background image

T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS

11

69-1510-4

TROUBLESHOOTING GUIDE

Table 6. Troubleshooting Guide.

Symptom

Possible Cause

Action

Display will not 
come on.

Thermostat is not being 
powered.

• Check if batteries are present and installed correctly.

— If batteries are present and installed correctly, replace 

thermostat.

Temperature 
display is incorrect.

Room temperature display has 
been reconfigured.

Enter Installer Setup number 37 and reconfigure the display.

Thermostat is configured for °F 
or °C display.

Enter Installer Setup number 14 and reconfigure the display.

Bad thermostat location.

Relocate the thermostat.

Temperature 
settings will not 
change. (Example: 
Cannot set the 
heating higher or 
the cooling lower.)

The upper or lower temperature 
limits were reached. 

Check the temperature setpoint:

• Heating limits are 4.5 to 32°C
• Cooling limits are 7 to 37°C

The setpoint temperature range 
stops were configured.

Check Installer Setup numbers 34 and 35 and reconfigure the 
setpoint stops.

Heating will not 
come on.

No power to the thermostat.

• Check for 24 Vac between R and W terminals (check for      

750 mV on PowerPile

®

 Systems).

— If missing 24 Vac:

— check if the circuit breaker is tripped—reset the circuit 

breaker.

— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is in 

the Off position—set to the On position.

— check wiring between thermostat and HVAC 

equipment—replace any broken wires and tighten any 
loose connections.

— If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is 
activated.

Wait up to five minutes for the system to respond.

System selection is not set to 
Heat.

Set system selection to Heat.

Heating setpoint is below room 
temperature.

Check heating setpoint. Set heating setpoint to desired 
temperature.

Cooling will not 
come on.

No power to the thermostat.

• Check for 24 Vac between R or RC and Y terminals 

— If missing 24 Vac:

— check if the circuit breaker is tripped—reset the circuit 

breaker.

— check if the system fuse is blown—replace the fuse. 
— check if the power switch on the HVAC equipment is in 

the Off position—set to the On position.

— check wiring between thermostat and HVAC 

equipment—replace any broken wires and tighten any 
loose connections.

— If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is 
activated.

• Wait up to five minutes for the system to respond.
• Enter Installer Setup number 33. Reconfigure minimum off 

time (if required).

System selection is not set to 
Cool.

Set system selection to Cool.

Cool setpoint is above room 
temperature.

Check cooling setpoint. Set cooling setpoint to desired 
temperature.

Heating or cooling 
come on 
momentarily and 
shut off.

Heat or cool circuit is opening 
up or becoming high 
impedance.

Add resistor in parallel with load or install interface relay.

Summary of Contents for Chronotherm IV T8602D

Page 1: ...tat about 1 5m 5 ft above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat Wallplate Installation Th...

Page 2: ... Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to pre vent drafts from affecting the thermostat Fig 3 Typical hookup in heat and cool system with two transformers 1 5 METERS 5 FEET YES NO NO NO M10856 WIRES THROUGH WALL WALL MOUNTING HOLES M15044 MOUNTING SCREWS WALL ANCHORS 2 L1 HOT L2 M10855 FAN RELAY Y G THERMOSTAT RC HEA...

Page 3: ...PPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CAN BE USED FOR CHANGEOVER VALVE ON SINGLE STAGE HEAT PUMP SYSTEMS AVAILABLE ON SELECT MODELS OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE 2 2 2 1 3 OT OT OUTDOOR TEMPERATURE SENSOR 3 RC W MILLIVOLT HEATING ONLY WALLPLATE R M2931 TH TH PP PP MILLIVOLTAGE GAS CONTROL LIMIT CONTROL MILLIVOLTAGE GENERATOR PILOTSTAT CON...

Page 4: ...sly Auto Fan operates with equipment Fig 10 Thermostat System and Fan key locations NOTE Always press the keys with your fingertip or sim ilar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard M14624 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy INCREASE TEMPERATURE SETTING OR S...

Page 5: ...ed See Fig 11 and 12 To advance to the next Installer Setup press the Time key To change a setting use the increase or decrease key To scroll the Installer Setup numbers backward press the Time key To exit the Installer Setup press Run Program Fig 11 Display of all LCD segments Fig 12 Display of Installer Setup number and setting CAUTION Electric Heat Configuration Hazard Can cause equipment damag...

Page 6: ...uto only Adaptive Intelligent Recovery control 13 1 Conventional recovery system starts recovery at programmed time Adaptive Intelligent Recovery control is activated system starts early so setpoint is reached by start of program period Not Used 14 thru 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not Used 17 thru 23 Outdoor temperature display select models 24 0 No outdoor tem...

Page 7: ...s to 1 5 C higher than actual room temperature 5 Display adjusts to 5 C lower than actual room temperature 1 0 Display adjusts to 1 0 C lower than actual room temperature 1 5 Display adjusts to 1 5 C lower than actual room temperature Furnace Air Filter Timer 43 0 Off 1 2 3 4 1 10 days 2 30 days 3 60 days 4 120 days Time counted when heat cool or fan is running Humidifier Pad Monitor 44 0 Off 1 2 ...

Page 8: ...gram to exit the System Test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Set Day Time Mon PM M14620 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Day Heat Cool Settings Daylight Time Copy Set Day Time PM Tue M14621 Time Set Pr...

Page 9: ...escription Heating Equipment System Test Time 10 Enter heating equipment system test 11 Heat comes on When Installer Setup number 2 is 1 the system fan is also energized 10 Heat and system fan turn off Cooling Equipment System Test Time 30 Change from heating to cooling equipment system test 31 Cool and system fan come on 30 Cool and system fan turn off Fan Equipment System Test Time 40 Change fro...

Page 10: ... identification code Example 02 software ID code 2 4 Press the increase key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the system test The system test times out after four minutes without any key presses CHECKOUT Outdoor Temperatur...

Page 11: ...C equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the system to respond System selection is not set to Heat Set system selection to Heat Heating setpoint is below ...

Page 12: ... fan operation Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint Wait a minute after seeing the on indicator and then check the registers Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermosta...

Reviews: