Updating CIU 888 Site configuration
Part No.: 4417593_Rev09
Ensite Pro to CIU 888 Migration Manual
CIU 888
4 - 1
$*6
CHAPTER 4 UPDATING CIU 888 SITE CONFIGURATION
If there are changes in the CIU 888 system setup, these changes must
be implemented in the site configuration. Subsequently, the updated
site configuration must be uploaded to the CIU 888 for the changes to
become effective.
Changes in the CIU 888 system setup can be the result of, for example:
Connection of additional tank gauging instruments to the CIU 888
Connection of additional host systems to the CIU 888
Installation of a new CIU 888 license resulting in the expansion of the
features and functionalities of the CIU 888 (e.g. redundancy, support
of a larger number of tanks)
The procedure for updating the CIU 888 site configuration consists of
the following steps:
1. Implementing the required changes in the site configuration and
regenerating the INI files, see section 4.2
2. Regenerating the INI files required for Entis Pro, see section 4.3
3. Uploading the updated site configuration to the CIU 888, see
4. If required, configuring the additional configuration settings, see
5. Updating the INI files required for Entis Pro, see section 4.6
6. Restarting the Entis Pro system connected to the CIU 888, and
reloading the INI files in Entis Pro, see section 4.7
7. Sealing the CIU 888, see section 4.8
8. Verifying the working of the system setup, see section 4.9
4.1 Requirements for updating the CIU 888 site configuration
The following requirements must have been met in order to update the
CIU 888 site configuration:
The CIU 888 must be switched on. See section 5.1.1 for more
information.
Both the W&M lock key switch and the Configuration lock key switch
of the CIU 888 must be in ‘unlocked’ position. See section 5.2 for
more information.
A PC/laptop running the CIU 888 Configuration System must be
connected to the Service port of the CIU 888 using a Cat. 5 Ethernet
cable (patch or crossover). The Service port is located at the front of