System on indicator
(flame=heat,
snowflake=cool) is
displayed, but no
warm or cool air is
coming from the
registers.
Fan operation set for 0 (con-
ventional heat) when it should
be set for 1 (electric heat).
Enter Installer Setup number 2 and reconfigure the fan
operation.
Conventional heating equipment
turns on the fan when the
furnace has warmed up to a
setpoint.
Wait a minute after seeing the on indicator and then check the
registers.
Heating or cooling equipment is
not operating.
Verify operation of heating or cooling equipment in self-test.
Outdoor tempera-
ture not displayed
a
Option not activated.
Enter Installer Setup number 24 and set to 1. Thermostat must
have OT terminals and a C7089B1000 Sensor installed.
Outdoor
temperature
display is incorrect
a
Outdoor sensor is connected
incorrectly.
Refer to C7089B1000 Installation Instructions and check wiring
between the thermostat and sensor.
Wrong sensor.
Replace sensor with C7089B1000 Sensor.
a
Select models.
Table 6. Troubleshooting Guide. (Continued)
Symptom
Possible Cause
Action