background image

C7772A, F, G WALLPLATE TEMPERATURE SENSOR

3

68-0213—04

Table 1. C7772 Models.

NOTE: TCR = temperature coefficient of resistance.

Mounting

To mount on conduit box (see Fig. 2):

1. Remove the appropriate knockout on the standard utility 

conduit box for the application.

2. Make wiring connections to the system components.

IMPORTANT

Level only for appearance. The sensor functions 

normally even when not level.

3. Use the No. 6 screws provided to mount the wallplate to 

the conduit box.

Wiring

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment 

circuitry.

Disconnect all power supplies before installation.

CAUTION

Erratic System Operation Hazard.

Failure to follow proper wiring practices can introduce 

disruptive electrical interference (noise).

Keep wiring at least one foot away from large inductive 

loads such as motors, line starters, lighting ballasts, 

and large power distribution panels.

Shielded cable is required in installations where these 

guidelines cannot be met.

Ground shield only to grounded controller case.

IMPORTANT

• Temperature sensor wiring can be sized from 

16 to 20 AWG depending on the application.

• The maximum length of wire from a device to the 

wallplate sensor is 300 ft (91m).

NOTE: Erratic temperature readings from a sensor can be 

caused by the wiring practices described below. 

These must be avoided to assure proper operation:

1.

Do not route temperature sensor wiring with 

building power wiring, next to control contactors, 

near light dimming circuits, electric motors or 

welding equipment.

2.

Avoid poor wiring connections.

3.

Do not mount sensor in an incorrect environment.

Connect the low voltage wiring from the controller terminals to 

the sensor screw terminals and tighten. See Fig. 2.

Fig. 2. Mounting, wiring for C7772.

OPERATION

The C7772 Wallplate Temperature Sensor provides a resistive 

output signal proportional to the sensed room temperature.

Model

Sensor Type

Nominal Resistance

Resistance-Temperature 

Curve Type

Lead Wire 

Color

C7772A

20K NTC Thermistor

20,000 ohms at 77°F (25°C)

Non-linear Negative TCR

Green/Blue

C7772F

10K Ohm NTC Type II Thermistor

10,000 ohms @ 77°F (25°C)

Non-linear Negative TCR

Green/White

C7772G

10K Ohm NTC Type III Thermistor

10,000 ohms @ 77°F (25°C)

Non-linear Negative TCR

White/White

STANDARD UTILITY

CONDUIT BOX

CONNECTOR

LOCKNUT 

AND

CONDUIT

TO APPROPRIATE 

SYSTEM 

COMPONENTS

BLANK

FACEPLATE

M16296

Summary of Contents for C7772A

Page 1: ... and other controllers that require a 10K ohm NTC Type III sensor The C7772 sensors provide a resistive output signal proportional to sensed room or space temperature The C7772 is well suited for low profile wall mounted applications where durability and tamper proof construction is desired such as schools prisons and institutions FEATURES Low profile when mounted on industry standard utility cond...

Page 2: ...no appreciable drift thereafter No calibration of the device is possible Long term drift calibration maintenance through controller software is typically not necessary Humidity Ratings 5 to 95 rh non condensing Approvals National Electrical Code NEC Class II Fig 1 C7772 Dimensions in in mm INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could da...

Page 3: ...sized from 16 to 20 AWG depending on the application The maximum length of wire from a device to the wallplate sensor is 300 ft 91m NOTE Erratic temperature readings from a sensor can be caused by the wiring practices described below These must be avoided to assure proper operation 1 Do not route temperature sensor wiring with building power wiring next to control contactors near light dimming cir...

Page 4: ...ons are made Use an accurate thermometer of 1 F 0 5 C to measure the temperature at the sensor location To verify sensor accuracy use an ohmmeter to measure the resistance across the sensor wires and use Table 2 to check the accuracy of the specific model Table 2 Typical Resistance of Sensor Models Typical Resistance in ohms C7772A C7772F C7772G At 41 F 5 C 54 200 25 392 23 467 At 50 F 10 C 41 758...

Reviews: