USER'S MANUAL FOR HTML5 PANELS WEB-HMI CAPACITIVE TOUCH SCREEN
11
EN2Z-1070GE51 R0920
Electromagnetic Compatibility (EMC)
Table 7. Electromagnetic Compatibility (EMC)
Radiated disturbance test
Class A
CISPR 22
CISPR 16-2-3
Electrostatic discharge
immunity test
8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
EN 61000-4-2
Radiated, radio-frequency,
electromagnetic field
immunity test
80 MHz … 1 GHz, 10V/m
1.4 GHz … 2 GHz, 3 V/m
2 GHz … 2.7 GHz, 1 V/m
EN 61000-4-3
Burst immunity test
± 2 kV dc power port
± 1 kV signal line
EN 61000-4-4
Surge immunity test
± 0.5 kV dc power port (line to earth)
± 0.5 kV dc power port (line to line)
± 1 kV signal line (line to earth)
EN 61000-4-5
Immunity to conducted
disturbances inducted by
radio-frequency field
0.15 … 80 MHz, 10 V
EN 61000-4-6
Power frequency magnetic
field immunity test
Enclosure, 50/60 Hz, 30 A/m
EN 61000-4-8
Voltage dips, short
interruptions and voltage
variations immunity test
Port: AC mains; Level:
100% duration:
1 cycle and 250 cycles (50Hz);
1 cycle and 300 cycles (60Hz);
40% duration:
10 cycles (50Hz);
12 cycles (60Hz);
70% duration:
25 cycles (50Hz);
30 cycles (60Hz);
Phase:
0°…180°
Test executed on the 230 Vac side of the Power Supply
EN 61000-4-11
Port: DC mains; Level:
0% duration:
10 ms, 20 interruptions in 1 s
Durability information
Table 8. Durability information
Backlight service life
(LED type)
40 000 Hrs. or more
(LED type) (Time of continuous operation until the brightness of the
backlight reaches 50% of the rated value when the surrounding air
temperature is 25°C) - see note below.
NOTE:
Extended use in environments where the surrounding air temperature is 40°C or higher may
degrade backlight quality/reliability/durability.