Commissioning of a Standalone System Setup
Ensite Pro to CIU 888 Migration Manual
Part No.: 4417593_Rev09
2 - 22
CIU 888
$*6
3. Click
OK
to close the dialogue box.
2.8 Restarting Entis Pro and loading the updated INI files in Entis Pro
When the INI files have been updated, the next step is to restart the
Entis Pro system connected to the CIU 888 and then load the updated
INI files in Entis Pro. Refer to the
Configuration manual Entis Pro
version 2.70x for Windows 7
(Part No. 4416381) for more information.
2.9 Sealing the CIU 888
If the CIU 888 features the option to be sealed, the next step is to have
it sealed by a representative of the W&M authorities or by a W&M
accredited user. Refer to the
CIU 888 Sealing Guide
(Part No. 4417595)
for more information.
NOTE: If the CIU 888 does not feature the option to be sealed, the W&M configuration
settings can either be locked or left unlocked.
2.10 Verifying the working of the system setup
The final step in the commissioning procedure is verifying if the CIU 888
system setup is working properly.
To verify the working of the system setup, the CIU 888 must be
connected to:
PC/laptop running the CIU 888 Configuration System via:
Service port located at the front using a Cat. 5 Ethernet cable,
and
One of the serial host ports located at the back using a serial
cable (see FIGURE 2-20)
FIGURE 2-20
CIU 888: serial host ports
Procedure:
1. Launch the CIU 888 Web interface. See section 1.4.2 for more
information.