / FUNCTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
Legend for Fig.2: 

Self-centering shaft adapter 

2 Retainer 

clip 

Rotational angle scales (0...90° / 90...0°) 

Mechanical end limits 

5 Declutch 

button 

6 Anti-rotation 

bracket 

Function Selection Switch 

8 Access 

cover 

 

Contents of Package 

The delivery package includes the actuator itself, parts 1 

through 8 (see Fig.2), the anti-rotation bracket screws, and 

installation instruction. 

 

RUN MODES 

The function selection switch (see Fig 3) is used to place the 

actuator into any one of five different modes: 

  2-10V, modulating control; floating/2-position control, cw 

run 

  0-10V/Dir, modulating control; floating/2-position control, 

cw run 

  Service/Off, actuator stop running 

  10-0V/Rev, modulating control; floating/2-position control, 

ccw run 


7 8 

Fig. 2. Setting units and control elements 

Summary of Contents for CN34 Series

Page 1: ...Supply voltage 24 Vac dc 15 50 60 Hz Nominal voltage 24 Vac dc 50 60 Hz All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN7220A2007 6 VA 3 W CN7234A2008 6 VA 3 W Ambient limits Ambient operating limits 20 60 C 5 140 F Ambient storage limits 40 80 C 40 175 F Relative humidity 5 95 non condensing Safety Protection standard IP54 as per EN 60529 Prot...

Page 2: ...liary Switches 2 Two Internal Auxiliary Switches XX System Controlled Numbers C N 72 20 A 2 0 XX Fig 1 Product Identification System OPERATION FUNCTIONS Legend for Fig 2 1 Self centering shaft adapter 2 Retainer clip 3 Rotational angle scales 0 90 90 0 4 Mechanical end limits 5 Declutch button 6 Anti rotation bracket 7 Function Selection Switch 8 Access cover Contents of Package The delivery packa...

Page 3: ... function selection switch setting Table 2 describes the actuator behavior stops rotates CCW or rotates CW for the 2 position mode in relation to the control signals applied to terminals 3 and 4 and to the function selection switch setting Table 3 describes the actuator behavior stops rotates CCW rotates CW runs in proportional position or runs to 0 of max stroke for the modulating mode in relatio...

Page 4: ... see Fig A1 the control signal s value rises up into the upper dead band i e to more than the max control signal minus 0 14V or drops down into the lower dead band i e to less than the min control signal plus 0 14V and if the shaft adapter can remain at the respective upper or lower mechanical end limit at least 3 seconds the actuator will recognize the new position automatically and auto adaption...

Page 5: ...d Internal End Switches NOTE Applicable to models with internal switches only The internal end switches are set to change from common to normally open at angles of 5 and 85 respectively from the totally counterclockwise position 5 10 15 92 5 0 90 2 5 85 80 75 85 80 75 2 5 90 0 92 5 5 10 15 5 10 15 0 90 85 80 75 CCW internal end switch CW internal end switch actuator scale clockwise end switch scal...

Page 6: ...le Fig 12 Access cover models with internal switches Depending upon the model the access cover may have one or two terminal strips including a layout with a description for each of the terminals Fig 13 Actuator with access cover removed models with internal switches OPTIONAL ACCESSORIES The following optional accessories can be ordered separately Auxiliary Switch Kit Order no SW2 S1 S2 S3 A B S4 S...

Page 7: ...d in the preceding wiring diagrams Function selection switch Terminal Modulating Floating 2 position 1 24 V power unused unused 2 common common common 3 0 2 10 V control 24 V control signal 24 V control signal 4 24 V override 24 V control signal 24 V control signal 5 0 2 10 V feedback unused unused NOTE All cables connected to these terminals must be equipped with spark suppression Connecting cabl...

Page 8: ...stion Controls Division of Honeywell Technologies Sàrl Ecublens Route du Bois 37 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell International Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C EN0B 0341CH33 R0803A DIMENSIONS ...

Reviews: